2.  Fan state: 

Display   

Corresponding mode 

Off 

Low fan   

High fan 

3.  Opening degree of EXV: 

Opening degree equals the display data times 8; 

4.  Number of indoor unit 

The indoor unit that can communicate with outdoor unit normally. 

 

7.11 Outdoor fan speed control 

There is one fan with two-speed, the fan speed is controlled according ambient temp. After 

the compressor stop, 30 seconds later the fan stop.   

When cooling: 

> 27 

High speed 

Ambient temp.rise 

<27 

Low speed 

>25 

High speed   

Ambient 

temp.decline 

<25 

Low speed 

When heating: 

> 14 

Low speed 

Ambient temp.rise 

<14 

High speed   

>12 

Low speed 

Ambient 

temp.decline 

<12 

High speed   

 

7.12 Oil return function 

If operation frequency is lower than 54Hz in 2 hours consecutively, it will be increased to 62Hz 

for 3 minutes. Then it recovers to the former operation frequency.   

Содержание SMF-4E27AI

Страница 1: ...1 MULTI SPLIT TYPE HEAT PUMP AIR CONDITIONERS Technical service manual R410A Cassette Inverter multi Series Indoor Models SMF C09AI SMF C12AI SMF C18AI Outdoor Models SMF 4E27AI...

Страница 2: ...2 CONTENTS 1 Features 2 Specification 3 Outline and dimension 4 Indoor unit combination 5 Capacity table 6 Wiring diagram 7 Electronic control functions 8 Exploded view...

Страница 3: ...3 1 Features 1 Fashion design quality life 2 Low operation noise 3 High efficiency screw fan 4 Equal fast wide angle cooling more comfortable...

Страница 4: ...of rows 2 2 2 b Tube pitch a x row pitch b mm 21x13 37 21x13 37 21x13 37 c Fin spacing mm 1 3 1 3 1 3 d Fin type code Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium e Tube outside...

Страница 5: ...28 28 36 Dimension W H D mm 650x30x650 650x30x650 650x30x650 Packing W H D mm 715x115x715 715x115x715 715x115x715 Indoor unit panel Net Gross weight panel Kg 3 5 3 5 3 5 Application area m2 14 21 18...

Страница 6: ...city range Btu h 9000 18000 16000 25000 21000 27000 28000 Rated input power range W 850 1790 1470 2520 2020 2650 2700 Rated current range A 3 5 7 5 6 1 10 5 8 43 11 1 11 3 Heating COP 10 4 Max input c...

Страница 7: ...Outdoor air flow m3 h 3500 Outdoor noise level dB A 57 Dimension W H D mm 895X860X330 Packing W H D mm 1043X915X395 Outdoor unit Net Gross weight Kg 80 84 Refrigerant type and charge g R410A 2700 Des...

Страница 8: ...nation 7K X4 setting temp 17 setting fan speed high speed 2 Nominal heating capacities are based on the following conditions Indoor temp 20 CDB Outdoor temp 7 CDB 6 CWB Equivalent ref Piping 8m horizo...

Страница 9: ...18k 580 Body 67 600 Ceiling hole 650 Panel 401 Hook location 611 Hook location 580 Body 422 28 5 600 Ceiling hole 650 Panel Drain side and Tubing side A 600 Hook 265 Panel Chart 4 Body Nut Ceiling Out...

Страница 10: ...e indoor unit capacity will attenuate That means you can not gain the nominal capacity but smaller than it We are out of responsibility if customers don t follow the notice below 1 You can connect two...

Страница 11: ...9 63 9 09 8 72 8 45 Sensitive capacity kW 8 36 7 99 7 70 7 27 6 98 6 76 32 C D 23 C W Input kW 2 50 2 85 3 21 3 57 3 92 4 28 HEATING OUTDOOR CONDITIONS Indoor Conditions 24 C D 18 C W 12 C D 11 C W 7...

Страница 12: ...12 6 WIRING DIAGRAM Indoor unit...

Страница 13: ...13 Outdoor unit SMF 4E27AI...

Страница 14: ...n 25A the compressor stops 9 Outdoor condenser high temperature protection Under cooling mode if T3 65 for 3 minutes the compressor will stop When T3 52 the protection is not valid 10 Outdoor low temp...

Страница 15: ...on T Indoor exchanger temp Indoor fan speed T 34 Off 34 T 37 Breeze 37 T 44 Low speed Indoor exchanger temp up T 44 Setting fan speed T 38 Setting fan speed 33 T 38 Low speed 24 T 33 Breeze Indoor exc...

Страница 16: ...heating at same time Heating mode has a priority 7 3 1 Definition Cooling mode Heating Mode Fan Off Cooling mode No Yes No No Heating Mode Yes No Yes No Fan No Yes No No Off No No No No No No mode con...

Страница 17: ...y locked When test the cooling capacity the frequency can be locked at 78Hz by following the below 1 Set the indoor temp to 17 and high speed 2 Push the outdoor check button for 5 seconds then its fre...

Страница 18: ...tdoor communication error P0 Compressor top protection against temperature P1 High pressure protection P2 Low pressure protection P3 Compressor current protection P4 Inverter module protection P5 Outd...

Страница 19: ...speed is controlled according ambient temp After the compressor stop 30 seconds later the fan stop When cooling 27 High speed Ambient temp rise 27 Low speed 25 High speed Ambient temp decline 25 Low...

Страница 20: ......

Страница 21: ...lle 2 50112111024 2114200446 26 4 Filter 1 50112111025 2114200443 26 5 Control box 1 50112111026 2114200441 26 6 LED holder 1 50118121041 2114200420 26 7 Control board 1 50118121042 2334209008 26 8 Co...

Страница 22: ......

Страница 23: ...3 Switch air inlet grille 2 50112111024 2114200446 26 4 Filter 1 50112111025 2114200443 26 5 Control box 1 50112111026 2114200441 26 6 LED holder 1 50118121041 2114200420 26 7 Control board 1 5011812...

Страница 24: ......

Страница 25: ...box 1 50112111026 2114200441 26 6 LED holder 1 50118121041 2114200420 26 7 Control board 1 50118121042 2334209008 26 8 Cover control box 1 50112111027 2114200447 26 9 Fan guide 4 50112111028 21142004...

Страница 26: ...550002 3 Holder for fan motor 1 2123549027 4 fan motor 1 2240041722 5 Front net 1 2124550017 6 Front clapboard 1 2124532935 7 Separating board 1 2124820000 8 Left clapboard 1 2124530063 9 Little handl...

Страница 27: ...2165739000 21 Rear right clapboard 1 2125739003 22 Cabinet Front Right 1 2124532903 23 installation board for valve 1 2125739002 24 drain pan 1 2113560000 25 Capillary pipe Ass y 1 2165739006 26 Base...

Отзывы: