Protection
Alarms
2 - 26
SKF Multilog On-Line System IMx-M
User Manual
Figure 2 - 17.
Enter/Leave Time Example.
The example of alarm status change shown in the diagram above;
1.
The alert has not triggered: The measurement value has exceeded the alarm level
for a shorter duration than the enter time.
2.
The alert has triggered: The measurement value has exceeded the alarm level for
longer duration than the enter time.
3.
The alert has released: The measurement value drops below the hysteresis
adjusted alarm level and remains below for the duration of the leave time.
*Only for digital channels
First Out Indication
First Out
is set when an armed channel enters a danger state.
Channel First Out Slot
is the first channel that reaches the danger state amongst
all the channels in the protection module.
Channel First Out Rack
is the first channel that reaches the danger state amongst
all the channels in the rack.