External wiring

The external wiring should now be connected to the fire panel.

The fire panel is supplied with End Of Line Resistors for the zone and

sounder circuits, these must be transferred to the last device in the circuit.

The End Of Line Resistor must be replaced with Active End Of Line

device if removable smoke/heat detectors are used on the zone cirucit..

Please note these units are polarised.

1

DISCONNECT MAINS SUPPLY & BATTERY.

2

Connect the zone wiring, one zone at a time, transferring either the

End Of Line Resistor or Active End Of Line Device, if removable

smoke/heat detectors are being employed. The active end-of-line

devices are polarised and should be connected with Red/Orange

wire to the +ve and Black to the –ve.

3

Repeat the above procedure until all the required circuits are

connected.

4

Connect the sounder wiring one circuit at a time, transferring the end

of line resistor to the last sounder on that circuit.

5

Repeat the above procedures until all the required zones are

connected.

6

Connect other external circuits as required

7

Reinstate the mains supply, enter access code then press the

‘RESET’ button

8

Refit plastic facia. Do not over tighten two retaining screws.

61600970 issue 9_8/02

3

4 & 8  zone - Fire alarm panels

Base of existing range of detectors

- +

1

DETECTOR

ZONE

FIRE PANEL

L2

L1

OUT

IN L1

DIODE

(SCHOTTKY)

L2

L1

OUT

IN L1

DIODE

(SCHOTTKY)

Black

Red or

Orange

Active

End of Line

-

+

Remote

LED

LED

module

Connecting LED to base

with LED Module fitted

3 2 7

4

5

DC +ve

DC -ve

+ve

-ve

+ -

2 7

2 7

4

4

5

5

Active end of line

device

black

red or

orange

- +

1

DETECTOR

ZONE

FIRE PANEL

Base for new range of detectors

Figure 3 Connecting the fire detectors and remote LED

COMMON

470 Ohms

680 Ohms

CALL POINT

- +

1

DETECTOR

ZONE

FIRE PANEL

COMMON

470 Ohms

680 Ohms

CALL POINT

black

red or

orange

Active

end of line

Fit an active end of line if

detectors are also connected

to the zone circuit.

8K2

Ohms

Figure 4 Connecting the Manual call points

-

+

END-OF-LINE

RESISTOR 8K2 Ohms

fitted to last sounder

- +

2

FIRE PANEL

SOUNDERS

- +

1

+

-

-

+ +

-

-

+ +

-

Polarised and suppressed

sounders only

2nd

SOUNDER

COMMON

1st

SOUNDER

-

-

-

-

+

+

END-OF-LINE RESISTOR

8K2 Ohms fitted to last sounder

Volume

Figure 5 Sounder circuit wiring

CLASS

CHANGE

- +

AUX

24V

FIRE PANEL

Non latching alarm

remotely set by

an external source

Figure 6 Class change connections

Содержание SECURI4

Страница 1: ...rated at 30VDC 1A This facility is not to be used for fire alarm routing equipment Class Change Activated by using volt free N O contacts between the ve of AUX 24V output and the CLASS CHANGE output Cabling Unless otherwise recommended and taking into account voltage drop not less than 1mm2 is recommended Sounder circuits should use cable that is fire proof All cabling should be earthed to the met...

Страница 2: ...ransformer output to the PCB terminals marked AC Note Polarisation of this connection is unimportant 4 Connect resistors supplied between the ve and ve of each detector zone and sounder zone via the terminal blocks on the PCB carrier At this stage it is not necessary to connect detector or sounder circuits 5 Connect to repeater and volt free auxiliary terminal block as necessary 6 Re instate the m...

Страница 3: ...Reinstate the mains supply enter access code then press the RESET button 8 Refit plastic facia Do not over tighten two retaining screws 61600970 issue 9_8 02 3 4 8 zone Fire alarm panels Base of existing range of detectors 1 DETECTOR ZONE FIRE PANEL L2 L1 OUT IN L1 DIODE SCHOTTKY L2 L1 OUT IN L1 DIODE SCHOTTKY Black Red or Orange Active End of Line Remote LED LED module Connecting LED to base with...

Страница 4: ...d then automatically reset 1 Enter the access code to get into supervisor mode if not already entered 2 Hold down the ADVANCE push button for at least 2 seconds until you hear a double bleep 3 The Test LED will light and the Zone 1 Fault LED will flash at a fast rate faster than the fault warning flash rate the flashing LED at this stage indicates that the zone is not in test 4 If you do not wish ...

Страница 5: ...g reset whilst the sounders are disabled will not revert the panel to normal operation If the panel is left in Test for more than 10 minutes the internal buzzer will sound intermittently 61600970 issue 9_8 02 5 4 8 zone Fire alarm panels Sounder General Fire General Fault Zone Fault Zone Fault Disable Test Sounder Fault Disable System Fault Power Power Fault Disabled Test Supervisor Mode Code Entr...

Страница 6: ...e address___________________________________________________________________________ _______________________________________________________________________________________ Person s responsible________________________________Date_______________________________ System installed by__________________________________Telephone__________________________ Date installed____________________________________...

Страница 7: ...61600970 issue 9_8 02 7 4 8 zone Fire alarm panels Fire panel event record Date Weekly Qtly Event Action Required Completed Name ...

Страница 8: ...8 61600970 issue 9_8 02 4 8 zone Fire alarm panels Date Weekly Qtly Event Action Required Completed Name ...

Отзывы: