This control panel must be installed and serviced by a 

licensed electrician in accordance with the National Electric Code 
NFPA-70, state and local electrical codes. 

 All conduit running from 

the sump or tank to the control panel must be sealed with conduit 
sealant to prevent moisture or gases from entering the panel. 

NEMA 

4X enclosures are for indoor or outdoor use,

 primarily to provide 

a degree of protection against corrosion, windblown dust and rain, 
splashing water and hose-directed water. 

Cable connectors must 

be liquid-tight in NEMA 4X enclosures.

The C-Level sensor is suitable for use in sewage applications. 

Do NOT use in potable water.

Installer Friendly Series

®

 (IFS) control panels are designed to control  

pump(s). The controller records number of pump cycles, elapsed run 
time, alarm counts, and signal error counts. 

Mounting the Control Panel

Note:

 The control panel should not be mounted in a location that may 

be subject to submersion.

1.

 

Determine mounting location for panel. If distance exceeds the 
length of either the sensor or fl oat cables or the pump power 
cables, splicing will be required. 

Note:

 For splicing C-Level cord, 

use only shielded cable. Splice conductors as well as shielding. 
Maximum total cable length is 300 feet. For outdoor or wet instal-
lation, we recommend the use of an SJE-Rhombus

®

 liquid-tight 

junction box with liquid-tight connectors to make required connec-
tions.  

You must use conduit sealant to prevent moisture or 

gases from entering the panel.

2. 

Mount control panel with mounting devices furnished.

3.

  Determine conduit entrance locations on control panel.  Check 

local codes and schematic for the number of power circuits re-
quired. 

(Sensor cable requires separate conduit from power 

and pump cables.)

Note:

 Be sure the proper power supply voltage, amperage, and phase 

meet the requirements of the pump motor(s) being installed.  If in 
doubt, see the pump identifi cation plate for voltage/phase require-
ments.

4.

  Drill proper size holes for type of connectors being used.

Note:

 If using conduit, be sure that it is of adequate size to pull the 

pump cable(s) through.  

5.

  Attach cable connectors and/or conduit connectors to control 

panel.

 

FOR INSTALLATION REQUIRING A SPLICE, FOLLOW STEPS 6-10;

FOR INSTALLATION WITHOUT A SPLICE, GO TO STEP 11.

Installer Friendly Series

®

SJE-Rhombus

®

 Type IFS w/C-Level

 Sensor

Installation Instructions and Operation/Troubleshooting Manual

Installation

Содержание Installer Friendly Series

Страница 1: ... may be subject to submersion 1 Determine mounting location for panel If distance exceeds the length of either the sensor or float cables or the pump power cables splicing will be required Note For splicing C Level cord use only shielded cable Splice conductors as well as shielding Maximum total cable length is 300 feet For outdoor or wet instal lation we recommend the use of an SJE Rhombus liquid...

Страница 2: ...etween 0 and 39 9 inches of water pressure for the CL40 or between 0 and 99 9 inches of water pressure for the CL100 The C Level sensor reads 0 inches at the approximate point shown in Figure 2 As the liquid level rises the IFS display shows depth of liquid from the zero point The minimum set point for the stop demand or redundant off timed dose level is 4 inches measured from 0 see Figure 2 The m...

Страница 3: ...4 inch minimum set level Figure 1 Figure 2 Installation Instructions Figure 3 Timed Dose Figure 4 Demand Dose 3 ...

Страница 4: ...ill turn off after five minutes of non use Viewing Panel Settings and Cycle Data To view panel settings and cycle data press the NEXT button Each time the NEXT button is pressed the display will advance to the next setting or cycle data Information will be displayed in the following order in Level of the liquid measured from the zero point on the sensor This will be shown in inches or centimeters ...

Страница 5: ...UP button to change the value of the flashing digit When the desired value of the flashing digit is reached push the NEXT button to advance to the next digit Use the UP and NEXT buttons to set the total value of that parameter 4 When done setting the parameter push the set button and the parameter will flash along with its new value If an ERROR message is received check above conditions to ensure ...

Страница 6: ... fuse of the same type voltage and amp rating Alarm Light With power on hold the test normal silence switch in the test position The alarm light should turn on If not replace the light with that of the same type Alarm Horn With power on hold the test normal silence switch in the test position The alarm horn should turn on If not replace the horn with that of the same type Troubleshooting Operation...

Страница 7: ...ed must be cleaned sanitized or decontaminated as necessary prior to shipment to ensure that employees will not be exposed to health hazards in handling said material All applicable laws and regulations shall apply NOTES __________________________________________________________________________________________________________ ________________________________________________________________________...

Страница 8: ..._____________________________________________________________________ __________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________ ____________________________________________________________________________________________________...

Отзывы: