background image

  

11

Supervision  Device  (FSD)  is  operating
correctly.  Always  check  that  the  gas  has
stopped  flowing  even  if  you  hear  the  FSD
valve close within the 3-minute period.

Turn  OFF  the  appliance  and  the  gas  supply
and refit the pressure test point sealing screw.
Turn  ON  the  gas  supply  and  check  for  leaks
around  the  pressure  test  point  sealing  screw
with a suitable leak detection fluid.

8

CHECK FOR SPILLAGE

A  SPILLAGE  CHECK  MUST  BE  MADE
BEFORE  THE  INSTALLED  APPLIANCE
IS  LEFT  WITH  THE  CUSTOMER.  DO
THIS  TEST  WITH  ALL  THE  COALS
FITTED  AND  THE  FENDER  AND
ASHPAN  IN  PLACE.  CARRY  OUT  THE
TEST AS FOLLOWS:

8.1

Close all doors and windows in the room
containing the appliance.

8.2

Light the appliance and set to the HIGH
setting.

8.3

Leave  the  appliance  ON  for  5  minutes
then  light  a  smoke  match.  The  match
should  be  inserted  10mm  below  the  top
of  the  opening  and  be  pointed  upwards
at 45° to the horizontal.

   

Move  the  smoke  match  across  the

opening. The installation is satisfactory if
all the smoke is drawn into the chimney.

8.4

If  all  the  smoke  is  not  drawn  into  the
chimney,  leave  the  fire  alight  for  a  further
10  minutes  at  the  HIGH  setting  and  then
repeat the test. If all the smoke is still not
drawn  into  the  chimney,  inspect  the
sealing  to  the  fireplace  surround.  If  the
sealing is satisfactory DISCONNECT THE
APPLIANCE  AND  SEEK  EXPERT
ADVICE.

8.5

Open  all  internal  connecting  doors,
hatches,  etc  in  the  same  room  as  the
appliance. Keep all the doors and windows
that  open  to  the  outside  of  the  building
closed. Re-check for spillage as described
above.  If  an  extractor  fan  is  fitted  in  the
same  room  as  the  appliance  or  a
connecting room, check that spillage does
not occur with the fan operating, all doors,
and  other  openings  between  the  fan  and
the appliance open.

9

FINAL CHECK AND CUSTOMER
BREIFING

9.1

Instruct the customer on the full operation
of the appliance.

9.2

Advise the customer how to assemble the
fuel  effect  as  described  in  these
instructions  and  that  any  build  up  of  soot
can  be  removed  as  described  in
CLEANING  on  page  4  of  these
instructions.

9.3

Advise  the  customer  that  any  cleaning
MUST  be  carried  out  when  the  appliance
is cold.

9.4

Please  explain  to  the  customer  the
purpose  of  the  Oxygen  Depletion  System
(ODS) and in particular the following:

(a) 

The ODS system operates if the Oxygen
level  in  the  room  falls  below  safe  levels
usually  due  to  interruption  of  the
evacuation of combustion products i.e. a
blocked chimney etc.

(b) 

Describe the restart procedures.

(c) 

Point  out  that  on  repeated  operation  of
the ODS system seek expert advice.

9.5

Hand  over  these  instructions  to  the
customer for keeping in a safe place.

9.6

Recommend  that  the  appliance  and
chimney should be inspected and serviced
by a competent person annually.

10

SERVICING

TURN  OFF  THE  GAS  SUPPLY  AND
A L L O W  

T O  

C O O L  

B E F O R E

COMMENCING  ANY  SERVICING.
ALWAYS  TEST  FOR  GAS  SOUNDNESS
AND SPILLAGE AFTER REFITTING THE
APPLIANCE.  (A  LONG  BRUSH  MAY  BE
REQUIRED  TO  REACH  SOME  JOINTS
FOR SOUNDNESS TESTING.)

Check that the appliance is clean and that soot
deposits  or  debris  is  not  blocking  the  gaps
between  coals  causing  an  imperfect  flame
appearance or that stray pieces of soot are not
impairing the electrode spark or pilot burner.

After servicing, make sure that the fuel effect is
correctly  assembled  as  described  on  pages  9
– 15.

VII-11-09

Содержание REMOTE ECO 1

Страница 1: ...NOT A DO IT YOURSELF PRODUCT THIS IS A NATURAL GAS G20 APPLIANCE FOR USE IN GB AND IE ONLY AT A SUPPLY PRESSURE OF 20mbar Our policy is one of constant development and improvement Strict accuracy of illustrations and specifications is not guaranteed Modifications to design and materials may be necessary subsequent to publication Tel 01282 441 771 eco VII 11 09 ...

Страница 2: ...__________________ 2 GENERAL INSTALLATION REQUIREMENTS ___________________ 8 3 CHECK CARTON CONTENTS _______________________________ 4 THE FIREPLACE______________________________________ 5 GAS SUPPLY PIPE _____________________________________ 6 APPLIANCE INSTALLATION _________________________________ 6 7 CHECK FOR GAS SOUNDNESS____________________________ 10 6 8 FUEL BED ASSEMBLY _________________...

Страница 3: ... OR ANY OTHER COMBUSTIBLE MATERIAL IS 766mm FOR COMBUSTIBLE PROJECTIONS ABOVE 150mm DEPTH ADD 12 5mm TO THE ABOVE CLEARANCE FOR EVERY 25mm OF ADDITIONAL PROJECTION DEPTH 8 NEVER THROW PAPER OR OTHER MATERIAL ONTO THE FIRE 9 IT SHOULD BE APPRECIATED THAT ALTHOUGH THIS APPLIANCE CONFORMS TO ALL THE REQUIRED STANDARDS IT IS A DECORATIVE FUEL EFFECT HEATING APPLIANCE WITH AN OPEN FLAME AND CERTAIN PAR...

Страница 4: ...o more than 20 seconds TO SELECT THE REQUIRED FLAME LEVEL To turn down the fire point the handset to the sensor on your fire then push and hold the minus button small flame if you release immediately the flame will go to low if you hold the flame will lower slowly and you can release the button to your desired position To turn the fire up point at the sensor push the plus button until the desired ...

Страница 5: ...d the serial number Both of which can be found on the data badge which is located next to the control knob behind the ash pan cover A full service kit is available FUEL BED ASSEMBLY Using the two brackets supplied in the fixing kit included are two _ screws fold these brackets by hand with the black painted facing forward locate them into the two slots in the burner bracket and fix them in place u...

Страница 6: ...e back row As shown in figure 2A The Coals Pebbles MUST be placed sitting on top of the front ceramic resting between the pillars of the floor matrix as shown in fig 2A and fig 2B This allows the flame path to take its correct direction REAR MATRIX FRONT MATRIX REAR MATRIX FRONT MATRIX FLAME PATH Figure 2B VII 11 09 ...

Страница 7: ...is is due to a series of holes tailored in the hotbox top and canopy fixing face allowing fixture via two self tapping screws Canopy Fixing 1 Place canopy beneath the top of the Hotbox as shown in figure 2c taking care not scratch the paintwork 2 When fixing the canopy locate the fixing holes from beneath behind the canopy screwing up into the hotbox top figure 2d Figure 2c Figure 2d VII 11 09 ...

Страница 8: ...tic Gas Installations and the current building regulations 2 2 The appliance can be used in a builders opening or fireplace conforming to the sizes below The Minimum depth of the opening see Figure 4 dimension C in the case of the Hotbox Eco 1 2 only shall be 180mm and 200mm for the Convector box Eco 1 2 only The minimum front width see Figure 4 dimension A of the chairbrick opening shall be E1 41...

Страница 9: ...s not normally required for this appliance For use in I E ventilation must be in accordance with IS 813 2 15 It is essential that all decorative fenders have a minimum open area of 50cm_ to ensure adequate air supply for correct combustion 3 CHECK CARTON CONTENTS Check the contents are as follows 1 Burner Unit 1 Hotbox or Convector Box eco 1 2 only 1 Isolation Elbow with Nut Olive 1 Set of fuel ef...

Страница 10: ...rick dust and debris entering the pipe and causing a blockage or damage to valves and components 6 4 HAVE YOU PURGED THE GAS SUPPLY PIPES This is essential to expel any foreign matter that might be blown into the valve assembly injector or pilot etc and cause a blockage 6 5 Once the gas supply has been connected and purged then the burner assembly can be refitted in the reverse order to removal en...

Страница 11: ...actor fan is fitted in the same room as the appliance or a connecting room check that spillage does not occur with the fan operating all doors and other openings between the fan and the appliance open 9 FINAL CHECK AND CUSTOMER BREIFING 9 1 Instruct the customer on the full operation of the appliance 9 2 Advise the customer how to assemble the fuel effect as described in these instructions and tha...

Страница 12: ...the firebox sides see Figure 5 Figure 5 10 2 TO REMOVE THE THERMOCOUPLE ASSY a Follow 10 1 above to remove the burner tray b Disconnect the thermocouple connection from the control unit c Remove the pilot tube d Disconnect the spark electrode lead e Remove the two screws fixing the assy 10 3 TO REMOVE THE GAS VALVE a Follow 10 1 above to remove the burner tray b Disconnect the lead from the contro...

Страница 13: ...ay lit or fire goes out in use See Flame Failure Functional Check Uneven flame pattern e g flame at one side only 1 The fuel effect may need adjusting to even the flame pattern See page 6 Blue flames 1 The fire will burn blue on initial lighting until sufficient heat is generated causing the flames to burn yellow Typically 10 minutes 2 Insufficient gas pressure Check the supply pressure to the app...

Страница 14: ... Ensure there is no debris around the spark ignitor e g coal soot etc which could short the spark clean the area IGNITION FUNCTIONAL CHECK 2 NO Consult the User s section in this manual and retry YES Check for damaged or defective control knob spindle or cam operation Check for correct location of peizo components Correct and retry NO Is the valve being operated correctly NO Reset the electrode ga...

Страница 15: ...data badge NO Problem is with the pipework or fittings which lead to the fire YES Run for 3 mins turn off time interval until mag unit shuts with a click Is this greater than 7 seconds YES With the fire running on Full is the gas pressure as stated on the data badge Will the burner stay alight Light the burner and keep the control knob pushed in for 10 20 seconds before letting go Ensure there is ...

Отзывы: