10. Tighten the AC terminal blocks in the inverter with the following torques:
11. Check that all terminals have the correct wiring and that the cables are secure.
208 V and 240 V System Configuration
Do not connect the Sunny Boy 8000-US to a 208 V grid.
6. Connect the white cable of the DC disconnect to the
terminal labeled N. Connect the black cable of the
DC disconnect to the terminal labeled L1.
7. Connect the red insulated conductor to the terminal
labeled L2.
277 V System Configuration
8. Connect the white cable of the DC disconnect to the
terminal labeled N. Connect the black insulated
conductor of the DC disconnect to the terminal
labeled L1.
9. Connect the red insulated conductor to the terminal
labeled
.
Gray terminal blocks (Weidmüller)
10 … 6 AWG: 18 in-lb. (2 Nm)
Green terminal blocks (Phoenix)
8 … 6 AWG: 40 in-lb. (4.5 Nm)
10 AWG: 2 in-lb. (2.5 Nm)
1
2
3
4
UNGROUNDED
GROUNDED
L1 L2 N
2 3 5 7
A B + -
GROUNDING
ELECTRODE
CONDUCTOR
COMBINED
2
4
0
V
2
7
7
V
2
0
8
V
L1
N
1
2
3
4
UNGROUNDED
GROUNDED
L1 L2 N
2 3 5 7
A B + -
GROUNDING
ELECTRODE
CONDUCTOR
COMBINED
2
4
0
V
2
7
7
V
2
0
8
V
L2
X
X
X
1
2
3
4
UNGROUNDED
UNGROUNDED
GROUNDED
GROUNDED
L1 L2 N
2 3 5 7
A B + -
GROUNDING
GROUNDING
ELECTRODE
ELECTRODE
CONDUCTOR
CONDUCTOR
COMBINEDCOMB
INED
0
V
24
0
V
2
0
8
V
2
7
7
V
0
V
2
4
0
V
black
Содержание SUNNY BOY 5000-US
Страница 2: ......
Страница 10: ......
Страница 104: ...SMA America LLC Installation Manual SB50US 80US IA en 36 104 4 NFSJDB 1SPEVDUJPO XXX 4 NFSJDB DPN...