background image

 

 

 

 

 

SITECO Connect 31 

 

Generation 2 

Commissioning Instruction V1.0 

 
 

Hardware : Controller 5LZ910100A, Sensor 5LZ910200A, Touchpanel 5LZ910300 

date: 2022-05-05 

document ID: 262639-002 

Содержание Connect 31

Страница 1: ...SITECO Connect 31 Generation 2 Commissioning Instruction V1 0 Hardware Controller 5LZ910100A Sensor 5LZ910200A Touchpanel 5LZ910300 date 2022 05 05 document ID 262639 002 ...

Страница 2: ...the Touchpanel to a controller 11 4 8 Connect the Sensor to the controller 13 4 9 Profile function setting on the controller 14 4 10 Calibration of daylight regulation 15 4 11 Additional Setting Manual Override Timeout for Controller 17 4 11 Additional Setting Dimming curve of DALI ECG 17 4 12 Set Lighting Scenes 18 4 13 Configure touchpanel 19 5 Wiring Connection Test 20 5 1 Wiring test pushbutto...

Страница 3: ...ng 28 8 Optional Control with Smartphone 29 8 1 Create an account 29 8 2 Delete account 30 8 3 Log In 30 8 4 Setup network options 32 8 5 Load network into cloud 33 8 6 Share network 34 9 Tips and Tricks 35 9 1 Withdraw authorization 35 9 2 Share administrator rights 36 10 Contact 37 ...

Страница 4: ...3 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 1 Overview Meeting room 1 in an office building will be equipped with SITECO Connect 31 Gen2 ...

Страница 5: ...mi automatic mode manual ON with pushbutton on entrance door D if movement is no longer detected in a lighting scene the lights are switched OFF after the delay time is over 3 Preparations for Commissioning Mounting and electrical wiring of the components according to the mounting instruction An initialization time of max 1 minute must be observed in the event of a mains recovery Once this has exp...

Страница 6: ...uction V1 0 262639 002 4 Commissioning Correctly installed connected components are required 4 1 APP installation Load the SITECO Connect 31 APP onto your smartphone Please note the system requirements Attention iPhone 6 and older not compatible ...

Страница 7: ...6 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 4 2 Setting the language Set the language to English 4 3 Create a network Create a new network called Office Building ...

Страница 8: ...7 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 ...

Страница 9: ... Share information networks option description open The administrator grants authorizations for users which can operate the network without a password password protection The administrator grants authorizations for users which can operate the network with a password only administrator The area network can only be accessed by the administrator edited and operated ...

Страница 10: ...et been added to a network area The red Status LED on the controller must therefore light up red continuously If the Status LED lights up green on the controller this has already been added to another area network You can only insert this into the meeting room by deleting it Please set the following in the app The controller is now automatically inserted into the construction area This can take up...

Страница 11: ...9 002 4 6 Localization assistant Now assign the controller to meeting room 1 Click the red icon first click is turn on the light command then turn off the light command and then cycle Locate the light you are turning on and off and assign it to the meeting room 1 ...

Страница 12: ...ouch panel to meeting room 1 Requirement The touch panel must not yet be assigned to a network area 1 insert the batteries 2 press RESET 5 seconds until the red LED flashes quickly 3 press the upper buttons simultaneously for 3 seconds 4 Press the upper buttons simultaneously for 3 seconds Please set the following in the app ...

Страница 13: ...12 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 The Touchpanel is now automatically inserted into the system This can take up to a minute ...

Страница 14: ... Sensor to the controller Now connect the sensor s to the controller Click the red icon and the red LED on the sensor will flash red for 15 times for location Select sensor 1 and make the necessary settings a Movement Detection Active b Delay time T1 15min c Daylight Detection Active ...

Страница 15: ...shbutton On Off Dim Max min Light Level 1 100 default State after power failure Last state default Ecg dimming curve Linear default Profile Setting Motion Profile Meeting Room Profile Type Motion Daylight Operating mode Semi automatic operation Dimming level D1 100 Profile Setting Daylight Daylighting Functionality Daylight Regulation Daylight Detection Switch on above treshold 20 Switch off deact...

Страница 16: ...hold 20 Switch off deactivated 4 10 Calibration of daylight regulation Now do the calibration of the system with the APP 1 Place a calibrated lux meter on the reference measuring surface 2 Slide the Brightness bar to dimming until the lux meter displays the desired desktop luminance value ...

Страница 17: ... Enter the measured light value in the input field of the APP and start the calibration The calibration can take a little time after successful calibration save the settings 4 Important to active the daylight regulation please switch the luminaires OFF and ON by the APP ...

Страница 18: ...02 4 11 Additional Setting Manual Override Timeout for Controller Now set the Manual Override Timeout for Controller 4 11 Additional Setting Dimming curve of DALI ECG If necessary you can setup the dimming curve of the used driver Default setting linear dimming curve ...

Страница 19: ...truction V1 0 262639 002 4 12 Set Lighting Scenes Now create the 3 lighting scenes for meeting room 1 The creation of a scene is described as an example Meeting room 1 scene Recommended setting meeting 80 presentation 100 beamer presentation 40 ...

Страница 20: ...missioning Instruction V1 0 262639 002 4 13 Configure touchpanel Now insert the touch panel in meeting room 1 and configure it to the required scenes All the necessary settings have now been made You can now start the function test ...

Страница 21: ...20 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 5 Wiring Connection Test 5 1 Wiring test pushbutton D A C B A ...

Страница 22: ...21 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 5 2 Wiring Luminaires B ...

Страница 23: ...SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 5 3 Touchpanel Test Check the function of the touch panel by pressing the individual keys The procedure for a scene is shown as an example D ...

Страница 24: ...23 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 6 Useful Functions 6 1 Assign components to another area ...

Страница 25: ...24 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 6 2 Delete components ...

Страница 26: ...25 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 6 3 Delete area ...

Страница 27: ...26 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 6 4 Delete network ...

Страница 28: ...27 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 6 5 Firmware current update ...

Страница 29: ...e with APP push button not connected correctly check electrical connection controller does not work green red LED on the controller lit controller ready for operation controller does not work red LED means controller was RESETTED by the controllers button configure new with APP DALI wiring check wiring between controller and luminaires touchpanel does not work battery empty or not inserted green L...

Страница 30: ...1 an employee should also be given the option of using a smart phone To do this please establish the Internet connection with your smartphone 8 1 Create an account Create your SITECO Connect 31 Account Now confirm the verification email in your mailbox and follow the instructions You can now start with the commissioning ...

Страница 31: ...30 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 8 2 Delete account 8 3 Log In Log into your account administrator ...

Страница 32: ...31 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 ...

Страница 33: ...tion Networks option description open The administrator grants authorizations for users which can operate the network without a password password protection The administrator grants authorizations for users which can operate the network with a password only administrator The area network can only be accessed by the administrator edited and operated ...

Страница 34: ...33 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 8 5 Load network into cloud Now load the office building network into the SITECO Connect 31 cloud ...

Страница 35: ...are the network with the relevant users You can define as many users as you want The user receives an email for verification The prerequisite is that the user has the SITECO Connect 31 APP and an account After approval the user receives an email for verification and can now use meeting room 1 ...

Страница 36: ...35 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 9 Tips and Tricks 9 1 Withdraw authorization You can withdraw the authorization for meeting room 1 from the user ...

Страница 37: ...36 SITECO Connect 31 Gen2 Commissioning Instruction V1 0 262639 002 9 2 Share administrator rights You can hand over the administrator rights to a colleague Important only one administrator is possible ...

Страница 38: ...ße 50 83301 Traunreut Deutschland Tel 49 8669 33 0 E Mail info siteco com Solution Support Information on control systems control components sensors system commissioning software Georg Simon Ohm Str 50 83301 Traunreut Deutschland Tel 49 8669 33 670 Fax 49 8669 33 540 E Mail Solution Support siteco de siteco com ...

Отзывы: