3.2  Illustrated installation procedure 

(j) Dismantle: 

® Wall mounting without brackets, 

2.0

-2.4M above ground 

@Bracket mounting  (optional) 

A. Insert the screwdriver 

Wall 

mounting 

�------� 

B. Mark the drilled hole 

and drill 

C. Insert two expandable 

dowels and attach the 

base into wall by four 

screws

D. 

Replace the 

dismantled parts to 

base cover 

3 pulse: after detecting 3 pulse, it will send alarm signal. 

4. Dip switch function specification

D-PIR-I MW can choose following detection mode. 

2 pulses: after detecting 2 pulses, it 

will 

send alarm signal (factory default) 

ON  3-PULSE 

SET PULSE 

OFF  2-PULSE 
ON  PIROR MW 

WORK MODE 

OFF  PIR AND MW 
ON  LEDON 

ALARM  LED 

More pulses means less sensitivity, but also can decrease the false alarm. 

OFF 

D-PIR-I MW apply both PIR and microwave technology, it can choose two working mode below 

LED OFF 

ALARM MODE 

15MINS MODE 
SMINS MODE 

TESTING MODE 

And mode: when both PIR and microwave detects intruder, it will give alarm signal. 
Or mode: when PIR or microwave detect intruder, it will give alarm signal. 

NO 

OFF 

Alarm Led on/off: for special cases, users can set alarm led visible or not according to the 

OFF 

ON 

needs. 

OFF  OFF 

 

D-PIR-I MW can set two alarm modes as below 
5mins mode: after alarm, there is 5mins dormancy, trigger the detector during this time, will not alarm. 

15mins mode: after alarm, there is 15mins dormancy, trigger the detector during this time, will not alarm. 
Testing mode: after alarm, there is 3s dormancy, trigger the detector during this time, will not alarm. (factory default) 

5. Coding method between detector

and panel:

6.Change battery:

Coding setting, 
CD Set detector as Normal mode, place the battery and LED will flash seconds. 

Set panel as Coding mode.(Panel coding please refer to panel manual), 
within 3 seconds when press the configure key of the panel, 

a. Wave hands near the front side of D-PIR-I MW, detector will 

send a alarm signal to the panel. If the panel sounds a response 
then code successfully.

b. Inverse the detector and detector will send alarm signal to the panel, 

vibration switch,if the panel sounds a response then code successfully. 

® Enter the address code to code with the panel. Set the panel as manual 

coding mode and enter the 9-digit address code. This will be a higher 
Probability of coding success. 

7. Walk test in coverage area:

CD Set as Test Mode to proceed walk-test, pulse count set as 1,2 or 3. 

When the voltage of the detector is lower than 4.8V, 

the control panel will receive low battery signal.

After that, each 2 hours, it will send low battery.
The user should buy the same battery and change. 

Place new lithium 
battery 

® Walk across the far edge of coverage area at the speed of 1 step/second(about0.75m/s) 

The LED will flash for seconds then alarm  (as shown in the right figure)  . 

@ Do walk-test in opposite direction to confirm the boundary of both sides, Make 

sure the detection centre pointing to the centre of protected area. 

@ Make sure the detection centre at the  proper place. Should properly adjust the 

detection area if you can not get an ideal detection area. 

@After adjust the detection angle , should redo the walk test  as above. 
® Please change TEST mode to NORMAL mode after the Walk-test . 

8.Customer service

Our products are very reliable,  but for some special reasons, the working performance will be limited  in certain range. We here list

some cases as follows, 

CD. The voltage of control panel is not stable;
®· Low-voltage of the detector.

For any help please contact with our company and your could visit our website for more information., 