background image

2. PROBLEM: Sensing Range is too short.

CAUSE: Extended Range Sensitivity is required.

SOLUTION: Dip Switch number 4 should be in the “DOWN” (Extended

Range Sensitivity) position. Increase range by adjusting Range
Potentiometer clockwise (yellow phillips screw in blue base).

CAUSE: Faucet has Surgical Bend Gooseneck Spout.

SOLUTION: For Long Range use (recommended for Surgical Bend

Gooseneck Spout Faucet models), remove Range Jumper from
upper right hand corner of Circuit Board. Adjust Range
Potentiometer.

3. PROBLEM: Faucet activates by itself (false triggers).

CAUSE: Sensor range is set too long.

SOLUTION: Decrease range by adjusting Range Potentiometer

counterclockwise. If necessary, flip Dip Switch number 4 to
the “UP” (Reduced Range Sensitivity) position. Check
surroundings for factors that contribute to Sensor range
detection problems (bright lights, highly reflective surfaces,
sunlight, etc.).

4. PROBLEM: Faucet delivers very low flow or just a dribble.

CAUSE: Water supply stop(s) may be partially closed.

SOLUTION: Open supply stop(s) completely.

CAUSE: Debris is clogging Solenoid Filter.

SOLUTION: Shut off water. Remove, clean, and reinstall Solenoid Filter.

CAUSE: Solenoid is worn or faulty. 

SOLUTION: Rebuild with ETF-1009-A Solenoid Repair Kit or replace ETF-

370-A Solenoid.

CAUSE: Debris is clogging Faucet Aerator or Spray Head.

SOLUTION: Shut off water. Remove Aerator or Spray Head (use Key if

required). Clean and reinstall Aerator or Spray Head.

5. PROBLEM: Faucet does not stop delivering water or continues to

drip after user is no longer detected (even after power to the
Module has been disconnected).

CAUSE: Solenoid Valve is installed backward.

SOLUTION: Disconnect Solenoid. Reconnect Solenoid with water flow

toward the Faucet (see arrow on Solenoid).

CAUSE: Debris is clogging Solenoid.

SOLUTION: Remove and clean Solenoid Operator. If necessary, rebuild

with ETF-1009-A Repair Kit.

CAUSE: Seat in Solenoid Valve body is damaged or pitted.

SOLUTION: Replace with ETF-370-A Solenoid.

When assistance is required, please contact Sloan Valve Company
Installation Engineering Department at:

1-888-SLOAN-14 (1-888-756-2614) OR 1-847-233-2016

Note: Remove Cover from Control Module to check diagnostic lights.

1. PROBLEM: No water is delivered when Faucet is activated.

INDICATOR: If no LED lights illuminate:

CAUSE: No electricity is being supplied to Faucet.

SOLUTION: Ensure that the main power is turned “ON.” Check all

Transformer, Sensor, Solenoid and Cable Connections. Make
sure that Transformer is supplying 24 VAC (Volts AC). If no
voltage is detected, replace Transformer.

CAUSE: There is an electrical system malfunction.

SOLUTION: Reset electrical system. Unplug Sensor Connection.

Disconnect power to circuit for ten (10) seconds. Reconnect.

INDICATOR: If the GREEN LED does NOT illuminate when power is
reconnected:

CAUSE: There is an electrical system malfunction.

SOLUTION: Reset electrical system. Unplug Sensor Connection.

Disconnect power to circuit for ten (10) seconds. Reconnect.

CAUSE: The Control Module circuit is “dead.”

SOLUTION: Replace ETF-450-A Control Module.

INDICATOR: If GREEN LED illuminates AND changes to RED when
hands are in the Sensor’s detection zone AND the RED Solenoid
LED illuminates:

CAUSE: Water supply stop(s) may be partially closed.

SOLUTION: Open supply stop(s) completely.

CAUSE: Debris is clogging Solenoid Filter.

SOLUTION: Shut off water supply. Remove, clean and reinstall Solenoid

Filter.

INDICATOR: If GREEN LED illuminates AND changes to RED when
hands are placed in the Sensor’s detection zone AND the RED
Solenoid LED flickers with a vibrating/clicking noise heard inside
the module:

CAUSE: There is a direct short in the Solenoid or Solenoid Cable.

SOLUTION: Replace with ETF-370-A Solenoid.

INDICATOR: If GREEN/RED LED illuminates AND changes to RED
when hands are NOT located in the Sensor’s detection zone BUT
the RED Solenoid LED (in upper left corner of circuit) does NOT
illuminate:

CAUSE: Sensor range is set too long and is detecting the sink.

SOLUTION: Reduce Sensor detection range.

CAUSE: Sensor is faulty. 

SOLUTION: Replace Sensor.

INDICATOR: If GREEN LED illuminates BUT does NOT change to
RED when hands are placed in the Sensor’s detection zone:

CAUSE: Sensor range is set too short.

SOLUTION: Increase Sensor detection range.

CAUSE: Sensor is faulty.

SOLUTION: Replace Sensor.

Troubleshooting Guide

7

Содержание ETF-660

Страница 1: ...ng for each solenoid valve used Refer to Step 5 Install Transformer for further information Mixing Valve When installing the faucet with a Sloan mixing valve these Installation Instructions AND the Installation Instructions packaged with the mixing valve MUST be followed Important INSTALL ALL ELECTRICAL WIRING IN ACCORDANCE WITH NATIONAL LOCAL CODES AND REGULATIONS INSTALL ALL PLUMBING IN ACCORDAN...

Страница 2: ...t with BDM and BDT Variation Mixing Valves for Hot and Cold Water Supply shown with 4 trim plate ETF 770 Faucet with Bak Chek Tee for Hot and Cold Water Supply shown with 4 trim plate ETF 770 Faucet with ADM Variation Mixing Valve for Hot and Cold Water Supply shown with 4 trim plate ETF 770 Faucet with BDM and BDT Variation Mixing Valves for Hot and Cold Water Supply shown with 4 trim plate ETF 6...

Страница 3: ...LL BEVEL SIDE DOWN NUT TRIM PLATE FAUCET SHANK SPOUT TRIM PLATE OPTIONAL WASHER NUT SPOUT ETF 660 FAUCET ETF 770 FAUCET TRIM PLATE OPTIONAL WASHER NUT FAUCET SHANK RUBBER WASHER 4 Connect Supply Line s Note If installation includes a Sloan mixing valve refer to the Installation Instructions supplied with the Sloan mixing valve Flush dirt debris and sediment from the supply line s FOR DUAL LINE HOT...

Страница 4: ... Faucet 18 gauge wire is recommended A Run wires from secondary side of Transformer to 3 8 inch 10 mm hole at back of Control Module Enclosure If necessary wires can be run through wall and then inserted through hole in back of Control Module Enclosure Plug in Transformers Important DO NOT plug Transformer into receptacle until all wiring has been completed The Transformer is supplied with a 10 fo...

Страница 5: ...LOTS FROM FAUCET SPOUT TERMINAL BLOCK 1 REMOVE TERMINAL BLOCK 2 INSERT POWER CABLES 3 SECURE WITH SCREWS 4 REINSTALL TERMINAL BLOCK CONNECTOR BOARD POWER CABLE MODULAR RECEPTACLE B Insert Solenoid Valve Connector into the Modular Receptacle on Connector Board D Insert each Conduit Cable into a strain relief slot in the Control Module 8 Plug In Transformer A Plug Transformer into 120 VAC Receptacle...

Страница 6: ...ime Out by configuring the number 1 2 and 3 Dip Switches as shown in Table 1 Table 1 Time Out Settings Unless otherwise specified all ETF 660 ETF 770 Faucets leave the factory set with a 30 second Time Out Note The position of Dip Switch 4 range enhancer setting does not affect Faucet Time Outs Push Cables into slots at the bottom of the Control Module Install Control Module cover using Screws pro...

Страница 7: ...eering Department at 1 888 SLOAN 14 1 888 756 2614 OR 1 847 233 2016 Note Remove Cover from Control Module to check diagnostic lights 1 PROBLEM No water is delivered when Faucet is activated INDICATOR If no LED lights illuminate CAUSE No electricity is being supplied to Faucet SOLUTION Ensure that the main power is turned ON Check all Transformer Sensor Solenoid and Cable Connections Make sure tha...

Страница 8: ...l Mixing Valve not shown Item Part Description No No OPTIONAL MIXING VALVES 13 MIX 60 A Below Deck Mechanical Water Mixing Valve BDM Variation 14 MIX 135 A Below Deck Thermostatic Water Mixing Valve BDT Variation 15 MIX 110 AA Optimix Deck Mounted Water Mixing Valve FAUCET CABLE EXTENSION CORDS Faucet to Control Module Solenoid to Control Module ETF 1005 26 26 0 7 meter Length ETF 1003 36 36 0 9 m...

Отзывы: