SMA New Energy Technology (Jiangsu) Co., Ltd.
7
SMASOLID-Q-Modbus-TI-en-10 | Version 1.0
Technical Information
4 = Fixed Q value
5 = Q(U) curve
30044
Active Power Mode
0 = None
1 = Fixed Active Power
U16
-
- RO
30047 Version of Protocol
U16
-
- RO
30048 String 1 Current
U16
A
0.1 RO
30049 String 2 Current
U16
A
0.1 RO
30050 String 3 Current
U16
A
0.1 RO
30051 String 4 Current
U16
A
0.1 RO
30052 String 5 Current
U16
A
0.1 RO
30053 String 6 Current
U16
A
0.1 RO
30054 String 7 Current
U16
A
0.1 RO
30055 String 8 Current
U16
A
0.1 RO
30056 String 9 Current
U16
A
0.1 RO
30057 String 10 Current
U16
A
0.1 RO
30058 String 11 Current
U16
A
0.1 RO
30059 String 12 Current
U16
A
0.1 RO
Read and Write Registers
AD
R
(D
EC
) Description/number code
Ty
pe
Unit
Gai
n
Acc
es
s
40013 0=Power Off / 1=Power On
U16
-
- RW
42021
…
42028
Serial Number (16 digits: 2 ASCII per ADR ..1 to ..8)
ASCII
-
- RW
45001 Grid Code (see Section 4.4)
U16
-
- RW
45007 Grid Voltage High Limit2
U16
V
0.1 RW
45008 Grid Voltage High Limit Time2
U16
ms
20 RW
45009 Grid Voltage High Limit1
U16
V
0.1 RW
45010 Grid Voltage High Limit Time1
U16
ms
20 RW
45011 Grid Voltage Low Limit2
U16
V
0.1 RW
45012 Grid Voltage Low Limit Time2
U16
ms
20 RW