6. The Hidden Menu

While in “User Menu”,  if      key is pressed for 7 seconds the           message is displayed and hidden 
menu is enterd and then  

upl

 

parameter is displayed. Selected the parameter’s value can be 

displayed by pressing      key and can be changed with          keys. Parameter accessing and saving 
functions can be performed like a "User Menu". All parameters can be accessed from this menu.      

 If              keys are pressed together for 2 seconds; parameter is transferred to the user menu. In this way 
up to 8 parameters can be transferred to the "User Menu".

7. How can we to transfer parameter between menus?

  Program Mode

ERROR MESSAGES

 

  

P

5

C

 Pfa

ALARM SITUATION

5. Changing Parameter Values

 4. Activating / Inactivating The Control Outputs

    

    

    

C.dI

5

C

E

NB

 When in the "Running mode", if        key is pressed for 2 seconds, 

C.dI5

 message is displayed and control outputs becomes to the inactive position, the device 

works as the indicator. When the control outputs are disabled; if       key is pressed for 2 seconds  

C.EnB

   is disabled and the device continues to control function.          

       

If          keys are pressed together for  2 seconds                 is displayed and “User Menu” is entered, then first parameter’s name is displayed in the user menu.

While a parameter is selected, by pressing         key, parameter value can be displayed. This parameter can be changed with            keys. If no operation 
performed for 3 seconds or  during this time,       key is pressed while parameter value displayed, parameter name will be displayed again. While parameter name 
displayed, if by pressing together           keys, "Running Mode" is entered. 

1000

-

24.0

The control ouput becomes inactive.

The control output becomes active.

EA

In “User Menu” if            keys are pressed together for 2 seconds, parameter is removed from “User Menu.
When a parameter is displayed “User Menu”,  

°

F LED lights up in hidden menu. If there is no parameter in 

"User Menu",   

nP

  message is displayed.

1000

-

24.0

SA

Means, thermostat probe is broken.

 Temperature value is higher than the scale.

Means, thermostat probe is short circuit.

Temperature value is lower than the scale.

1.

 Measurements shown flashes when the alarm condition occurs and if 

5ND

 parameter is not  

0

 , audible warning is heard.

2.

 External alarm is active but the outputs are unaffected.

3.

 External alarm is active and in this state, specifies that the relay outputs are turned off (off state).

    While warning, by pressing        key, audible warning can be temporarily disabled.  

FACTORY SETTINGS

If        key is held down while the device is powered up, 

 

d.PAr

 message appears and factory parameters restored.

 FRONT PANEL COMMANDS

1. Viewing and  Changing The Set Value

Measurement 

value

-

30.0

-

29.9

-

30.0

1000

-

24.0

While in "Running Mode", if         key is pressed set value is displayed for 3 seconds. While in this case, the set value is changed with          keys.

Loc

unl

1000

-

24.0

Keys are locked.

Keys are unlocked.

While in  "Running Mode", if             keys are pressed together for 2 seconds, 

 

Loc

 message is displayed and the keys are locked. If the keys are locked

             keys are pressed for 2 seconds again, 

unL

 message is displayed and keys are unlocked. While keys are locked  and  if       key is pressed, set value can be 

displayed but can not be changed. While the keys are locked and if any key is pressed 

( except        key )

,  

Loc

  message appears.

 2. Locking and Unlocking Keys

 3. Manuel Defrost Process

While in the "Running Mode", if       key is pressed for 2 seconds, defrost process starts manually. If   

parameter is 

 

0

 , manual defrost will be inactive.         

d.dur 

*

 When in the "Running Mode", if the control outputs 

are  inactive, 

oFF

 message appears periodically.

Measurement 

value

Measurement 

value

    While warning, by pressing any key, audible warning can be temporarily disabled.  

DEFROST

 LED :

 

Lights up while defrosting process.

°

F

  FAHRENHEIT LED : 

This LED lights up if the temperature unit set to  “

°

F

" or during parameter  value               

                                          displaying. Also, indicates the parameter if its have been in hidden menu.

COMPRESSOR LED : 

Lights up, if the compressor output is activated. It is flashes while waiting compressor delay.

Used for displaying and configuring the selected parameter value.

Used for increasing the setpoint value and changing parameters.
When held down for a few seconds, configured numeric value increases faster.

Used for decreasing the setpoint value and changing parameters.

 

When held down for a few seconds, 

configured numeric value decreases faster.

HEATING LED

 :

 Lights up, if  the output is activated during heating process.

ENDA

EDT5411A

°C

1

2

3

4

5

6

7

8

9

18

17

16

15

14

13

12

11

10

ENDA

EDT5411A

SET

°C

°F

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:18

ENDA

TM

EDT5411-EN-01-191216

2

/4

Содержание Enda EDT5411A

Страница 1: ...EN60529 Front panel IP65 Rear panel IP20 Supply Voltage 230V AC 110V AC 10 20 50 60Hz 12V AC DC 10 24V AC DC 10 or 9 30V DC 7 24V AC SMPS Power Consumption Max 5VA 2 5mm screw terminal connections 1 4 Digits 12 5mm 7 Segment Red LED Connection Scale Sensitivity Accuracy Time Accuracy Display EMC Safety Requirements EN 61326 1 2013 EN 61010 1 2010 Pollution degree 2 overvoltage category II ELECTRIC...

Страница 2: ...specifies that the relay outputs are turned off off state While warning by pressing key audible warning can be temporarily disabled FACTORY SETTINGS If key is held down while the device is powered up d PAr message appears and factory parameters restored FRONT PANEL COMMANDS 1 Viewing and Changing The Set Value Measurement value 30 0 29 9 30 0 1000 24 0 While in Running Mode if key is pressed set v...

Страница 3: ...OTE 2 Please specify at order ENDAKEY if required parameter nd d 5mt Smart Defrost selection no Defrost counter between 2 defrost duration decrease irrespective of d int status of the compressor YE5 Defrost counter decreases as long as compressor work No YE5 No baud Adr5 19 20 1 off Modbus slave device address for device MODBUS COMMUNICATION PARAMETERS Modbus communication speed Baud rate 0 oFF 1 ...

Страница 4: ...rite Read Write Read Write Input Register Addresses Decimal Hex Data Type Data Content Read Write Permission 0000d 0x0000 word Measured temperature value C F 1 2 INPUT REGISTERS Read Parameter Name Holding and Input Register parameters of type integer those signed integer is defined as the decimal port of and associated with these parameters So 14 0 is a parameter value of 140 will be read in Rele...

Отзывы: