• In the drop-down list
Signal source
, select the desired signal source. Note that the
desired Modbus server must be activated in the Cluster Controller when you are using the
Modbus (see Section 12.1, page 60).
• In the drop-down list
Predefined Quantity
, select the setpoint
cos Phi
.
6. When using the digital inputs, make the settings for the digital inputs:
• Select the group
Settings of digital inputs
.
• In the field
Failure tolerance time
, enter a value above 1 if possible. This prevents e.g.
a brief, simultaneous activation of two relays of a ripple control receiver during a
Cluster Controller status change being classified as an invalid status.
7. When using the analog inputs, make the settings for the analog inputs:
• Select the group
Settings of analog inputs
.
• In the field
Failure tolerance time
, enter the desired time interval.
• In the field
Initial value input signal
, enter the desired value.
• In the field
Final value input signal
, enter the desired value.
• In the field
Cos Phi start setpoint
, enter the desired value.
• In the drop-down list
Excitation type
, select the desired excitation type.
• In the field
Cos Phi end setpoint
, enter the desired value.
• In the drop-down list
Excitation type
, select the desired excitation type.
8. When using the digital inputs, set the status configuration:
• Select the group
Status configuration
.
☑ The columns
cos Phi
and
Excitation type
are also displayed.
• Depending on the number of digital inputs used in the column
Active
, activate the
selection field of the status to be configured in each case.
• In the column
cos Phi
, enter the desired value.
• In the drop-down list
Excitation type
, select the desired excitation type.
9. Make the settings for the fallback (see Section 13.5, page 70).
13.5 Making Settings for Fallback
Fallback is an operating mode in the Cluster Controller used for grid management services.
There are two types of fallback.
• Fallback in case of missing or invalid external setpoint
• Fallback in case of failure of Speedwire communication between Cluster Controller and
inverters
Fallback in Case of Missing or Invalid External Setpoint
This type of fallback is an operating mode containing setpoints which are implemented by the
Cluster Controller if it classifies a setpoint as invalid or does not receive a setpoint within a
configurable time. The Cluster Controller classifies a setpoint as invalid if there is no configuration
for the setpoint available in the Cluster Controller or if the setpoint is not within the value range
configured in the Cluster Controller. In the event of an invalid or missing setpoint, the fallback
prevents the Cluster Controller from continuing to transmit to the inverter setpoints which may no
13 Grid Management Services
SMA Solar Technology AG
User Manual
ClusterController-BA-en-15
70