3
Connection
3.1
Connection overview
A
B
E
D
C
F
Figure 5 : Rear side view of PSE
A
Mains power socket
Socket for connecting the battery charger to the mains
B
Auxiliary output terminals
(outputs 7 to 9)
Three auxiliary output terminals (5 A max.). The outputs are
protected by a fuse (Faux1 to Faux3).
C
Temperature sensor socket
Socket to connect the temperature sensor.
D
Main output terminals
(outputs 1 to 6)
Six output terminals (40 A max.). The outputs are
protected by a fuse (F1 to F6).
E
Alarm reports
Fail-safe, dry contact, three-pole SPDT switch (C- NC-
NO), allowing 1 A at 24 Vdc or 0,5 A at 120 Vac:
A
Mains status
B
Battery status
C
Output voltage status
F
Battery terminal
Terminal for connecting the battery leads (150 A max.).
+ positive polarity of the battery
- negative polarity of the battery
Important: the openings provided in the cabinet must be kept free. Do not create additional openings
because this can cause the device to malfunction and voids the warranty.
3.2
Connection specifications
-
Mains: 2.5 mm².
-
Battery: 16 to 50 mm².
-
Main outputs (outputs 1 to 6): 16 mm².
-
Auxiliary outputs (outputs 7 to 9): 2.5 mm².
-
Alarm reports (plug-in): 1.5 mm².