Sinope TH1400ZB Скачать руководство пользователя страница 2

The thermostat features two temperature 

regulation modes:

A mode (default): 

Regulation of ambient temperature 

with the possibility to limit floor temperature through an external 

temperature sensor.

F mode: 

Regulation of floor temperature through an 

external temperature sensor with the possibility to limit 

ambient temperature.

11) Circulator pump's anti-seizure

When the thermostat is not heating for an extended period, this 
parameter will activate the main output during 1 minute every 
24 hours to ensure the hydronic system pump does not seize.

TECHNICAL SPECIFICATIONS

Operating voltage:

 24 Vac

Maximum load:  

1 Amp

Setpoint range:  

5 ˚C to 36 ˚C (41 ˚F to 97 ˚F)

Display range:  

0 ˚C to 70 ˚C (32 ˚F to 99 ˚F)

Resolution:  

±

 0,5 ˚C (

±

 1 ˚F)

Storage:  

-20 ˚C to 50 ˚C (-4 ˚F to 122 ˚F)

Auxiliary output:

 24 Vac / Vdc / 0.1 A

Protocol: 

Zigbee 3.0

Frequency:

 2.4 GHz

Transmission power:

 +20 dBm

Receiver sensitivity:

 -108 dBm

Compatible with:

• Baseboard heater activated by mechanical relay 
  or electonic relay (SSR)
• Fan-forced convector activated by mechanical relay 
  or electronic relay (SSR)
•  Electric floor heating (activated by a relay)
•  Hydronic floor heating
• Hydronic heating system
•  Furnace (without fan control)

All of the thermostat's parameters can be set through your 
compatible Zigbee hub. However, if you have not 
connected your thermostat to your Zigbee network 
and wish to change the temperature format or the control 
cycle, you need to:

Transmitter Module IC : 22394-ZBM1501 / FCC ID:2AK2T-ZBM1501 

This device complies with Industry Canada license exempt RSS standard(s). 

Operation is subject to the following two conditions: 

(1) this device does not cause interference, and (2) this device must accept 

any interference, including interference that may cause undesired operation 

of the device.

This equipment has been tested and found to comply with the limits for a 

Class B digital device, pursuant to part 15 of the FCC Rules. These limits are 

designed to provide reasonable protection against harmful interference in a 

residential installation. This equipment generates, uses and can radiate radio 

frequency energy, and if not installed and used in accordance with the 

instructions, may cause harmful interference to radio communications. 

However, there is no guarantee that interference will not occur in a 

particular installation. If this equipment does cause harmful interference to 

radio or television reception, which can be determined by turning the 

equipment OFF and ON, the user is encouraged to try to correct the 

interference by one or more of the following measures:

   Reorient or relocate the receiving antenna.

   Increase the separation between the equipment and receiver.

   Connect the equipment into an outlet on a circuit different from that to  

   which the receiver is connected.

   Consult the dealer or an experienced radio/TV technician for help.

3-year limited warranty

SINOPE TECHNOLOGIES INC. warrants the components of their products against 

defects in material and workmanship for a 3-year period from the date of purchase, 

under normal use and service, when proof of purchase of such is provided to the 

manufacturer. This warranty does not cover any transportation costs that may be 

incurred by the consumer. Nor does it cover a product that has been improperly 

installed, misused or accidentally damaged. 

The obligation of SINOPÉ TECHNOLOGIES INC., under the terms of this warranty, 

will be to supply a new unit and this releases the manufacturer from paying the 

installation costs or other secondary charges linked to replacing the unit or the 

components.

For more information, visit our Website:

660-0735-0020-E

PARAMETERS THAT CAN BE CONTROLLED 

FROM THE DEVICE (CONTINUED):

USER SETTINGS

PARAMETERS THAT CAN BE CONTROLLED FROM 

THE DEVICE (CONTINUED): 

Lower the setpoint to its minimum and hold the       button for 
10 seconds to access the menu.

Press the       or the       button to change the setting.

Press the       and the       buttons simultaneously to save and go 
to the next parameter. Continue to press until the end of the list 
to exit the menu. 

0.15

5

10

15

20

25 30

Convector or baseboard heater 
activated by electronic relay (SSR)

Minimum cycle length (min)

Fan-forced convector activated 
by electronic relay (SSR)

Fan-forced convector or 
baseboard heater activated by 
mechanical relay

Hydronic heating pump system 

Furnace 

To disconnect your thermostat from the GT130 gateway or a 

compatible Zigbee hub, press the       and       buttons simultaneously 

for 10 seconds. The       symbol will disappear from the display.

DISCONNECT YOUR THERMOSTAT FROMT THE GT130 

GATEWAY OR A COMPATIBLE ZIGBEE SYSTEM

Neviweb® is a registered trademark of Sinopé Technologies Inc. in Canada and the United States.
Apple and the Apple logo are trademarks of Apple Inc., registered in the U.S. and other countries. 
App Store is a service mark of Apple Inc., registered in the U.S. and other countries. 
Google Play and the Google Play logo are trademarks of Google Inc.

Alimentez le thermostat.

10 sec.

10 sec.

Alimentez le thermostat.

8) and 9) Main and auxiliary output cycle length

The thermostat has a main and an auxiliary output. 
Select the appropriate cycle length based on your heating 
system. The selection of an inappropriate cycle length may 
damage your unit. 

7) Minimum floor temperature limit (A mode)

The thermostat limits the minimum temperature of the floor in 
order to keep it at a comfortable temperature.

This parameter can only be used when a floor sensor is 
connected to the thermostat.

6) Maximum floor temperature limit (A mode)

The thermostat limits floor heating to the set temperature to 
ensure it does not exceed the selected limit. This parameter is 
ideal for protecting engineered wood floors. (Verify with your 
flooring manufacturer to determine the heat limit.)

This parameter is only usable when a floor sensor is connected 
to the thermostat.

5) Maximum limit of the ambient

temperature (F mode)

Thermostat limits floor heating so as not to exceed the set ambient 
temperature limit.

#

Parameters & settings

Display

8

Name

Aux

Cyc

9

Cyc

6

Max

Floor

Max

Air

10

Sens

11

PE

Maximum floor temperature limit

(Only visible in A mode)

7 °C to 36 °C – (Default: OFF)

7

Min

Floor

Minimum floor temperature limit

(Only visible in A mode)

5 °C to 36 °C - (Default OFF)

Floor sensor

10K or 12K – (Default: 10K)

Circulator pump's anti-seizure

ON or OFF (Default: OFF)

#

Parameters & settings

Display

2

Name

Control

1

Temp

Temperature format

°C or °F – (Default: °C)

Control mode of thermostat

A (Air), F (Floor) – (Default: A)

4

Max

3

Min

Minimum setpoint 

5 °C to 36 °C - (default: 5 °C)

Maximum setpoint 

5 °C to 36 °C - (default: 36 °C)

5

Maximum ambient temperature limit

(Only visible in F mode)

5 °C to 36 °C - (Default OFF)

Cycle lenght / Main output

15 sec, 5 min, 10 min, 15 min, 20 min,

25 min, 30 min – (Default: 15 min)

Cycle lenght / Auxiliary output

OFF, 15 sec, 5 min, 10 min, 15 min, 20 min,

25 min, 30 min – (Default: OFF)

PARAMETERS THAT CAN BE CONTROLLED 

FROM THE DEVICE :