E93.1601EN032.C VGH installation manual
63
Programmable in- and outputs
It is possible to re-program some in- and outputs to other functions. To do this use list below and go to:
Menu\settings\boiler settings\"1122" (installer password)\boiler parameters
boiler parameter
name
default setting
description
terminal
(117)
Prog. Input 2.
2
DHW flow switch
LV 16-17
(118)
Prog. Input 3.
2
Gas pressure switch
LV 24-25
(122)
Prog. Input 7.
3
Cascade sensor
LV 3-4
(124)
Prog. Input RT.
1
room thermostat on
LV 12-13
(125)
Prog. Output 1.
4
System pump
HV 4-5
(126)
Prog. Output 2.
9
Ext. Igniter
separate connector
(127) Prog.
Output
3.
6 Alarm semi-conductor output.
HV 10-11
(128)
Prog. Output 4.
18
3-way Valve DHW
HV 3-2-1
To all outputs following applies: maximum current 2 A each output.
Total output of all currents combined maximum 3.5 A.
The inrush current of the 3-way valve and/or circulators is maximum 8 A.
para-
meter
Display:
INPUTS:
re-
mark
para-
meter
Display:
OUTPUTS
:
re-
mark
(117)
Prog. Input 2.
0 Disabled
(127) Prog. Output 3. 0 Disabled
1 DHW flow sensor
N.A.
1 Module pump
N.A.
2 DHW flow switch
2 CH pump
N.A.
3 CH flow sensor
N.A.
3 DHW pump
N.A.
4 CH flow switch
4 System pump
N.A.
(118)
Prog. Input 3.
0 Disabled
5 Cascade pump
N.A.
1 Drain switch
6 Alarm relay
2)
2 Gas pressure switch
7 Filling valve
2)
(122)
Prog. Input 7.
0 Disabled
8 LPG tank
2)
1 T_Flue_2 sensor
N.A.
9 Ext. Igniter
2)
2 T_Flue_2 with blocked flue
N.A.
10 Air damper
2)
3 Cascade sensor
(128) Prog. Output 4. 0 Disabled
4 Blocked Flue switch
N.A.
1 Module pump
5 CH Sensor
2 CH pump
(124)
Prog. Input RT. 0 room thermstat off
3 DHW pump
1 room thermstat on
4 System pump
Display:
OUTPUTS
:
5 Cascade pump
(125)
Prog. Output 1. 0 Disabled
6 Alarm relay
1 Module pump
7 Filling valve
2 CH pump
8 LPG tank
3 DHW pump
9 Ext. Igniter
4 System pump
10 Air damper
5 Cascade pump
11 empty
6 Alarm relay
12 empty
7 Filling valve
13 empty
8 LPG tank
14 empty
9 Ext. Igniter
15 empty
10 Air damper
16 empty
(126)
Prog. Output 2. 0 Disabled
17 3-way Valve CH
1 Module pump
1)
18 3-way Valve DHW
2 CH pump
1)
19 3-way Valve CH
(power when idle)
3 DHW pump
1)
20 3-way Valve DHW
(power when idle)
4 System pump
1)
5 Cascade pump
1)
6 Alarm relay
1)
7 Filling valve
1)
8 LPG tank
1)
9 Ext. Igniter
1)
10 Air damper
1)
Table 11. 6
Table 11. 7
NOTICE
Remarks:
1) Prog. output 2: (ext. igniter); this is a separate connector,
the pin in the middle is for ionization, it has no PE
connection. If earth is needed, it must be connected to
the main earth terminal.
2) Prog. output 3: (alarm relay); this is a triac output with an
active voltage of 120 VAC, it can only handle resistive
loads between 5 and 50 Watt.
Содержание VGH-299-CH
Страница 6: ...E93 1601EN032 C VGH installation manual 6 1 SAFETY GUIDELINES ...
Страница 59: ...E93 1601EN032 C VGH installation manual 59 Ladder Logic Diagram Figure 11 3 ...
Страница 60: ...E93 1601EN032 C VGH installation manual 60 Electrical schematics Figure 11 4 ...
Страница 61: ...E93 1601EN032 C VGH installation manual 61 Figure 11 5 ...
Страница 123: ...E93 1601EN032 C VGH installation manual 123 22 SPARE PARTS Figure 22 1 ...
Страница 124: ...E93 1601EN032 C VGH installation manual 124 Figure 22 2 ...
Страница 127: ...E93 1601EN032 C VGH installation manual 127 ...