background image

smoke and dry soot formation in the fire box.

F. If smoke reading is satisfactory, but CO

2

can not be

increased to a satisfactory level (12%) or overfire draft of
0.02" W.C. can not be obtained, check for proper sealing
between sections, between the hinged burner mounting
door and front section, around burner blast tube and
around flue collector and collar. If seal is not satisfactory,
reseal with furnace putty or silicone with a temperature rat-
ing of at least 400° F. (All safety precautions indicated on
material package must be followed.) 

G. Once burner and draft have been set up, then smoke, CO

2

and stack temperature should be checked and recorded. If
smoke is greater than trace, review the burner instructions
and replace the nozzle if necessary. Normal smoke to be
expected is zero to a trace.

H. Make sure that the observation port cover is closed and

the screw is tightened.

CLEANING AND FILLING A NEW WATER BOILER

I. There are a number of commercial preparations available

from your distributor for cleaning and for corrosion protection
conditioning the internal (waterside) surfaces of boilers.
Follow the preparation manufacturer’s instructions.

DANGER:

Use CAUTION when handling chemicals and

draining hot water from a boiler. Scalding water and/or
chemicals can cause permanent injury to the skin, eyes
and respiratory system.

II. Filling and venting the water boiler after cleaning

A. Refill the system with fresh water.
B. Bring water temperature to at least 180° F promptly.
C. Circulate water through entire system.
D. Vent the system, including the radiation.
E. The boiler is now ready to be put into service or on

standby.

F. If brand name air-control devices are used, venting

instructions furnished with the devices should 
be followed.

XL-2000

8

XL-20      XL-30

XL-40

XL-50

5.5          7.0

8.5

10.0

WATER CONTENT OF BOILER (GALLONS)

3/8

—          —

0.430

0.0075

1/2

40

0.622

0.0157

0.545

0.0121

5/8

—   

0.666

0.0181

3/4

40

0.824

0.0277

0.785

0.0251

1

40

1.049

0.0449

1.025

0.0429

1 1/4

40

1.380

0.0779

1.265

0.0653

1 1/2

40

1.610

0.106

1.505

0.0924

2

40

2.067

0.174

1.985

0.161

2 1/2

40

2.469

0.249

2.465

0.248

3

40

3.068

0.384

2.945

0.354

Nominal

Pipe

Size

Inches

Schedule

No.

Inside

Diameter

Inches

Gallons

per

Lin. Ft.

Inside

Dia.

Inches

Gallons

per

Lin. ft..

Standard Steel Pipe

Type L Copper Tube

VOLUME OF WATER IN STANDARD PIPE OR TUBE

III. Safety check for control system

High limit control test: Set thermostat high enough for boiler
water temperature to reach high limit control setting. When
this temperature is reached, the high limit switch should
open, and the burner should shut off automatically. If the
high limit does not operate to shut off the burner, the high
limit or the wiring is faulty. Repair or replace immediately.

CARE AND MAINTENANCE

I. EXTENDED SHUTDOWN, CLEANING OR REMOVAL OF

BOILER FROM SERVICE.

DANGER:

 Use CAUTION when handling chemicals and

draining hot water from a boiler. Scalding water and/or
chemicals can cause permanent injury to the skin, eyes
and respiratory system.
A.Shut down burner by disconnecting all electrical power to

the burner by turning OFF the BURNER EMERGENCY
SWITCH of this boiler. After shutting down burner, while
the boiler is still hot (180°F to 200°F), drain water from
the bottom of the boiler until it runs clear.

B.Provide corrosion protection conditioning to the boiler

water in the heating system. There are a number of com-
mercial heating system preparations available from your
distributor. Follow the preparation manufacturer’s instruc-
tions.

C.To clean the fireside boiler surfaces, first shut down

burner by disconnecting all electrical power to the burner
by turning OFF the OIL BURNER EMERGENCY
SWITCH of this boiler in order to perform the following
work in (1) through (10) below.
1. Remove the flue pipe from the boiler flue collar and

clean thoroughly.

2. Inspect the entire vent connector back to the chim-

ney and clean if necessary.

3. Inspect the chimney for soot, debris and other unsafe

conditions of the chimney and take the necessary
action.

4. Remove the flue collector by first removing the top

jacket panel. The flue collector is held in place by two
hex 1/4-20 screws. Remove the screws and carefully
remove the flue collector. Try not to disturb the flat
fiberglass rope under the flue collector.

5. When necessary to clean the combustion chamber

you must first CLOSE the suction valve (and return
valve if two pipe). Then disconnect the oil lines from
the burner. The flexible electric conduit connected
from the junction box on the boiler to the burner via a
plastic connector must be disconnected from the
burner by grasping the plastic half of the connector
closest to the flexible conduit and gently pulling it in
the direction of the conduit until it is disconnected.
Remove the single 3/8-16 hex head screw on the
LEFT side of the swinging door. You will need a 9/16”
drive socket. Open the door to completely expose the
combustion chamber for thorough cleaning and for
inspection of target wall, blanket (provided in certain
models; see rating plate), main cast iron burner door
insulation and burner door fiberglass sealing rope. If
combustion chamber parts above are badly deterio-
rated then replace with original factory parts avail-
able at your distributor.

Содержание XL-2000

Страница 1: ...must con form to the requirements of the authority having jurisdiction or in the absence of such requirements to the Installation of Oil Burning Equipment ANSI NFPA 31 latest edition and to the National Electrical Code ANSI NFPA 70 latest edition The installation must also conform to the additional require ments in this Slant Fin Instruction Manual Where there is any difference the more stringent ...

Страница 2: ...y output The net I B R output ratings shown are based on an allowance for piping and pickup of 1 15 water or 1 33 steam D O E capacity output is divided by the allowance to obtain net rating The Slant Fin Technical Service department should be consulted before selecting a boiler for unusual piping and pickup requirements such as intermittent system oper ation extensive piping etc Ratings apply to ...

Страница 3: ...models and rating table shown on page 2 for chimney sizes B Check chimney condition Existing chimneys and stacks may have deteriorated with out repairs their use would be hazardous Before connect ing to an old chimney or stack 1 Clean it 2 Inspect it thoroughly 3 Remove obstructions 4 Replace worn sections of metal stacks 5 Seal bad masonry joints 6 Repair damaged lining C Where more than one appl...

Страница 4: ...space If there is NOT sufficient air for combustion due to tight construc tion or other conditions it REQUIRES AIR FROM OUT DOORS SEE ACTION REQUIRED column at right See NOTE 2 below Action Required NONE Provide air from outdoors directly through a permanent out side wall opening or openings with a free open area of not less than 1 sq in per 4000 Btu hr of TOTAL input of ALL fuel burning appliance...

Страница 5: ...s located in confined spaces Air from out doors See Table 2 2 4 Figure 3c Appliances located in confined spaces Air from out doors through ventilated attic See Table 2 2 4 Figure 3d Appliances located in confined spaces All air from outdoors through ventilated crawl space and outlet air to ventilated attic See Table 2 2 4 ...

Страница 6: ...e are used to control system pressure in an AIR COLLECTING SYSTEM Within the system after initial start up and venting air is collected in the tank and acts in contact with the water to control pres sure see dashed area in figure 5 and paragraph E Air is not vented from this system except at radiation high points see C If system pressure needs further control add another tank in parallel with the ...

Страница 7: ... E Install barometric draft regulator on horizontal breeching near chimney with hinge horizontal and face vertical condi tions permitting as in Figure 3a See Figure 3b as a second choice See manufacturer s instructions packed in carton with barometric draft regulator F If two or more appliances are used on the same chimney see CHIMNEY page 3 G Make up all joints with minimum air leaks secure with ...

Страница 8: ... high limit switch should open and the burner should shut off automatically If the high limit does not operate to shut off the burner the high limit or the wiring is faulty Repair or replace immediately CARE AND MAINTENANCE I EXTENDED SHUTDOWN CLEANING OR REMOVAL OF BOILER FROM SERVICE DANGER Use CAUTION when handling chemicals and draining hot water from a boiler Scalding water and or chemicals c...

Страница 9: ... the building is kept above freezing temperature by some means the plumbing system is not protected PROPYLENE GLYCOL is used in the quick freeze food industry it is practically non toxic Its use may be permit ted when indirect water heaters are used When anti freeze must be used inhibited propylene glycol is recom mended Useful information on the characteristics mixing proportions etc of glycol in...

Страница 10: ...XL 2000 10 ...

Страница 11: ... 4 65 Closed XL 50 99 FRD 1 80 1 75 60 B DELAVAN 105 4 20 Open 71399 00F XL 50 2 00 1 75 60 B DELAVAN 130 5 40 Open BOILER MODEL CARLIN BURNER MODEL 2 3 FIRING RATE NO 2 OIL GPH SIZE GPH ANGLE AND TYPE MFR NOZZLES OIL PUMP PRESSURE SETTING PSIG A APPROXIMATE HEAD SETTING NO APPROXIMATE AIR BAND OPENING 1 SHUTTER NON ADJUSTABLE NOTES 1 Single slotted air band for XL 20 and XL 30 double slotted air ...

Страница 12: ...ATE NO 2 OIL GPH SIZE GPH ANGLE AND TYPE MFR NOZZLES OIL PUMP PRESSURE SETTING PSIG APPROXIMATE AIR SHUTTER SETTING NO 1 APPROXIMATE AIR BAND SETTING NO STATIC DISK DIAMETER INCHES NOTES 1 Blank closed air band for XL 20 2 slot band for XL 30 4 slot band for XL 40 and 8 slot air band for XL 50 2 See PRECAUTIONS BEFORE STARTING OIL BURNERS and START UP on page 7 and burner figures on this page 3 Al...

Страница 13: ...E MFR OIL PUMP PRESSURE SETTING PSIG APPROX HEAD SETTING NO APPROX AIR SHUTTER SETTING NO XL 20 R 40 F 3 48 0242 100 XL 30 R 40 F 5 48 0243 100 XL 40 R 40 F 5 48 0244 100 XL 50 R 40 F 10 48 0245 100 70 SS 80 ES 1 1 0 85 70 ES 1 1 15 0 85 70 ES 1 1 35 1 2 80 B 1 1 5 1 2 80 B 1 1 8 1 5 60 B DELAVAN 145 1 3 8 HAGO 170 1 3 1 2 HAGO 140 1 2 6 HAGO 185 1 3 2 DELAVAN 130 3 4 DELAVAN 160 4 4 75 Figure 7A ...

Страница 14: ... manual AIR ADJUSTMENT PLATE 4 should line up with the SETTING INDICATOR 2 on the fan housing cover Once set the air adjustment plate should be secured in place by tightening SCREWS 3 and 5 For F 10 model manually open and release the hydraulic air shutter to ensure it has free movement 3 The final position of the air adjustment plate will vary on each installation Use instruments to establish the...

Страница 15: ...SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com Slant Fin Corp 1996 ...

Отзывы: