INSTALLATION NOTE

Low battery trouble indication: An intermittent “chirp” accompanied by a red LED flash every 32 seconds indicates 
a low battery.
Fault indication: This chirp will occur between the flashes of the red LED indicator light.
SMOKE SENSING CHAMBER OPERATION: This alarm will “chirp” if any of the components in the smoke sensing 
chamber fail. This chirp will occur between the flashes of the red LED indicator light. (If the chirp occurs at the same 
time as the red LED flash, indicating a low battery information).
NOTE: WEEKLY TESTING IS REQUIRED
DANGER: If the alarm sounds, and it is not being tested, it means the unit is sensing smoke, 
THE SOUND OF THE ALARM REQUIRES YOUR IMMEDIATE ATTENTION AND ACTION.

SITERWELL ELECTRONICS CO ., LIMITED

Address:NO.666 Qingfeng Road, Jiangbei District, Ningbo, Zhejiang Province, China

Tel: 0086-574-87729581                          Fax: 0086-574-87729581

E-mail: [email protected]        Http://www.china-siter.com

If you are not sure about the insulation in your mobile home, or if you notice that the outer walls 
and ceiling are either hot or cold, install the alarm on an inside wall. For minimum protection, 
install at least one alarm close to the bedrooms. For additional protection, see SINGLE FLOOR 
PLAN in Figure 3 and MULTIPLE FLOOR PLAN in Figure 4. 

• When mounting an alarm on the ceiling, locate it at a minimum of 4"(10cm) 

  from the side wall (see figure 1).

• When mounting the alarm on the wall, use an inside wall with the top edge 

  of the alarm at a minimum of 4"(10cm) and a maximum of 12"(30.5cm)below 

  the ceiling (see figure 1).

• Put smoke alarms at both ends of a bedroom hallway or large room if the 

  hallway or room is more than 30 ft (9.1 m) long.

• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 

  3 ft (0.9m) of the highest point (measured horizontally). NFPA72 states: 

  "Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 

  2.4m)horizontally shall be located on the high side of the room. " NFPA 72 

  states: "A row of alarms shall be spaced ac'usmated within 3 ft (0.9m) of 

  the peak of the ceiling measured horizontally" (see figure 2).

SINGLE FLOOR PLAN    

Figure 3

 

 

Smoke or smoke/CO alarms for required protection
Smoke or smoke/CO alarms for additional protection
Smoke alarm with silence control for additional protection

MULTIPLE FLOOR PLAN 

Figure 4