The following parameters are displayed in the parameter list but cannot be modified:
Usoll-Konst /
Vconst-
Setpoint
V
150 ... 430
330 ... 410
Desired DC voltage for constant
operational voltage. These parameters
are only important when the
"Betriebsart" parameter is set to U-
Konst.
U
PV
Start
V
150 ... 400
180
U
PV
Start is the parameter defining the
voltage at which the Windy Boy is
capable of connecting to the system.
180 V is the recommended voltage for
the Windy Boy 1100 and the Windy
Boy 1700. Reducing this voltage
parameter can lead to numerous
unnecessary connection attempts.
Increasing this voltage parameter can
lead to energy losses since the Windy
Boy does not immediately connect to
the system.
Name
Unit
Value range
(WB1100/
1700)
Factory
settings
(WB1100/
1700)
Description
Plimit
W
1100 / 1700
Upper limit for AC output power
SMA-SN
Serial number of the Windy Boy
Software-BFR
Firmware version of the operation
control unit (BFR)
Software-SRR
Firmware version of the current control
unit (SRR)
Name
Unit
Value range
(WB 1100 /
WB 1700)
Factory
settings
(WB 1100 /
WB 1700)
Description
Содержание Windy Boy 1100
Страница 2: ......
Страница 4: ...SMA Technologie AG Page 4 WB11_17 11 FE4205 Operating Instructions...
Страница 12: ...Safety Information SMA Technologie AG Page 12 WB11_17 11 FE4205 Operating instructions...
Страница 30: ...Setting the display language SMA Technologie AG Page 30 WB11_17 11 FE4205 Operating instructions...
Страница 36: ...Turbine operation SMA Technologie AG Page 36 WB11_17 11 FE4205 Operating instructions...
Страница 38: ...Maintenance and care SMA Technologie AG Page 38 WB11_17 11 FE4205 Operating instructions...
Страница 64: ...Stand alone systems SMA Technologie AG Page 64 WB11_17 11 FE4205 Operating instructions...
Страница 66: ...Contact SMA Technologie AG Page 66 WB11_17 11 FE4205 Operating instructions...
Страница 67: ......