EN
6. Assembly
- 72 -
951-170-218-EN
Version 06
6.7.2 Connection of aerosol lines to an MQL system with bypass control
See Figure 34
On an MQL system with bypass control, the
aerosol flow must be divided by a Y-piece at
the end of the aerosol line coming from the
aerosol generator (
2
), as close as possible to
the tool spindle. One of the two downstream
aerosol lines is then routed to the tool
spindle (
8
), while the other aerosol line is to
be routed through the provided bypass valve
(
6
) either back to the refill reservoir (de-
signed for this application) or the customer’s
exhaust air system.
• Route the aerosol line (
1
) from the aero-
sol generator (
2
) to the immediate vicin-
ity of the tool spindle (
8
)
• Install the supplied Y-distributor at
the end of the aerosol line (
1
), as close
as possible to the entrance to the tool
spindle
• Connect both outlets of the Y-distributor
(
3
) to the aerosol lines
• Route and connect one of the two aero-
sol line (
4
) to the tool spindle
There are two ways to route the other
aerosol line, which leads through the bypass
valve:
1. Routing to exhaust air system on ma-
chine tool
• Secure the bypass valve (
6
) at an appro-
priate location in the machine tool
• Connect the inlet side of the bypass valve
(
6
) to the aerosol line (
5
) coming from
the Y-distributor (
3
).
• Connect the outlet side of the valve (
6
), in
which the bypass restrictor (
9
) has been
pre-installed, to the aerosol line (
5
) and
route the line to the suction area of the
machine tool.
• Use the supplied cable to establish the
electrical connection between the bypass
valve (
6
) and the bypass control (Chapters
7 and 8).
2. Routing to oil reservoir (accessory) of the
MQL system
The bypass line can also return to the oil re-
filling reservoir. As this is system-dependent,
consultation with the SKF dealer or the SKF
Customer Service department is required.