Table 5-4 Auto-Leveling Outrigger Settings and Error Codes
Reading the Codes:
In order to read the fault codes, a sequence of pauses and flashes can be seen on the LED mounted on the out-
rigger control module. The codes are continuously displayed by the LED until the fault is cleared, the outrigger
control module is reset and no longer detects the fault, or idle timeout becomes active.
The sequence is as follows:
1. Half second flashes followed by half second pauses indicate the first digit.
2. A 2.5 second pause.
3. Half second flashes followed by half second pauses indicate the second digit
4. A 5 second pause.
Repeat steps 1-4
Since the outrigger control module only reports one error, only one code can be read from the LED per instance.
If the error is cleared and another error is present, it will then be presented.
LED ERROR CODES
EVERYTHING OK
ON
VEHICLE TILTED
1/1
OUTRIGGERS CANNOT BE MOVED !
1/2
OUTRIGGERS NOT HOME
2/2
NOT FULLY LEVEL
2/1
RELEASE OUTRIGGER DEMAND !
5/5
CHECK OUTRIGGER SUPPLY (P4-9)
5/2
CANNOT LEVEL : BAD TILT SENSOR
7/1
OUTRIGGERS MANUALLY CONTROLLED !
6/6
TESTING HWFS
7/8
B+ SUPPLY TOO LOW
5/1
STARTUP !
7/7
FAULT : BAD SLAVE MICRO
7/5
FAULT : BAD TILT SENSOR
7/1
FAULT : BAD HWFS
7/2
FAULT : P2-5 FAULTY
8/1
FAULT : P2-6 FAULTY
8/2
FAULT : P2-8 STUCK ON
8/3
FAULT : P2-8 ALWAYS ON
8/4
FAULT : P2-8 ALWAYS OFF
8/5
FAULT : HWFS STALLED !
7/6