Sinclair MV-H**BIF series Скачать руководство пользователя страница 21

19

Service Manual

1. Select the installation location according to the require-

ment of this manual.(See the requirements in installation

part)

2. Handle unit transportation with care; the unit should not

be carried by only one person if it is more than 20kg.

3. When installing the indoor unit and outdoor unit, a suffi

-

cient fixing bolt must be installed; make sure the installation

support is firm.

4. Ware safety belt if the height of working is above 2m.

5. Use equipped components or appointed components dur-

ing installation.

6. Make sure no foreign objects are left in the unit after fin

-

ishing installation.

Electrical Safety Precautions:

7. Notes for Installation and Maintenance

Safety Precautions: 

Important!

Please read the safety precautions carefully before 

installation and maintenance.

The following contents are very important for installation 

and maintenance.

Please follow the instructions below.

●The installation or maintenance must accord with the

instructions.

●Comply with all national electrical codes and local

electrical codes.

●Pay attention to the warnings and cautions in this

manual.

●All installation and maintenance shall be performed by

distributor or qualified person.

●All electric work must be performed by a licensed

technician according to local regulations and the 

instructions given in this manual.

●Be caution during installation and maintenance. Prohibit

incorrect operation to prevent electric shock, casualty and

other accidents.

1. Cut off the power supply of air conditioner before

checking and maintenance.

2. The air condition must apply specialized circuit and

prohibit share the same circuit with other appliances.

3. The air conditioner should be installed in suitable

location and ensure the power plug is touchable.

4. Make sure each wiring terminal is connected firmly

during installation and maintenance.

5. Have the unit adequately grounded. The grounding

wire can’t be used for other purposes.

6. Must apply protective accessories such as protective

boards, cable-cross loop and wire clip.

7. The live wire, neutral wire and grounding wire of

power supply must be corresponding to the live wire,

neutral wire and grounding wire of the air conditioner.

8. The power cord and power connection wires can’t be

pressed by hard objects.

9. If power cord or connection wire is broken, it must be

replaced by a qualified person.

1. Avoid contact between refrigerant and fire as it generates

poisonous gas; Prohibit prolong the connection pipe by

welding.

2. Apply specified refrigerant only. Never have it mixed with

any other refrigerant. Never have air remain in the refrigerant

line as it may lead to rupture or other hazards.

3. Make sure no refrigerant gas is leaking out when

installation is completed.

4. If there is refrigerant leakage, please take sufficient

measure to minimize the density of refrigerant.

5. Never touch the refrigerant piping or compressor without

wearing glove to avoid scald or frostbite.

Warnings

Refrigerant Safety Precautions:

Improper installation may lead to fire hazard, explosion, 

electric shock or injury.

Installation Safety Precautions:

Part 

: Installation and Maintenance 

10. If the power cord or connection wire is not long enough,

please get the specialized power cord or connection wire

from the manufacture or distributor. Prohibit prolong the wire

by yourself.

11. For the air conditioner without plug, an air switch must

be installed in the circuit. The air switch should be all-pole

parting and the contact parting distance should be more than

3mm.

12. Make sure all wires and pipes are connected properly and

the valves are opened before energizing.

13. Check if there is electric leakage on the unit body. If yes,

please eliminate the electric leakage.

14. Replace the fuse with a new one of the same specification

if it is burnt down; don’t replace it with a cooper wire or

conducting wire.

15. If the unit is to be installed in a humid place, the circuit

breaker must be installed.

Содержание MV-H**BIF series

Страница 1: ...MULTI VARIABLE SERIES WALL MOUNTED FOCUS MV HxxBIF SERVICE MANUAL EN...

Страница 2: ...Original instructions IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference...

Страница 3: ...intenance 19 7 Notes for Installation and Maintenance 19 8 Installation 24 8 1 Installation Dimension Diagram 24 8 2 Installation Parts checking 26 8 3 Selection of Installation Location 26 8 4 Requir...

Страница 4: ...1 Service Manual 1 Summary Indoor Unit Part Technical Information Remote Controller YAC1FB9 WiFi...

Страница 5: ...3 Service Manual 2 2 Noise Criteria Curve Tables...

Страница 6: ...Unit mm Model W H D 09K 790 275 200 12K 845 289 209 18K 970 300 224 24K 1078 325 246 W 12K 09K D H 90 150 54 168 5 462 159 5 55 55 54 123 5 542 179 5 83 2 124 7 35 55 55 35 18K 104 685 181 140 190 38...

Страница 7: ...ilter filter filter C2 C3 D3 D2 B3 B2 A2 A3 A1 A unit electronic expansion valve B1 B unit electronic expansion valve C1 C unit electronic expansion valve D1 D unit electronic expansion valve A2 A uni...

Страница 8: ...l Color Symbol Symbol Color Symbol Name WH White GN Green CAP Jumper cap YE Yellow BN Brown COMP Compressor RD Red BU Blue Grounding wire YEGN Yellow Green BK Black VT Violet OG Orange Note Jumper cap...

Страница 9: ...5220 78 57 5 9 5 1 63 2 5 3 63 63 6 1 8 0 83 2 1 02725 67 33 1 6 1 5 67 33 1 02725 7 5 7 0 7 7 1 8 5 2 3 60 1 5 725 35 17 5 8 7 2 5 3 803 3 1 1 7 3 9 325 725 2 7 50 1 8 8 1 20 287 1 11 7 1 1 0 1 0272...

Страница 10: ...ace of fan 6 Interface of health function live wire 7 8 Auto button Interface of WIFI 9 Up down swing interface Interface of PG feedback 10 11 12 Needle stand for tube temperature sensor 13 Display in...

Страница 11: ...ller that the unit will keep the original running status After putting through the power the air conditioner will give out a sound Operation indicator is ON red indicator the colour is different for d...

Страница 12: ...the unit by pressing ON OFF button indoor fan will continue running for a few minutes at low speed In this period Hold fan speed button for 2s to stop indoor fan directly Having set X FAN function of...

Страница 13: ...first entering will display according to the initial curve setting value of original factory 2 Adjust and button could change the corresponding setting temperature after adjusted press Turbo button fo...

Страница 14: ...peed is not available The Quiet function is only available for some models When quiet function is selected Under cooling mode indoor fan operates at notch 4 speed 10 minutes later or when indoor ambie...

Страница 15: ...13 Service Manual...

Страница 16: ...14 Service Manual...

Страница 17: ...alled register the account and add the device to achieve long distance control and LAN control of smart home appliances For more information please refer to Help in App 6 3 Ewpe Smart App Operation Ma...

Страница 18: ...r each condition Ambient temperature is Tamb Tcompensation for heat pump unit and Tamb for cooling only unit 4 If there s I feel function Tcompensation is 0 Others are same as above 5 Fan mode Under t...

Страница 19: ...overy If the complete unit is at ON status the unit will operate according to original operation mode 11 Ambient temperature display control mode 1 When user set the remote controller to display set t...

Страница 20: ...Cooling drying Indoor fan stops operation Heating Cooling drying fan Indoor unit B Heating Indoor fan stops operation Fan Heating Indoor unit A Indoor fan stops operation Heating Note 1 Indoor unit A...

Страница 21: ...y grounded The grounding wire can t be used for other purposes 6 Must apply protective accessories such as protective boards cable cross loop and wire clip 7 The live wire neutral wire and grounding w...

Страница 22: ...it at the place where there may be leaked corrosive gas or flammable gas If there leaked gas around the unit it may cause explosion and other accidents 7 Do not use extension cords for electrical conn...

Страница 23: ...tinuous ventilation status should be kept during the operation process Check whether there is fire source or potential fire source in the maintenance area The naked flame is prohibited in the maintena...

Страница 24: ...d gas valve are fully closed and power is disconnected before detaching the connection pipe If compressor starts running when stop valve is open and connection pipe is not yet connected air will be su...

Страница 25: ...roprobe 7 Electronic leakage detector 10 Pipe pliers pipe cutter 2 Screw driver 5 Universal meter 8 Vacuum pump 11 Pipe expander pipe bender 3 Impact drill drill head electric drill 6 Torque wrench op...

Страница 26: ...allation 8 1 Installation Dimension Diagram Drainage pipe At least 250cm At least 15cm At least 300cm Space to the Space to the ceiling Space to the obstruction At least 15cm At least 15cm Space to th...

Страница 27: ...he bound pipes pass through the wall hole and then connect outdoor unit Neaten the pipes Vacuum pumping and leakage detection Check after installation and test operation Finish installation Note this...

Страница 28: ...special circumstances 7 Do not use the unit in the immediate surroundings of a laundry a bath a shower or a swimming pool 2 Grounding Requirement 1 The air conditioner is first class electric applian...

Страница 29: ...rench moment of force Fig 5 Fig 6 Fig 7 5 Connect the Pipe of Indoor Unit 1 Aim the pipe joint at the corresponding bellmouth As show in Fig 5 2 Pretightening the union nut with hand 3 Adjust the torq...

Страница 30: ...drain hose with the band As show in Fig 14 2 Reserve a certain length of drain hose and power cord for installation when binding them When binding to a certain degree separate the indoor power and the...

Страница 31: ...It may cause insufficient cooling heating capacity 10 The dust and sundries caused during installation are removed It may cause malfunction or damaging the parts 11 The gas valve and liquid valve of c...

Страница 32: ...nsor malfunction Hardware malfunction b7 blink 22 times IPM sensor circuit malfunction Hardware malfunction P7 blink 18 times Outdoor ambient sensor open or short circuit Hardware malfunction F3 blink...

Страница 33: ...essor exhaust high temperature protection E4 blink 4 times Anti high temperature protection E8 blink 8 times AC over current protection E5 blink 5 times Over compressor phase current protection P5 bli...

Страница 34: ...ess Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted Start Insert the temperature sensor tightly Yes Yes Yes Yes Yes Yes No No No No No No Is malfu...

Страница 35: ...f PG motor control terminal is firm Turn on the unit again measure whether the output voltage on control terminal for PG motor is more than 50V within 1 min after the louvers are opened Tighten the sc...

Страница 36: ...is defined abnormal Malfunction diagnosis process Start Is there jumper cap on the mainboard Is the jumper cap inserted correctly and tightly Replace the jumper cap with the same model Appearance of t...

Страница 37: ...The zero cross detectioncircuit of the mainboard is defined abnormal Malfunction diagnosis process Turn power off for 1minute the turn back on The unit returns to normal Conclusion U8 is displayed due...

Страница 38: ...Replace the mainboard with the same model End Is the supply voltage too low with overload Is the indoor outdoor heat exchanger dirty or are the air inlet and outlet blocked The fan is abnormal Fan sp...

Страница 39: ...ature is higher than 53 C If the airflow of indoor and outdoor unit is good If the indoor and outdoor fan are running normally Replace outdoor mainboard Connect normally Adjust the connection Replace...

Страница 40: ...s eliminated Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Check motor and re install the motor to make it run normally Make compressor run normally Remove blockage in...

Страница 41: ...to point 4 of maintenance method for details Malfunction of compressor Compressor can t operate Refer to point 5 of maintenance method for details 1 Air Conditioner Can t be Started Up 2 Poor Cooling...

Страница 42: ...drain pipe Wrapping is not tight Water leaking from the pipe connection place of indoor unit Wrap it again and bundle it tightly 5 Compressor Can t Operate Possible causes Discriminating method air co...

Страница 43: ...emove filter assy 2 Remove horizontal louver Front panel Front case Right filter Groove Left filter Open the front panel Push the left and right filters to make them break away from the groove on the...

Страница 44: ...ifferent for different models Loosen the connection clasps between vertical louver and bottom case to remove vertical louver Loosen the connection clasps between front case sub assy and bottom case Li...

Страница 45: ...s that are locking lead wire and rotate the electric box assy Twist off the screws that are locking wire clip Loosen the power cord and remove its wiring terminal Lift up the main board and take it of...

Страница 46: ...l out the holder for some terminals at first holder is not available for some wiring terminal hold the connector and then pull the terminal Circlip Soft sheath Holder Connector Procedure Step Remove 3...

Страница 47: ...e connection place of cross flow blade and motor lift the motor and cross flow blade upwards to remove them Remove the bearing holder sub assy Remove the screw fixing step motor and then remove the st...

Страница 48: ...76 75 2 24 84 85 84 2 29 68 68 20 77 77 25 86 86 30 Appendix 2 Configuration of Connection Pipe 4 The additional refrigerant oil and refrigerant charging required after prolonging connection pipe Afte...

Страница 49: ...Cut the pip Confirm the pipe length according to the distance of indoor unit and outdoor unit Cut the required pipe with pipe cutter B Remove the burrs Remove the burrs with shaper and prevent the bu...

Страница 50: ...37 9 003 76 2 133 115 0 66 1 51 59 38 8 642 77 2 064 116 0 642 0 49 02 39 8 297 78 1 997 117 0 625 1 46 6 40 7 967 79 1 933 118 0 608 2 44 31 41 7 653 80 1 871 119 0 592 3 42 14 42 7 352 81 1 811 120...

Страница 51: ...2 51 75 2 94 114 0 904 2 72 41 37 12 76 2 844 115 0 88 1 68 79 38 11 52 77 2 752 116 0 856 0 65 37 39 11 06 78 2 663 117 0 833 1 62 13 40 10 62 79 2 577 118 0 811 2 59 08 41 10 2 80 2 495 119 0 77 3 5...

Страница 52: ...4 103 3 04 13 323 9 26 47 08 65 10 18 104 2 96 12 306 2 27 45 07 66 9 83 105 2 87 11 289 6 28 43 16 67 9 49 106 2 79 10 274 29 41 34 68 9 17 107 2 72 9 259 3 30 39 61 69 8 85 108 2 64 8 245 6 31 37 96...

Страница 53: ...PARTS GUIDE MULTI VARIABLE SERIES WALL MOUNTED FOCUS MV HXXBIF...

Страница 54: ...MV H07BIF...

Страница 55: ...20874 1 AX 16 Connecting pipe clamp 2611216401 1 AB 17 Rubber Plug Water Tray 76712012 1 AC 18 Stepping Motor 1521212901 1 AF 19 Crank 73012005 1 AB 20 Electric Box Assy 100002002491 1 BB 21 Axile Bus...

Страница 56: ...MV H09BIF...

Страница 57: ...120874 1 AX 16 Connecting pipe clamp 2611216401 1 AB 17 Rubber Plug Water Tray 76712012 1 AC 18 Stepping Motor 1521212901 1 AF 19 Crank 73012005 1 AB 20 Electric Box Assy 100002062337 1 BB 21 Axile Bu...

Страница 58: ...MV H12BIF...

Страница 59: ...12146 1 AX 16 Connecting pipe clamp 2611216401 1 AB 17 Rubber Plug Water Tray 76712012 1 AC 18 Stepping Motor 1521210108 1 AG 19 Crank 73012005 1 AB 20 Electric Box Assy 100002062377 1 21 Axile Bush 1...

Страница 60: ...MV H18BIF...

Страница 61: ...AN 19 Fan Motor 1501214502 1 AX 20 Motor Press Plate 26112511 1 AE 21 Wall Mounting Frame 01362026 1 AK 22 Connecting pipe clamp 2611218801 1 AB 23 Crank 73012005 1 AB 24 Stepping Motor 1521240212 1 A...

Страница 62: ...MV H24BIF...

Страница 63: ...26112515 1 AE 18 Fan Motor 15012145 1 AZ 19 Connecting pipe clamp 26112514 1 AB 20 Drainage Hose 0523001405 1 AD 21 Stepping Motor 1521240212 1 AG 22 Crank 73012005 1 AB 23 Guide Louver 1051232001 1 A...

Страница 64: ...NT MEDIUM This unit is containing fluorinated gases included in the Kyoto protocol The maintenance and the liquidation must be carried out by qualified personnel Type of refrigerant R32 The quantity o...

Отзывы: