6.

 

EXTRAORDINARY MAINTENANCE 

All operations of extraordinary maintenance must be carried out by specialized personnel only, authorized to operate on electric and 

refrigerating parts. The following section gives indications and suggestions on how to manage and solve possible breakdowns or functioning 

problems. 

Contact our dealers for service, always reporting model and serial number indicated on the specification plate attached on the left side of the 

unit. 

Original spare parts are available at our Technical Service Centres only. 

 

7.

 

BREAKDOWNS 

The following table is a valid and very useful self-support chart for possible problem-solving solutions to any kind of malfunctioning. 

  

MALFUNCTIONING

 

CAUSE

 

SOLUTION

 

The controller doesn’t 

switch on

 

Tension missing. 

Check the line tension and make sure that the plug is 

plugged-into the feeding board. 

Breakdown of the feeding line protection fuses. 

Service by a technician. 

The unit is not cooling 

Malfunctioning of the compressor group. 

Service by a technician. 

Long chilling / freezing 

times 

The portions of product are too big or the trays 

position is not correct. 

Remove some product so as not to exceed the 

recommended weight (see par. 3). 

Overloaded unit. 

See par. 3. 

Excessive creation of frost 

on the evaporator 

Continuous execution of cycles with no pauses. 

Execute a manual defrost between two cycles keeping 

the door open (see par. 4.2.5.). 

Water drain cap missing. 

Place back the cap onto the drain. 

The compressor is not 

working 

Activation of protection. 

Service by a technician. 

The fan is not working 

Broken fan. 

Service by a technician. 

The compressor works but 

the unit is not chilling 

Freon missing. 

Service by a technician. 

Broken line solenoid valve. 

Service by a technician. 

id 

Open door. 

Close the door. 

Broken microswitch. 

Service by a technician. 

HP 

Dirty condenser. 

Clean the condenser (see par. 5.3). 

Space missing for a correct airflow on the front and/or 

back of the unit. 

Move to unit to allow a better airflow (see par. 2.3). 

Water missing (in models with water condensation).  Make sure that the water tap is open and restore the 

water flow. 

Inappropriate ambient temperature (see par. 2.2). 

Place the unit in a cooler place or with better air 

circulation. 

Alarm continues even after the solution suggested. 

Service by a technician. 

AL 

Check the chamber temperature. 

Service by a technician. 

AH 

Check the chamber temperature. 

Service by a technician. 

Pr1 

Broken chamber probe. 

Service by a technician for replacement. 

Pr2 

Broken core probe. 

Service by a technician for replacement. 

 

 

8.

 

DISMANTLING OF THE MACHINE 

The dismantling of the machine should be carried out respecting following warnings: unplug the unit from the power point and cut the feeding 

cable as much near as possible to the unit. Take the doors away and keep children away from the unit, take care not  to damage the 

refrigerating system inside or in the back. The blast chiller does not contain any harmful substance for the ozone layer. The refrigerant gas is 

indicated on the plate outside the unit.  

  

This product is projected and manufactured with high quality materials and components, which can be recycled and reused.  

  

The symbol of a crossed bin with wheels applied on the product means that the product complies with the European Directive 2002/95/EC.   

  

You are required to get all information on this subject at your local recycling centre. 

Содержание AS.003

Страница 1: ...AND OFF OF THE BLAST CHILLER 7 4 2 2 FUNCTIONING 7 4 2 2 1 TEMPERATURE BLAST CHILLING SOFT WITH CORE PROBE 1 CONSERVATION 7 4 2 2 2 TIME BLAST CHILLING SOFT 5 CONSERVATION 7 4 2 2 3 TEMPERATURE BLAST CHILLING HARD WITH CORE PROBE 2 CONSERVATION 8 4 2 2 4 TIME BLAST CHILLING HARD 6 CONSERVATION 8 4 2 2 5 TEMPERATURE DEEP FREEZING HARD WITH CORE PROBE 3 CONSERVATION 8 4 2 2 6 TIME DEEP FREEZING HARD...

Страница 2: ...ENGLISH ...

Страница 3: ...achine e g gas for lighters petrol ether acetone or others The blast chiller is not a refrigerated cabinet As soon as the working cycles are over the unit turns automatically into a temporary and transitional conservation phase At the end of the cycle the product is to be stored in an appropriate refrigerator As deep freezing of foodstuff is regulated by law a qualifying license issued by the Loca...

Страница 4: ... the front bottom of the unit If the blast chiller is not correctly leveled its functioning and condensation flow may be compromised In the roll in units the condensation drain should be kept free at least 20 mm from the nearby drain Remove the protective film and clean the machine inside and outside using protective gloves Wash the unit inside using a light detergent avoiding the use of steel woo...

Страница 5: ...led lower than the blast chiller no syphons are needed the pipe inclination towards the compressor unit should be respected at least 3mm mt Gas proof soldering must be executed and the pipes must be emptied through both service taps Check for eventual leaks turn on the taps in the compressor unit and add gas R404A if necessary checking the liquid sign Add oil type Artic 32 synthetic if necessary c...

Страница 6: ...ctions The standard working cycles are as follows TEMPERATURE BLAST CHILLING SOFT WITH CORE PROBE 1 CONSERVATION This cycle reduces the food temperature to 3 C at the core of the product with chamber temperature around 0 C Suitable for delicate or thin products TEMPERATURE BLAST CHILLING HARD WITH CORE PROBE 2 CONSERVATION This cycle reduces the food temperature down to 3 C at the core of the prod...

Страница 7: ... 4 2 2 2 TIME BLAST CHILLING SOFT 5 CONSERVATION Press and release the button the led will start flashing the display will show the temperature of end cycle which can be modified with the buttons and the value 3 0 is recommended Press and release the button the led and will be steadily lighted and the working cycle including the conservation phase will start The check for the correct introduction ...

Страница 8: ... the conservation phase will start The check for the correct introduction of the core probe will be activated If this test is successfully executed the cycle will go on in temperature mode 3 if the test is not successfully executed the cycle will go on as time cycle in mode 7 the led will go off and the led will switch on At this point within 5 minutes press the button or to change the duration of...

Страница 9: ...t up To take the product out press the button to stop the unit remove the core probe and lay it back into the probe holder take the trays out and store the product in the provided refrigerated cabinets 4 3 RAW FISH SANITATION CYCLE The raw fish sanitation cycle consists in a special deep freezing cycle to 20 C at the core of the product followed by a 24 hours maintenance stage This kind of sanitat...

Страница 10: ... products which might corrode or scratch the surfaces In short the blast chiller must be clean when used and must be left clean at the end of every working session The racks are easily removable for cleaning Reposition them once they have been washed It is important to carefully wash the inside of the unit and the door Do not scrape with sharp tools especially the cool generator Remove the drain c...

Страница 11: ...ce by a technician The compressor works but the unit is not chilling Freon missing Service by a technician Broken line solenoid valve Service by a technician id Open door Close the door Broken microswitch Service by a technician HP Dirty condenser Clean the condenser see par 5 3 Space missing for a correct airflow on the front and or back of the unit Move to unit to allow a better airflow see par ...

Страница 12: ... 0 8 60 70 0 260 AS 005C 5 12 AS 005ST 5 12 230 1 50 5 0 0 9 80 70 0 500 AS 005 5 15 230 1 50 5 5 1 0 100 70 0 550 AS 005 5 20 230 1 50 7 0 1 3 100 70 0 700 AS 005SG 230 1 50 2 0 0 3 85 70 0 000 AS 007 7 20 230 1 50 7 0 1 3 130 70 0 800 AS 007 7 30 230 1 50 8 5 1 5 130 70 0 900 AS 007SG 230 1 50 2 0 0 3 110 70 0 000 AS 010 10 30 230 1 50 9 0 1 6 190 70 1 000 AS 010SG 230 1 50 2 5 0 4 190 70 0 000 ...

Страница 13: ...ENGLISH 13 10 WIRING DIAGRAMS ...

Страница 14: ...ENGLISH 14 NOTE ...

Страница 15: ...ENGLISH ...

Страница 16: ... In the event that the notification is not accepted A T O s r l reserves the right to hold this warranty valid thus making known this intention on pain of ineffectiveness in writing fax is admitted or by phone within five days from receipt of the notification For the applicability of this warranty the existence of a production defect is left to the exclusive technical assessment of A T O S r l whi...

Отзывы: