SMA I/O Box Скачать руководство пользователя страница 5

SMA Solar Technology AG / SMA Solar Technology America LLC

3   Inverter Manager

Installation Manual

IMVIOBOX-IA-xx-11

5

3.3.4 Connecting the I/O Box and 

Weather Station (Optional)

Pin assignment of the serial interface (RS485) at the Inverter 
Manager:

The I/O Box must be connected to port 2 of the Inverter 
Manager. Termination for the RS485 interface is not 
necessary.

Interfaces and Data of the Weather Station

Only one weather station can be connected to each Inverter 
Manager. The weather station must be connected to port 1 
of the Inverter Manager. A maximum of two temperature 

sensors are supported. The meteorological data is provided 
depending on the firmware version via the following 
interfaces:

The following data of the weather station are provided by 
the Inverter Manager with firmware version 1.45/1.50:

The following data of the weather station are provided by 
the Inverter Manager with firmware version 1.60:

5

---

TRD(2)-

6

ERx-

TRD(1)-

7

---

TRD(3)+

8

---

TRD(3)-

Do not connect during operation

Do not connect the I/O Box or the weather station to 
the Inverter Manager during operation. Errors might 
occur that cannot be detected immediately.

• Disconnect the Inverter Manager from voltage 

sources.

Pin

Assignment

1

---

2

---

3

DataB(+)

4

DataA(-)

5

GND

6

---

7

---

8

---

Pin

Assignment for 
10/100 Mbps

Assignment for 
1000 Mbps

3

2

1

4

5

9

8

7

6

Firmware

Baud rate

Interfaces

1.45/1.50

9600

• Sunny Portal
• LCS tool
• FTP Push

from 1.60

9600, 19200, 
57600, 115200

• Sunny Portal
• LCS tool
• SunSpec 

Modbus TCP

• FTP Push

Meteorological 
data

SunSpec 
Modbus 
TCP

LCS tool / 
FTP Push

Sunny 
Portal

Ambient 
temperature and 
PV temperature

no

yes

yes

Wind speed and 
wind direction

no

no

no

Horizontal 
irradiation

no

no

no

Inclined 
irradiation

no

yes

yes

Meteorological 
data

SunSpec 
Modbus 
TCP

LCS tool / 
FTP Push

Sunny 
Portal

Ambient 
temperature and 
PV temperature

yes

yes

yes

Wind direction 
and wind speed

yes

yes

yes

Horizontal 
irradiation

yes

yes

If inclined 
irradiation 
is not 
available

Inclined 
irradiation

no

yes

yes

Содержание I/O Box

Страница 1: ...r Manager The I O Box receives commands for grid management services via digital signals and sends these specifications to the Inverter Manager The Inverter Manager receives the specifications from th...

Страница 2: ...mentation is an integral part of this product 3 Inverter Manager 3 1 Scope of Delivery Check the scope of delivery of each product for completeness and any externally visible damage Contact your distr...

Страница 3: ...Option 2 Mounting on Top Hat Rail 3 3 Connection to the Inverter Manager 3 3 1 Safety Information Danger to life due to electric shock Lethal voltages are present at the connection point of the utili...

Страница 4: ...of network ports LAN 1 and LAN 2 LAN1 LAN2 LCS B C D A A A F E RS485 Port 1 Dual Run 1 2 ON Rep Initial RS485 Port 2 SMA INVERTER MANAGER Position Designation A Sunny Tripower 60 B PC with LCS tool C...

Страница 5: ...Manager with firmware version 1 60 5 TRD 2 6 ERx TRD 1 7 TRD 3 8 TRD 3 Do not connect during operation Do not connect the I O Box or the weather station to the Inverter Manager during operation Error...

Страница 6: ...the connecting terminal plate for the voltage supply 9 VDC to 36 VDC Make sure that the shielded grounding conductor is connected with the grounding terminal 4 Plug the connecting terminal plate for...

Страница 7: ...bs Mounting type Wall mounting or top hat rail Operating temperature range 40 C to 75 C 40 F to 167 F Relative humidity non condensing 5 to 95 Approvals UL 508 UL 60950 1 CSA C22 2 No 60950 1 07 EN 60...

Страница 8: ...the I O Box are not protected against splash water Consequently moisture can penetrate the device and damage the products and cables The Inverter Manager and the I O Box must be installed in a dry env...

Страница 9: ...I O Box to the Inverter Manager during operation Errors might occur that cannot be detected immediately Disconnect the Inverter Manager from voltage sources Connect the I O Box with the Inverter Manag...

Страница 10: ...hing green Data is being sent or received Port 2 Flashing yellow Data is being sent or received System data Electricity supply 24 Vdc nominal 12 Vdc to 36 Vdc Cabling I O cable max 4 AWG Dimensions 27...

Страница 11: ...It can take several minutes until the LCS tool has identified all Inverter Managers 2 The screen now shows a list of all Inverter Managers see figure 5 2 To start the assistant click on the Inverter...

Страница 12: ...lation Manual Figure 5 2 LCS tool start screen 3 Assign a password for your user group when first registering The security status of your password is displayed 4 Verify that date and time are correct...

Страница 13: ...5 4 Figure 5 4 LCS tool PV system details 6 A list of the identified inverters of the selected Inverter Manager is displayed See figure 5 5 Make sure that all inverters are present It is possible to...

Страница 14: ...options available for the inverters in the network See figure 5 6 8 Select the desired grid code from the list of options available for the selected country If necessary load a customer specific grid...

Страница 15: ...inverter added at a later stage automatically inherits the same grid code The application of only one grid code is possible per Inverter Manager 11 A green square identifies the commissioned inverter...

Страница 16: ...ager 12 If sufficient PV power is present and the grid code conditions are met the inverters are connected to the grid 13 During commissioning it is possible to download a commissioning report in the...

Страница 17: ...ssword for the user interface you can log in with a Personal Unlocking Key PUK Each user group has its own PUK Procedure 1 Request a PUK see Application for ordering a PUK at www SMA Solar com 2 Open...

Страница 18: ...rating hours and to select a new country data set use your SMA Grid Guard code under the user group Installer see certificate Order form for the SMA Grid Guard code at www SMA Solar com Procedure 1 Op...

Страница 19: ...pdate You can carry out the firmware update of the Inverter Manager manually Procedure 1 Open the LCS tool 2 Log in as User or Installer 3 Call up the menu Service 4 Select the tab Inverter Manager un...

Страница 20: ......

Страница 21: ...arnhinweisen 1 3 Symbole 1 4 Nomenklatur Symbol Erkl rung 3 Warnhinweis dessen Nichtbeachtung unmittelbar zum Tod oder zu schwerer Verletzung f hrt Warnhinweis dessen Nichtbeachtung zum Tod oder zu sc...

Страница 22: ...den Angaben der beigef gten Dokumentationen und gem den vor Ort g ltigen Normen und Richtlinien ein Ein anderer Einsatz kann zu Personen oder Sachsch den f hren Aus Sicherheitsgr nden ist es untersag...

Страница 23: ...Besch digung der Produkte und Leitungen durch Feuchtigkeit Der Inverter Manager und die I O Box sind nicht spritzwassergesch tzt Dadurch kann Feuchtigkeit eindringen und die Produkte und Leitungen bes...

Страница 24: ...s Stelle des ffentlichen Stromnetzes liegen lebensgef hrliche Spannungen an Die Anschluss Stelle freischalten und sicherstellen dass die Anschluss Stelle frei von Spannung ist LAN1 LAN2 LCS B C D A A...

Страница 25: ...er folgende Schnittstellen bereitgestellt Folgende Daten der Wetterstation werden vom Inverter Manager mit Firmware Version 1 45 1 50 bereitgestellt Pin Belegung bei 10 100 Mbps Belegung bei 1 000 Mbp...

Страница 26: ...Das Anschlusskabel an das Netzteil anschlie en siehe Anleitung des Herstellers Dabei die nicht ben tigten Adern bis zum Kabelmantel k rzen und die Aderfarben notieren 3 Das Anschlusskabel an die Klemm...

Страница 27: ...Tx2 P1 P2 Gr n blinkt Daten bertragung ber serielle Ports P1 P2 Aus Keine Daten bertragung ber serielle Ports P1 P2 Rx1 Rx2 P1 P2 Gr n blinkt Datenempfang durch serielle Ports P1 P2 Aus Kein Datenempf...

Страница 28: ...unSpec Modbus TCP Wirk und Blindleistungsvorgabe Konstanter Wert Kurve oder fernsteuerbar ber SunSpec Modbus TCP mit I O Box Netzteil empfohlen Typenbezeichnung CLCON PWRSUPPLY Eingang 100 Vac bis 240...

Страница 29: ...hlie en Sie die I O Box nicht im laufenden Betrieb an den Inverter Manager an Es k nnten Fehler auftreten die nicht sofort erkannt werden Den Inverter Manager spannungsfrei schalten Die I O Box mit de...

Страница 30: ...rmware wird aktualisiert Gr n blinkt Wenn die gr ne LED 5 Sekunden leuchtet und danach f r 5 Sekunden erlischt bedeutet dass dass das System sich im Safe Mode befindet Aus Das System ist nicht betrieb...

Страница 31: ...mehrere Minuten dauern bis das LCS Tool alle Inverter Manager identifiziert hat 2 Der Bildschirm zeigt jetzt eine Liste aller Inverter Manager siehe Abbildung 5 2 Zum Start des Assistenten klicken Sie...

Страница 32: ...S Tool Startbildschirm 3 Vergeben Sie bei der Erstanmeldung ein Passwort f r Ihre Benutzergruppe Der Sicherheitsstatus Ihres Passworts wird Ihnen angezeigt 4 berpr fen ob Datum und Uhrzeit richtig sin...

Страница 33: ...agendetails 6 Eine Liste der durch den ausgew hlten Inverter Manager identifizierten Wechselrichter wird angezeigt Siehe Abbildung 5 5 Pr fen ob alle Wechselrichter vorhanden sind Es ist m glich mit d...

Страница 34: ...e Wechselrichter im Netzwerk Siehe Abbildung 5 6 8 W hlen Sie den gew nschten Grid Code aus der Liste der verf gbaren Optionen f r das ausgew hlte Land aus Im Bedarfsfall einen kundenspezifischen Grid...

Страница 35: ...einem sp teren Zeitpunkt hinzugef gte Wechselrichter bernimmt automatisch denselben Grid Code Pro Inverter Manager ist nur die Anwendung von einem Grid Code m glich 11 Ein gr nes Quadrat macht den in...

Страница 36: ...stung vorhanden ist und die Grid Code Bedingungen erf llt sind werden die Wechselrichter ans Netz angeschlossen 13 Bei Inbetriebnahme ist es m glich einen Inbetriebnahmebericht im Men Reports herunter...

Страница 37: ...haben dann k nnen Sie sich mit einem Personal Unlocking Key PUK einloggen F r jede Benutzergruppe gibt es einen eigenen PUK Vorgehen 1 PUK anfordern siehe Antrag f r die Bestellung einer PUK unter ww...

Страница 38: ...n neuen L nderdatensatz zu w hlen verwenden Sie Ihren SMA Grid Guard Code unter der Benutzergruppe Installer siehe Zertifikat Bestellformular f r den SMA Grid Guard Code unter www SMA Solar com Vorgeh...

Страница 39: ...ate Sie k nnen manuell ein Firmware Update des Inverter Managers durchf hren Vorgehen 1 LCS Tool ffnen 2 Als User oder Installer anmelden 3 Das Men Service aufrufen 4 Unter Software Update die Registe...

Страница 40: ......

Страница 41: ...s indicaciones y advertencias de seguridad 1 3 S mbolos 1 4 Nomenclatura S mbolo Explicaci n 1 30 Advertencia cuyo incumplimiento causa la muerte o lesiones f sicas graves 7 35 Advertencia cuyo incump...

Страница 42: ...observe las normativas y directivas locales vigentes Cualquier otro uso puede causar lesiones al usuario o da os materiales Por razones de seguridad se proh ben las modificaciones del producto as com...

Страница 43: ...El Inverter Manager y la I O Box no est n protegidos contra las salpicaduras de agua Podr a penetrar humedad y da ar los productos y cables El Inverter Manager y la I O Box deben instalarse en entorn...

Страница 44: ...las de las hembrillas de red LAN 1 y LAN 2 LAN1 LAN2 LCS B C D A A A F E RS485 Port 1 Dual Run 1 2 ON Rep Initial RS485 Port 2 SMA INVERTER MANAGER Posici n Denominaci n A Sunny Tripower 60 B Ordenado...

Страница 45: ...on versi n de firmware 1 60 facilitar estos datos de la estaci n meteorol gica 5 TRD 2 6 ERx TRD 1 7 TRD 3 8 TRD 3 No conectar en funcionamiento No conecte la I O Box o la estaci n meteorol gica al In...

Страница 46: ...e los conductores que no sean necesarios hasta el revestimiento del cable y anote el color de los conductores 3 Conecte el cable de conexi n a la caja de bornes del suministro de tensi n de 9 V CC a 3...

Страница 47: ...de puertos en serie P1 P2 Rx1 Rx2 P1 P2 Intermitente en verde Recepci n de datos a trav s de puertos en serie P1 P2 Desactivado Sin recepci n de datos a trav s de puertos en serie P1 P2 Suministro de...

Страница 48: ...rma de potencia efectiva y norma de potencia reactiva Valor constante curva o control remoto a trav s de SunSpec Modbus TCP con I O Box Fuente de alimentaci n recomendado Modelo comercial CLCON PWRSUP...

Страница 49: ...ntener el ajuste de f brica 1 Dual 2 Initial 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 D1 D1 GND D2 D2 P1 P2 V V X10 X1 Dual Run Rep Initial COM0 DI0 DI1 DI2 DI3...

Страница 50: ...DIO2 DIO3 GND DIO4 DIO5 DIO6 DIO7 GND COM0 DI0 DI1 DI2 DI3 DI4 DI5 GND Wet Contact 0 V to 3 V off 10 V to 30 V on U U 10 V to 30 V V V Ready Encendido en verde El sistema est listo para funcionar El v...

Страница 51: ...agen 5 1 Puesta en marcha de inversores con la LCS Tool Entrada digital Tipo de sensor Contacto sin potencial NPN o PNP contacto con potencial Modo I O DI o contador de eventos Contacto sin potencial...

Страница 52: ...Inverter Manager que vaya a configurar Tras seleccionar el Inverter Manager se visualizan los inversores descubiertos por este Los inversores que todav a no se han puesto en marcha no cuentan con un c...

Страница 53: ...CS Tool Instrucciones de instalaci n IMVIOBOX IA xx 11 53 Imagen 5 3 LCS Tool comprobaci n de fecha y hora 5 Si lo desea puede introducir un nombre una sede y un propietario del Inverter Manager Consu...

Страница 54: ...ta aunque no se hayan descubierto todos los inversores Los inversores no descubiertos se pueden configurar m s tarde Imagen 5 5 LCS Tool lista de inversores conectados 7 Seleccione el pa s deseado de...

Страница 55: ...Tool selecci n de pa s y c digo de red 9 La LCS Tool solicita una confirmaci n del pa s y el c digo de red seleccionados Consulte la imagen 5 7 Utilice el bot n Back y la posibilidad de cambiar los a...

Страница 56: ...estos en marcha No obstante los inversores no se conectan a la red hasta que no se les env a un comando de Start desde la barra que hay debajo del men superior Consulte la imagen 5 8 Imagen 5 8 LCS To...

Страница 57: ...s condiciones de ajuste de red los inversores se conectan a la red 13 Tras la puesta en marcha es posible descargar un informe de puesta en marcha en el men Reports El informe contiene toda la informa...

Страница 58: ...o puede iniciar sesi n con una clave personal de desbloqueo PUK Cada grupo de usuario tiene su propia clave personal de desbloqueo PUK Procedimiento 1 Solicite el c digo PUK consulte Solicitud de PUK...

Страница 59: ...rvicio y escoger un nuevo registro de datos nacionales utilice su c digo SMA Grid Guard bajo el grupo de usuarios Installer consulte el certificado Formulario de solicitud del c digo SMA Grid Guard en...

Страница 60: ...al del firmware Puede ejecutar una actualizaci n manual del Inverter Manager Procedimiento 1 Abra LCS Tool 2 Inicie sesi n como User o Installer 3 Acceda al men Service 4 En Software Update escoja la...

Страница 61: ...s curit et les mises en garde 1 3 Symboles 1 4 Nomenclature Symbole Explication 3 Mise en garde dont le non respect entra ne in vitablement des blessures corporelles graves voire mortelles 7 35 44 5 M...

Страница 62: ...vec les normes et directives en vigueur sur le site Tout autre usage peut compromettre la s curit des personnes ou entra ner des dommages mat riels Pour des raisons de s curit il est strictement inter...

Страница 63: ...I O Box ne sont pas prot g s contre les claboussures d eau De l humidit peut donc p n trer dans les produits et les c bles et les endommager Le SMA Inverter Manager et la I O Box doivent tre install s...

Страница 64: ...oches sur les prises r seau LAN 1 et LAN 2 LAN1 LAN2 LCS B C D A A A F E RS485 Port 1 Dual Run 1 2 ON Rep Initial RS485 Port 2 SMA INVERTER MANAGER Position D signation A Sunny Tripower 60 B Ordinateu...

Страница 65: ...avec la version de micrologiciel 1 45 1 50 Les donn es suivantes de la station m t orologique sont fournies par le SMA Inverter Manager avec la version de micrologiciel 1 60 4 TRD 2 5 TRD 2 6 ERx TRD...

Страница 66: ...on voir instructions du fabricant Raccourcissez pour ce faire les conducteurs isol s non utilis s jusqu la gaine de c ble et notez leur couleur 3 Raccordez le c ble de raccordement la plaque bornes d...

Страница 67: ...Aucune activit ou Ethernet 10 Mbps Tx1 Tx2 P1 P2 clignote en vert Transmission de donn es via ports s rie P1 P2 teinte Aucune transmission de donn es via ports s rie P1 P2 Rx1 Rx2 P1 P2 clignote en ve...

Страница 68: ...unSpec Modbus TCP Consigne de puissance active et r active Valeur constante courbe ou commande distance via SunSpec Modbus TCP avec I O Box Bloc d alimentation recommand D signation du type CLCON PWRS...

Страница 69: ...r glages par d faut 1 Dual 2 Initial 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 D1 D1 GND D2 D2 P1 P2 V V X10 X1 Dual Run Rep Initial COM0 DI0 DI1 DI2 DI3 DI4 DI5...

Страница 70: ...6 DI7 COM1 DIO0 DIO1 DIO2 DIO3 GND DIO4 DIO5 DIO6 DIO7 GND COM0 DI0 DI1 DI2 DI3 DI4 DI5 GND Wet Contact 0 V to 3 V off 10 V to 30 V on U U 10 V to 30 V V V Ready allum e en vert Le syst me est op rati...

Страница 71: ...e 5 1 Mise en service des onduleurs avec LCS Tool Entr e num rique Type de capteur Contact libre de potentiel NPN ou PNP contact avec potentiel Mode I O DI ou compteur d v nements Contact libre de pot...

Страница 72: ...ncer l assistant cliquez sur le SMA Inverter Manager configurer En cliquant sur le SMA Inverter Manager les onduleurs d couverts par celui ci s affichent Les onduleurs non mis en service aucun code r...

Страница 73: ...S Tool Instructions d installation IMVIOBOX IA xx 11 73 Figure 5 3 LCS Tool V rification de la date et l heure 5 En option vous pouvez attribuer un nom un site et un titulaire au SMA Inverter Manager...

Страница 74: ...ont pas tous d couverts Les onduleurs non d couverts pourront tre configur s ult rieurement Figure 5 5 LCS Tool Liste des onduleurs connect s 7 S lectionnez le pays souhait dans la liste des options d...

Страница 75: ...ement re oit automatiquement le m me code r seau Un seul code r seau est autoris par SMA Inverter Manager 11 Un carr vert identifie les onduleurs mis en service Cependant les onduleurs ne se connecten...

Страница 76: ...isponible est suffisante et que les conditions de code r seau sont remplies les onduleurs se connectent au r seau 13 Lors de la mise en service il est possible de t l charger un rapport de mise en ser...

Страница 77: ...ez vous connecter l aide d un code PUK Personal Unlocking Key Il existe un code PUK pour chaque groupe d utilisateurs Proc dure 1 Demandez le PUK voir Demande d un code PUK sur www SMA Solar com 2 Ouv...

Страница 78: ...onner un nouveau jeu de donn es r gionales utilisez votre code Grid Guard dans le groupe d utilisateurs Installer voir certificat Formulaire de commande du code Grid Guard sur www SMA Solar com Proc d...

Страница 79: ...ez mettre jour le micrologiciel du SMA Inverter Manager manuellement Proc dure 1 Ouvrez le LCS Tool 2 Connectez vous en tant que User ou Installer 3 Appelez le menu Service 4 Sous Software Update s le...

Страница 80: ......

Страница 81: ...alizzati e grandi impianti FV con una potenza fino a 2 5 MW I O Box un interfaccia funzionale per 1 Inverter Manager I O Box riceve i comandi per la gestione di rete mediante segnali digitali e trasme...

Страница 82: ...cato nella sezione Utilizzo conforme La targhetta di identificazione deve essere applicata in maniera permanente sul prodotto La documentazione in allegato parte integrante del prodotto 3 Inverter Man...

Страница 83: ...83 3 2 2 Variante 2 montaggio su guida DIN 3 3 Collegamento a Inverter Manager 3 3 1 Avvertenza di sicurezza 1 3 0 0 Pericolo di morte per folgorazione Nel punto di connessione alla rete pubblica sono...

Страница 84: ...ei pin sulle prese di rete LAN 1 e LAN 2 LAN1 LAN2 LCS B C D A A A F E RS485 Port 1 Dual Run 1 2 ON Rep Initial RS485 Port 2 SMA INVERTER MANAGER Posizione Denominazione A Sunny Tripower 60 B PC dotat...

Страница 85: ...firmware 1 60 Inverter Manager fornisce i seguenti dati della stazione meteo 5 TRD 2 6 ERx TRD 1 7 TRD 3 8 TRD 3 Non effettuare il collegamento durante il funzionamento Non collegare I O Box o stazion...

Страница 86: ...nduttori non necessari fino alla guaina e annotare i colori 3 Collegare il cavo alla morsettiera di alimentazione di tensione 9 VCC 36 VCC Tenere presente che il conduttore di terra schermato collegat...

Страница 87: ...rasmissione di dati tramite le porte seriali P1 P2 Rx1 Rx2 P1 P2 Lampeggia nte verde Ricezione di dati tramite le porte seriali P1 P2 Spento Nessuna ricezione di dati tramite le porte seriali P1 P2 Al...

Страница 88: ...tal SunSpec Modbus TCP Set point della potenza attiva e reattiva Valore costante curva o regolabile a distanza tramite SunSpec Modbus TCP con I O Box Alimentatore raccomandato Denominazione del tipo C...

Страница 89: ...E Mantenimento delle impostazioni di fabbrica 1 Dual 2 Initial 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 D1 D1 GND D2 D2 P1 P2 V V X10 X1 Dual Run Rep Initial CO...

Страница 90: ...IO6 DIO7 GND COM0 DI0 DI1 DI2 DI3 DI4 DI5 GND Wet Contact 0 V to 3 V off 10 V to 30 V on U U 10 V to 30 V V V Ready Acceso verde Il sistema pronto per il funzionamento Lampeggiante verde 1 volta al se...

Страница 91: ...ndata Figura 5 1 Messa in servizio di inverter per mezzo di LCS Tool Ingresso digitale Tipo di sensore Contatto a potenziale zero NPN o PNP contatto in tensione Modo I O Ingresso digitale o contatore...

Страница 92: ...re clic sull Inverter Manager da configurare Facendo clic sull Inverter Manager vengono visualizzati gli inverter rilevati dall Inverter Manager Gli inverter non messi in servizio senza codice di rete...

Страница 93: ...LC 5 LCS Tool Istruzioni per l installazione IMVIOBOX IA xx 11 93 Figura 5 3 LCS Tool Verificare data e ora 5 A scelta possibile assegnare un nome un ubicazione e un proprietario di Inverter Manager V...

Страница 94: ...sono stati rilevati tutti gli inverter Gli inverter non ancora rilevati possono comunque essere configurati successivamente Figura 5 5 Tool LCS Elenco degli inverter collegati 7 Selezionare il paese...

Страница 95: ...ra 5 6 LCS Tool Selezionare il paese e il codice rete 9 LCS Tool chiede di confermare il paese selezionato e il codice rete V figura 5 7 Una configurazione non corretta pu essere modificata usando il...

Страница 96: ...e identifica gli inverter messi in funzione Tuttavia gli inverter non si collegano a una rete prima che sia inviato il comando Start dalla barra sotto il menu superiore V figura 5 8 Figura 5 8 LCS Too...

Страница 97: ...ettate le condizioni del codice di rete gli inverter si collegano alla rete 13 Dopo la messa in funzione possibile scaricare un rapporto di messa in servizio dal menu Reports Il rapporto contiene tutt...

Страница 98: ...ssibile effettuare l accesso con un codice Personal Unlocking Key PUK Per ogni gruppo di utenti previsto un PUK separato Procedura 1 Richiedere il PUK v modulo di richiesta sul sito www SMA Solar com...

Страница 99: ...ovo record di dati nazionali utilizzare il proprio codice SMA Grid Guard dopo aver selezionato il gruppo di utenti Installer v certificato Modulo di richiesta del codice SMA Grid Guard sul sito www SM...

Страница 100: ...nuale del firmware possibile effettuare un aggiornamento manuale del firmware di Inverter Manager Procedura 1 Aprire LCS Tool 2 Effettuare l accesso come User o Installer 3 Aprire il menu Service 4 Al...

Страница 101: ......

Страница 102: ......

Отзывы: