                       ES2 Ethernet/SIOX Gateway p 7 
 
 

 

When contact is established with the unit, the following configurations may be 
checked and changed:

 

 

 

IP-address and Subnet mask

 for the network where the unit eventually will 

be installed. It might be a good idea to perform these changes as the final 
ones after the rest of the configurations are handled. Otherwise, an 
inadvertent restart of the unit will necessitate a repeated recovery process 
as previously described. 

 

 

Default Gateway address

. Used by the ES2 to know where to send 

communications with destination addresses outside the network where it is 
located. Will typically be the address of the firewall/router. 

 

 

TCP port number

 used for SIOX Net communication. This is the port 

number that the central should try to connect to when establishing contact 
with the ES2. Factory default is 1024 which will usually work fine if the unit 
is located on a LAN (Local Area Network) or directly connected to the 
Internet. However, if the unit is located on a LAN and access from Internet 
is desirable, firewall configurations must be considered as well, as they 
normally will prevent connection attempts from the Internet to a LAN. In this 
case a 'hole' thru the firewall specifically directed to the ES2 IP-address 
must be opened. This is perfectly safe for the LAN and will not represent a 
security risk because the ES2 unit does not contain any operating system 
that can be manipulated to perform malicious activity on the LAN. Please 
contact the network administration to check if this is feasible. However, it is 
very important that the firewall configuration will be restored in case the 
ES2 unit is permanently removed. Otherwise another equipment occupying 
the same IP-address could possibly represent a security hazard. 

 

 

ES2 address

 (1 - 63) on the SIOX bus for its virtual SIOX module, thru which 

these configurations are carried out. This address can not be used by any 
SIOX module connected to the SIOX bus. Factory default address is 63.  

 

 

SIOX bus baud rate.

 Available baud rates are 300, 600, 1200, 2400, 4800, 

9600 and 19200 baud. Factory default is 4800 baud. 

 

 

SIOX bus current

 drive capability 0, 25, 50, 75 or 100 mA. Factory default is 

100 mA. 

 

 

Additional SIOX timeout

 (0 - 63 ms), used in conjunction with modems or 

radio modules where delays inherent in these units must be considered. 
Factory default is 0 ms. 

 

                       ES2 Ethernet/SIOX Gateway p 8 
 
 

Start configuration by writing SIOX baud rate to parameter with the Write Enable 
flag set. Refer to 

Parameter Description

 below for further details. If using the 

ES2setup.dff

, simply check the box 

EEPROM Write Enable

 before changing any 

configuration, otherwise it will not be possible to make any changes. 
 
When finished, move the unit to its intended installation point. The new 
configurations will take effect after power is applied. Access to the unit may quickly 
be tested by sending a 'ping' to it. Use 

Visual Setup

 or the intended system 

application for further testing including access to the SIOX bus to verify that all 
connected modules are responding. 
 
 

 

Содержание 6ES2

Страница 1: ...etween a IOX fieldbus provid To simplify insta ounting on standar gable screw connec a standard RJ 45 co t s Communicatio accordance with the CP IP For a des e refer to the EX2 or as file AES X Net an...

Страница 2: ...tween the shield and the bus wires will add to the total capacitive load on the ES2 Ethernet SIOX Gateway p 4 SIOX bus and decrease the maximum distance over which communication can be carried out for...

Страница 3: ...is now connected For instance if the local network is configured to use the 192 168 4 xxx range then the ES2 unit will be accessible at IP address 192 168 4 234 Enter the address in the Server Addres...

Страница 4: ...lated to perform malicious activity on the LAN Please contact the network administration to check if this is feasible However it is very important that the firewall configuration will be restored in c...

Страница 5: ...t tttt 3 300 bits second transmission speed 4 600 bits second transmission speed 5 1200 bits second transmission speed 6 2400 bits second transmission speed 7 4800 bits second transmission speed 8 960...

Страница 6: ...000 00FF16 Fourth byte of subnet mask 0 25510 Parameter 16 000016 Restart unit to effectuate change 0000 00FF16 First byte of Default Gateway address 0 25510 ES2 Ethernet SIOX Gateway p 12 Parameter 1...

Страница 7: ...t voltage 24 V AC DI1 4 Input activation voltage 10 V DC DI1 4 Input activation voltage 10 V AC Environmental Specifications Min Typ Max Unit Operating Temperature Range 0 55 C Storage Temperature Ran...

Отзывы: