CTU CAN-bus
Overall Measurement Values
SKF Copperhead Transmitter Unit CMPT CTU
10-32
Instruction Manual
Overall Measurement Values
If overall values are needed the following request as in Table 10-15 can be used. This
will get the value from parameters that save the values.
Request
:
Command RR
Source
Dest
Data
Remarks
0x48
0
Client ID
Server ID
[0-1] Parameter ID
[2-3] Elem Index
ID of parameter
Element index
Table 10-15: Unit address response
Response
:
Comman
d
RR
Source
Dest
Data
Remarks
0x48
1
Server ID
Client ID
[0-1] Result
[2-5] Value
Result = 0: OK
Result >0: Error
32-bit aligned value
Table 10-16: Unit address response
Parameter ID
with default Elem Index (value 0) for getting temperature and different
vibration values:
Current measured temperature ( °C)
204 (0x00, 0xCC)
Acceleration RMS output
266 (0x01, 0x0A)
Acceleration PH output
267 (0x01, 0x0B)
Velocity RMS output
268 (0x01, 0x 0C)
Enveloper PH output
269 (0x01, 0x0D)
Current measured Bias offset voltage
209 (0x00, 0xD1)
Response will return a result code and 32 bit aligned value. Overall value will be 32 bit
floating point IEEE 754 format. When calling these values you should know the dial
setup of the unit and the kind of sensor you have. If you call for example Velocity RMS
when you measure Envelope according to CTU dial selector, you will receive value 0.
Result codes
:
Result code (hex)
Description
0x0000
Ok
0x0001
Invalid parameter
0x0002
No write access
0x0003
Invalid condition
0x0004
Invalid state
0x0005
Zero sample rate
0x0006
No read access
0x0007
Invalid mode
0x0008
Invalid parameter value
0x0009
Algorithm not active