-1-
-2-
-3-
Thank you for purchasing our smoke alarm!
Please read these instruc ons carefully and store them in a safe place
where you can access them easily.
Product descrip on and intended use
This is a smoke alarm with an op cal sensor for installa on in residen al
buildings, apartments and rooms with residen al-like use. Smoke alarms
are designed to provide an early warning of fire smoke and fires to
persons present, so that these persons can react appropriately to the
hazardous event. Always consult local regula ons for smoke alarms.
Product specifica ons
Detec on method : Op cal
Power supply : Mains powered with back-up ba ery
Voltage : AC 220-240 V~
Current consump on : <100mA
Mains frequency : 50 Hz
Ba ery life me
: >1 year
Recommended ba eries : 1. Gold Peak GP1604S (9V DC)
: 2. Gold Peak GP1604A (9V DC)
: 3. Raymax 6LR61 (9V DC)
: 4. EVE CR9V/P (9V DC)
Alarm volume : > 85 dB (A) at 3 meters
Alarm sensi vity : 0,095 - 0,175 dB/m
Monitored area : 20 - 40 m²
Opera ng temperature : 0 °C - 40 °C
Opera ng humidity : < 93 %
Date of replacement : See product label
Individual alarm indicator : Yes
Alarm silence facility : Yes | Hush me: 8 minutes
Low ba ery warning : Yes
Installa on in leisure
accommoda on vehicles : No
Moun ng loca on : Ceiling
Interconnectable : Yes | Max amount: 12
Type of wires : 0,8mm² – 1,5mm² or according local
wiring standard
Warnings:
Ÿ
To prevent injury, this apparatus must be securely a ached to the
ceiling in accordance with the installa on instruc ons.
Ÿ
Ba eries should not be exposed to excessive heat such as sunshine,
fire or the like.
• Do not paint or cover the smoke alarm.
• The apparatus shall not be exposed to dripping or splashing and no
objects filled with liquids, such as vases, shall be placed on the
apparatus.
• The smoke alarm, together with any associated supply and
interconnect wiring, shall be installed in accordance with appropriate
na onal electrical installa on regula ons.
Where to install a smoke alarm
Smoke alarms must be installed in such a way that they can be reached
unhindered by the fire smoke so that fires can be reliably detected during
the development phase.
• Install at least in sleeping areas (especially children's rooms);
• Install at least in escape rooms;
• In the middle of the ceiling of a room;
• At least 50 cm away from the wall and other objects;
• Maximum installa on height of 6 meter.
Where to install a smoke alarm in rooms
with special geometries
• Corridors with a maximum width of 3m: Max. 15m between 2 smoke
alarms. Max. 7,5m to the front side of the gallery and smoke alarms at
edges/crossings of corridors.
• Rooms with sloping ceilings:
- If the ceiling inclina on is > 20° to the horizontal: Smoke
alarms must be installed at least 0.5 m and at most 1 m
from the ceiling top.
- Par al roof slopes: If the flat ceiling is ≤ 1m wide, consider
as ceiling inclina on is of > 20°. If the flat ceiling is >1m
wide, consider as flat ceiling.
• Rooms with subdivided ceilings:
- Height of the subdivisions is ≤ 0.2 m: Beams without considera on;
smoke alarm may be installed on the beams as well as on the
ceiling.
- Height of subdivisions is > 0.2 m and area of ceiling panels > 36 m²
: Smoke alarm should be installed in each ceiling panel.
- Height of subdivisions > 0.2 m and area of ceiling panels ≤ 36 m²
: Individual ceiling without considera on.
Where not to install a smoke alarm
• In an environment with a high risk of draught (e.g. close to air
condi oning, fans and ven la on outlets). The movement of air can
impair the penetra on of fire smoke into the smoke alarm.
• Areas where combus ons regularly occurs, such as kitchens.
• Areas with high humidity such as bathrooms, or close to devices such
as dish washers or washing machines.
Ac va on
• Before commissioning the smoke alarm, it is important to ac vate it
and test it for correct opera on.
• Open the ba ery compartment and place the ba ery. Connect the +
on the ba ery to the + on the ba ery compartment and the - ba ery
to the - on the ba ery compartment. Close the ba ery cover.
• Test the correct ac va on of your smoke alarm by pressing the test
bu on. If no sound is generated, the smoke alarm is not ac vated
properly and should not be used!
Moun ng and connec ng
• WARNING: Turn off the mains power before installing this alarm to
avoid the risk of electrical shocks;
• Connect the wires of the AC connector to the mains power supply and
signal wires:
- Brown wire: Connect to live wire of mains power
- Blue wire: Connect to neutral wire of mains power
- White wire: Connect to signal wire to other devices
• Remove the fixing plug from the moun ng plate (if necessary, use a
screw driver for this);
• Pull the AC connector through the
centre hole in the moun ng plate.
• Hold the moun ng plate on the
desired installa on loca on and
mark where holes should be drilled;
• Drill two holes with a diameter of 5
millimetres;
• Push the plas c plugs into the holes;
• Insert the screws into the moun ng
plate, and ghten them firmly into
the plugs;
• Connect the AC connector to the
smoke alarm;
• Fit the smoke alarm on the moun ng
plate and secure it by turning it
clockwise;
Con nue on page 4 >>
Minimum
Op mal
Restric ons
Test bu on
LED indicators
Sound output
Ceiling
AC connector
fixing plug
fixing plug