E95.1901EN032 User manual Slant Fin VGH-CH / CO 

 

  Service reminder 

The Service reminder will remind you that the appliance needs to be serviced. The "Service_Interval" is factory 
set at 2000 burn hours. When service is not done within this time, a service reminder will be shown: 

 

on the screen: "Service is required!" is displayed, alternating with the normal status display; 

 

  Menu structure display 

Menu structure Display: 

 

Access  
level  

Description: 

1. Central Heating (CH) 

User 

Enter the Central Heating (CH) menu 

2. Domestic Hot Water (DHW) 

User 

Enter the Domestic Hot Water (DHW) 
menu 

3. Information 

User 

Enter the Information menu 

4. Settings 

User 

Enter the Settings menu 

5. System Test 

Installer  Enter the System Test menu 

(Installer only). 

 

1. Central Heating (CH) 

min. 

max. 

Default  unit 

Access  
level 

 

Description:

 

1.1 CH Setpoint 

68 
(20) 

194 
(90) 

185 
(85) 

°F 
(°C) 

Installer  Set the CH setpoint if CH mode is 0 

1.2 Outdoor Reset 

 

 

 

 

User 

Enter the Outdoor Reset menu if CH 
mode is 1 

 

1.2 Outdoor reset 

min.

 

max.

 

Default

 

unit

 

Access  
level 

 

Description:

 

Des. Supply T. 

68 
(20) 

194 
(90) 

185 
(85) 

°F 
(°C) 

Installer  Set CH setpoint when outdoor 

temperature equals Des. Outd. T. 

Bas. Supply T. 

68 
(20) 

194 
(90) 

104 
(40) 

°F 
(°C) 

Installer  Set CH setpoint when outdoor 

temperature equals Bas. Outd. T. 

WW Shutdown 

32 
(0) 

95 
(35) 

72  
(22) 

°F 
(°C) 

Installer  Set outdoor temperature above which 

CH demand is locked. 

Bas. Outd. T. 

32 
(0) 

86 
(30) 

68  
(20) 

°F 
(°C) 

Installer  Set the outdoor temperature at which 

CH setpoint is set to Bas. Supply T. 

Des. Outd. T. 

-13  
(-25) 

77 
(25) 

23 
(-5) 

°F 
(°C) 

Installer  Set the outdoor temperature at which 

CH setpoint is set to Des. Supply T. 

 

2. Domestic Hot Water 
(DHW) 

min.

 

max.

 

Default

 

unit

 

Access  
level 

 

Description:

 

DHW Setpoint 

104 
(40) 

160 
(71) 

140 
(60) 

°F 
(°C) 

Installer  Set the DHW setpoint 

DHW Store Setpoint 

104 
(40) 

160 
(71) 

149 
(65) 

°F 
(°C) 

Installer  Set the DHW store setpoint for DHW 

mode 1 and 2 

 

3. Information 

min.

 

max.

 

Default

 

unit

 

Access  
level 

 

Description:

 

3.1 Software versions 

 

 

 

 

User 

Enter the Software Versions menu 

3.2 Boiler Status 

 

 

 

 

User 

Enter the Boiler Status menu 

3.3 Boiler History 

 

 

 

 

User 

Enter the Boiler History menu 

3.4 Error Log 

 

 

 

 

User 

Enter the Error Log menu 

3.5 Service 

 

 

 

 

User 

Enter the Service menu 

 

3.1 Software versions

 

min.

 

max.

 

Default

 

unit

 

Access  
level 

 

Description:

 

Display

 

 

 

 

 

 

 

xxxx 

 

User

 

Display the software checksum

 

Boiler

 

 

 

 

 

 

 

Xxxx

 

User

 

Display the boiler software checksum

 

Device Group

 

 

 

 

 

 

 

xxxMN

 

User

 

Display the boiler group ID

 

 

 

 

 

If the message “Service is required” is shown, the boiler will continue running, but 
maintenance must be carried out before this message is reset.  

 

    

 

NOTICE

 

Содержание VGH-100-CH

Страница 1: ...WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follo...

Страница 2: ......

Страница 3: ...R BOILER 11 FUNCTIONAL INTRODUCTION 11 INSTALLATION AND SETTINGS 11 4 DISPLAY AND BUTTONS 12 DISPLAY ICONS 12 SCREENS AND SETTINGS 13 De aeration sequence 13 CONTROL PANEL MENU STRUCTURE 14 Set Actual...

Страница 4: ...y Alert Symbol indicates a hazardous situation which will or can cause minor or moderate personal injury or property damage Caution Sign plus a lightning bolt indicates the risk of electric shock and...

Страница 5: ...5 E95 1901EN032 User manual Slant Fin VGH CH CO 1 SAFETY GUIDELINES...

Страница 6: ...6 E95 1901EN032 User manual Slant Fin VGH CH CO CONSIGNES DE S CURIT...

Страница 7: ...ead and follow the supplied instructions before installing servicing or removing this boiler This boiler contains materials that have been identified as carcinogenic or possibly carcinogenic to humans...

Страница 8: ...pressure BCU Burner Control Unit BTU British Thermal Unit C Degree Celsius CH Central Heating Heating Only CO 1 Combi boiler CH DHW 2 Carbon monoxide CO2 Carbon dioxide Combi A boiler providing a comb...

Страница 9: ...ebris Inspect also for any gaps at the wall penetration s which could allow vented gasses to reenter the home Visually inspect water and gas pipes for leaks Visually inspect to see that the condensate...

Страница 10: ...ent terminal The plate must be of sufficient size to be easily read from a distance of eight feet away and read Gas Vent Directly Below For direct vent boilers mechanical vent heating boilers or domes...

Страница 11: ...thermostat control CH mode 2 Central Heating with full outdoor temperature reset CH mode 3 Central Heating with permanent heat demand CH mode 4 Central Heating with analog input control of setpoint C...

Страница 12: ...nt LEFT Return to previous menu item or Status overview UP Directly select Actual setpoint of DHW setpoint in the Status overview push RIGHT to confirm and use UP or DOWN to adjust value DOWN Directly...

Страница 13: ...ATION SEQUENCE The De Aeration sequence is a safety function that starts at every power ON of the boiler and is used to remove the air from the heat exchanger The DAir sequence does not start after a...

Страница 14: ...owing service intervals Using the submenu s following items can be set 1 Language To set the menu language 2 Unit Type Setting to imperial or SI units 3 Date Time Set date time zone display mode summe...

Страница 15: ...The header in the display shows you are inside the main menu While scrolling through the menu you will see that the selected menu item is shown in a white rectangle Enter a menu item by pressing ENTER...

Страница 16: ...and Italian BE AWARE DO NOT set the language to the Chinese Language if you are not familiar with this language Contact your installer for instructions if the display is set to Chinese and needs to b...

Страница 17: ...104 40 F C Installer Set CH setpoint when outdoor temperature equals Bas Outd T WW Shutdown 32 0 95 35 72 22 F C Installer Set outdoor temperature above which CH demand is locked Bas Outd T 32 0 86 3...

Страница 18: ...Calculated Setpoint F C User Actual CH setpoint 3 3 Boiler history min max Default unit Access level Description Successful Ignitions User Display the number of successful ignitions Failed Ignitions...

Страница 19: ...cess level Description Date dd mm yy User Set the current date Time hh mm User Set the current time A Time Zone Settings User Enter the time zone settings menu B Display Settings User Enter the displa...

Страница 20: ...the freezing of the Central Heating circuit when the boiler is in error during the winter period For some non volatile lockouts the circulator will not be running also see the error tables in this cha...

Страница 21: ...only Filter errors based on Boiler ID Managing Dep 1 Dep2 etc Clear Error Log Clear the error log protected by password When no filtering option is selected Disabled the error log will show all errors...

Страница 22: ...ctly If the boiler does not start after Reset contact your installer 4 BLOCKING_ TOO_LONG Control had a blocking error for more than 20 hours blocking code active for more than 20 hours Reset and chec...

Страница 23: ...the heat exchanger or flue gas sensor is malfunctioning or heat exchanger is overheated If the boiler does not start after Reset contact your installer 17 STACK_ERROR Internal software error wrongly p...

Страница 24: ...CHANGE_ DIFF_ERROR The 2 exchange sensors deviate too much for more than 60 seconds there is not enough water flow through the heat exchanger If the boiler does not start after Reset contact your inst...

Страница 25: ...boiler does not start after Reset contact your installer 107 REFHI_TOO_ LOW Internal hardware error wrongly programmed BCU or PB If the boiler does not start after Reset contact your installer 108 REF...

Страница 26: ...unctioning DHW sensor or short circuiting If the boiler does not start after Reset contact your installer 130 FLUE_ SHORTED Flue sensor shorted malfunctioning flue sensor or short circuiting If the bo...

Страница 27: ...ade control lost communication with one of the depending connection between cascaded boilers is interrupted or wiring is broken Contact your installer 202 APP_SELECTION_ ERROR Unknown appliance model...

Страница 28: ...28 E95 1901EN032 User manual Slant Fin VGH CH CO...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...UBLICATIONVGHR UIM SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario 400 Ambassador Drive Mississauga Ontario L5T 2J3Phone 905...

Отзывы: