Operations
-5-
Programming Panel Settings
Entering the program mode:
Press and hold the
SET
button for 3 seconds until the “Prog” is displayed. The fi rst parameter that can be set,
along with its current value, will then fl ash on the display. You are now in the program mode.
Exiting the program mode:
At any point in the program mode push and hold the
SET
button for 3 seconds until run is displayed. The
display will then return to its normal state.
To change and set a parameter:
NOTE: While setting parameters the following conditions must be met or the display will show
(ERROR):
LAg
- level must be
above LEAd
for Demand Dose
LEAd
- level must be
above StOP
for Demand Dose
StOP
- level must be
4 inches or higher
for Demand Dose
tO
- level must be
above tEnbLE
for Time Dose
tEnbLE
- level must be
above rEdOFF
for Time Dose
rEdOFF
- level must be
4 inches or higher
for Time Dose.
1.
When in the program mode push the NEXT button until the desired parameter is displayed.
2.
Push the SET button and the current value of that parameter will be displayed with the fi rst digit fl ashing.
3.
Use the UP button to change the value of the fl ashing digit. When the desired value of the fl ashing digit is
reached, push the NEXT button to advance to the next digit. Use the UP and NEXT buttons to set the total
value of that parameter.
4.
When done setting the parameter, push the set button and the parameter will fl ash along with its new value.
If an (ERROR) message is received, check above conditions to ensure all are being met.
5.
Push the NEXT button to advance to the next parameter and follow steps 2 – 4 to set the values.
Parameters that can be set:
The parameters that can be set when in the program mode are:
For Time Dose Panels:
On
– On time for pump in hh:mm:ss
OFF
– Off time for the pump in hh:mm:ss
ALtErn
– Sets the alternation of the pumps. Settings are ALt, 2-1 and 1-2. (duplex panels only)
ALAr
– High water alarm set point.
tO
– Timer override set point
tEnbLE
– Timer enable set point
rEdOFF
– Redundant off set point.
UnitS
– Units of measure can be set in inches (in) or centimeters (c).
For Demand Dose Panels:
ALtErn
– Sets the alternation of the pumps. Settings are ALt, 2-1 and 1-2. (duplex panels only)
ALAr
– High water alarm set point.
LAg
– Lag pump start point. (duplex panels only)
LEAd
– Lead pump start point.
StOP
– Pump stop set point.
UnitS
– Units of measure can be set in inches (in) or centimeters (c).