PROGRAMMING INSTRUCTIONS
WITH POWER ON, HOA OFF, FLOATS OFF OR DISCONNECTED, PRESS DESIRED FLOAT BUTTON RAPIDLY 4 TIMES AND HOLD
**PUMP LED WILL FLASH UPON SUCCESSFUL PROGRAMMING**
OPTIONS
FLOAT BUTTON DEFAULT
OPERATION
MANUAL ALARM RESET
STOP
OFF
LATCHES HIGH ALARM: CLEAR WITH EXTERNAL TEST SWITCH
SEAL FAIL ALARM ACTIVATION START
OFF
ACTIVATES HORN UPON SEAL FAIL
ALARM FLASHER
ALARM
OFF
FLASHES BEACON UPON HIGH ALARM
ALARM CONDITIONS
ALARM
BEACON
CONTROLLER LED
HORN
PUMP POWER FAIL FLASHING RED PUMP LIGHT
NO
SEAL FAIL
FLASHING SF1
PROG
FLOAT FAIL
FLASHING BAD FLOAT NOT LIT NO
HIGH ALARM
SOLID
ALARM FLOAT
YES
COMPONENTS
a. ON/OFF Switch - Control/Alarm Power
g. Simulate Float Buttons x3
b. 120V Incoming Power Terminals
h. Float Terminals x6
c. Power LED - (Green)
i. Seal Fail Pot - (Optional)
d. Pump HOA Switch
j. Seal Fail LED - (Red) - (Optional)
e. Float LEDs - (Red) x3
k. Auxiliary Alarm Terminals
f. Pump LED
Pump Run - (Green)
Pump Fail - (Red)
Model shown contains optional Seal Fail circuitry.