Malfunction analysis

Error Code

● When air conditioner status is abnormal, temperature indictor on indoor unit will

   ation of error code.

Indoor 

display

Error code

Above indicator diagram is only 

for reference. Please refer to 

actual product for the actual

indicator and position.

■ When below phenomenon occurs, please turn off air conditioner and discon-

   for service.      

      ● Power cord is overheating or damaged.

      ● There

s abnormal sound during operation.

      ● Circuit break trips off frequently.

      ● Air conditioner gives off burning smell.

      ● Indoor unit is leaking.

■ If the air conditioner operates under abnormal conditions, it may cause

Note: 

service.

Error code

Troubleshooting

 

 

 

Means defrosting status. It’s the normal phenomenon.

Heating indicator ON 10s OFF 0.5s

 

E5: overcurrent protection

Power indicator blinks and E5 is displayed

C5:Connector jumper malfunction 

Check if the connector jumper contacts the 

properly. If replace the PCB, please take off 

the old for the new PCB.

F1:Indoor ambient temp. sensor 

malfunction

Check if indoor room temp. sensor is connected 

properly?

malfunction

F2:Evaporator temp.sensor

Check if indoor tube temp. sensor is

connected properly?

Feedback terminal of PG motor hasn’t been 

connected firmly.

The control end of PG motor hasn’t been

connected firmly.

Fan blade hasn’t been installed correctly 

and it can’t run smoothly.

Motor hasn’t been installed correctly and tightly.

Motor has been damaged.

Control panel has been damaged.

H6:PC motor (indoor fan) can’t run

Control panel has been damaged.

U8:Malfunction of zero cross detection 

circuit for PG motor (indoor fan)



WARNING

19

Содержание MS-H07AICN PT

Страница 1: ...USER S MANUAL MS H07AICN PT MS H09AICN PT MS H12AICN PT MS H18AICN PT NEW MULTI SYSTEM ...

Страница 2: ... Original instructions ...

Страница 3: ...ntenance Clean and maintenance 13 Malfunction Malfunction analysis 17 Installation Notice Installation dimension diagram 20 Tools for installation 21 Selection of installation location 21 Requirements for electric connection 22 Installation Installation of indoor unit 23 Check after installation 28 Test and operation Test operation 28 Attachment 29 This appliance is not intended for use by persons...

Страница 4: ...ppliance Cleaning and user maintenance shall not be made by children without supervision years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Do not wash the air conditioner with water to avoid electric ...

Страница 5: ...damage Precautions WARNING conditioner and disconnect power immediately and then If the air conditioner operates under abnormal conditions it may cause malfunction electric shock or fire hazard Do not spill water on the remote controller otherwise the electric shock or damage Please contact dealer when you need to repair air conditioner Do not repair air conditioner by yourself It may cause object...

Страница 6: ...bles before using the air conditioner An all pole disconnection switch having a contact separation Must follow the electric safety regulations when installing the unit grounding wire of power socket Properly connect the live wire neutral wire and any work related to electricity and safety Be sure to cut off the power supply before proceeding Including an circuit break with suitable capacity please...

Страница 7: ...onnected by a professional national wiring regulations requirement of NEC and CEC by authorized personnel only Precautions WARNING wire which can t be used for other purposes The grounding resistance should comply with national electric safety regulations The air conditioner is the first class electric appliance It keep the interconnection cable away from the copper tube The temperature of refrige...

Страница 8: ...be installed in the line For the air conditioner without plug an circuit break Select a location which is out of reach for children and For the air conditioner with plug the plug should be Working temperature range NOTICE Indoor side DB WB C Outdoor side DB WB C Maximum cooling 32 23 43 26 Maximum heating 27 24 18 The operating temperature range outdoor temperature for cooling is 15 43 Heating tem...

Страница 9: ...izontal louver air outlet heating indicator temp indicator cooling indicator power indicator receiver window drying indicator display remote control NOTICE Actual product may be different from above graphics please refer to actual products ON OF F MOD E FAN SW I NG I FEE L SLEE P TE M P TI MER ON CLOCK T OF F IMER TURBO LIGHT X FAN F C H O U R ONOFF 6 ...

Страница 10: ...it to decrease temperature setting FAN Press it set swing angle TIMER ON SWING TIMER OFF CLOCK X FAN page 9 TEMP page 9 TURBO page 9 SLEEP page 9 LIGHT Press it to set fan speed Press it to set auto on timer Press it to set auto off timer Press it set clock 1 7 Press it to set HEALTH or AIR function 8 I FEEL Page 8 4 3 2 5 6 11 13 12 16 10 14 9 15 Operation of Remote Controller 3 15 5 4 14 7 16 13...

Страница 11: ... pressed current operation mode icon AUTO COOL DRY FAN or HEAT only for heat pump models will show 17 is displayed when pressing the up down swing down button Press this button again to clear the display 21 Up down swing icon After pressing TIMER button ON or OFF will blink This area will show the set time SET TIME display 23 Pressing TEMP button set temperature ambient temperature outdoor ambient...

Страница 12: ... button again to clear the display TURBO icon 28 is displayed when Pressing TEMP and CLOCK simulta neously in Heat mode 8 Heating icon 31 is displayed when pressing the X FAN button Press this button again to clear the display X FAN icon 27 Press FAN button to select the desired fan speed setting AUTO Low Med High Your selection will be displayed in the LCD windows except the AUTO fan speed FAN SP...

Страница 13: ... ON OFF MODE This button is used for setting Fan Speed in the sequence that goes from AUTO to then back to Auto FAN 1 4 3 2 5 Operation of Remote Controller Press this button to turn on the unit Press this button again to turn off the unit Press this button to decrease set temperature Holding it down above 2 seconds rapidly decreases set temperature In AUTO mode set temperature is not adjustable P...

Страница 14: ... then by 10 minutes every 0 5 second During blinking after setting press CLOCK button again to confirm the setting and then 12 will be constantly displayed TIMER ON TIMER OFF 11 13 TURBO 10 14 Operation of Remote Controller TEMP Press this button to initiate the auto ON timer To cancel the auto timer program simply press this button again After press of this button disappears and ON blinks 00 00 i...

Страница 15: ... In this case pressing any button blinks three times At unit OFF press MODE and buttons simultaneously to switch between and Combination of and buttons About lock 17 About Back lighting Function About HEALTH function COLD PLASMA Turn on the unit start up the fan Breezing and X FAN are excluded and press HEATLTH button on remote controller to start health function If there is not HEALTH button on r...

Страница 16: ... the air conditioner The operation in details are as below WARNING NOTICE Turn off the air conditioner and disconnect the power before cleaning the air conditioner to avoid electric shock Do not wash the air conditioner with water to avoid electric shock Do not use volatile liquid to clean the air conditioner Clean surface of indoor unit When the surface of indoor unit is dirty it is recommended t...

Страница 17: ...n panel Pull out the panel to a certain Use dust catcher or water to the water below 45 to clean it and then put it in a shady and cool place to dry panel cover tightly operation environment clean frequency can be increased WARNING 14 ...

Страница 18: ...ge pipe is damaged 1 Disconnect power supply Notice for recovery 1 Many packing materials are recyclable materials Please dispose them in appropriate recycling unit 2 If you want to dispose the air conditioner please contact local dealer or consultant service center for the correct disposal method NOTICE Checking before use season NOTICE Checking after use season 15 ...

Страница 19: ...m Pull out the plug Reinsert the plug after about 3min and then turn on the unit again Signal receiving range is 8m Remove obstacles Select proper angle and point the remote controller at the re ceiving window on indoor unit Check the batteries If the power of batteries is too low please replace them Take the remote controller close to indoor unit Turn off the fluoresent lamp and then try it again...

Страница 20: ...or temperature and hum idity is high Because indoor air is cooled rapidly After a while indoor temperature and humidity will be decrease and mist will disappear Phenomenon Check items Solution Set temper ature can t be adjusted Unit is operating under auto mode Temperature can t be adju sted under auto mode Please switch the operation mode if you need to adjust temperature Your required temperatur...

Страница 21: ...s devices etc Disconnect power put back power and then turn on the unit again Water flowing noise Air conditioner is turned on or turned off just now The noise is the sound of refrigerant flowing inside the unit which is a normal phenomenon Cracking noise Air conditioner is turned on or turned off just now This is the sound of friction caused by expansion and or contraction of panel or other parts...

Страница 22: ...al phenomenon Heating indicator ON 10s OFF 0 5s E5 overcurrent protection Power indicator blinks and E5 is displayed C5 Connector jumper malfunction Check if the connector jumper contacts the properly If replace the PCB please take off the old for the new PCB F1 Indoor ambient temp sensor malfunction Check if indoor room temp sensor is connected properly malfunction F2 Evaporator temp sensor Check...

Страница 23: ...stallation dimension diagram At least 250cm At least 15cm At least 300cm Space to the floor Space to the ceiling Space to the obstruction At least 15cm At least 15cm Space to the wall Space to the wall 20 ...

Страница 24: ...iver 3 Impact drill 4 Drill head 5 Pipe expander 6 Torque wrench 7 Open end wrench 8 Pipe cutter 9 Leakage detector 10 Vacuum pump 11 Pressure meter 12 Universal meter 13 Inner hexagon spanner 14 Measuring tape Note Please contact the local agent for installation Don t use unqualified power cord Basic requirement Indoor unit Installing the unit in the following places maycause malfunction If it is...

Страница 25: ... to avoid a hazard 8 The temperature of refrigerant circuit will be high please keep the interconnec tion cable away from the copper tube 9 The appliance shall be installed in accordance with national wiring regulations 10 Installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only 1 The air conditioner is the first class electric appliance It must...

Страница 26: ...ole 2 Open a piping hole with the diameter of Φ55 or Φ70 on the selected outlet pipe position In order to drain smoothly slant the piping hole on the wall slightly downward to the outdoor side with the gradient of 5 10 Left Wall Φ55mm Right Mark in the middle of it Level meter Rear piping hole Wall Space to the wall above 150mm Space to the wall above 150mm Φ55mm Rear piping hole Left Wall Φ70mm R...

Страница 27: ...ut the pipe from left or right please cut off the corresponding hole on the bottom case cut off the hole left right 1 The pipe can be led out in the direction of right rear right left or rear left left rear left right rear right Step four outlet pipe Installation of indoor unit Indoor 5 10 outdoor Φ Φ 55 70 Note Pay attention to dust prevention and take relevant safety measures when opening the ho...

Страница 28: ...ain hose drain hose tape outlet pipe drain hose insulating pipe Note Add insulating pipe in the indoor drain hose in order to prevent condensation The plastic expansion particles are not provided 1 Open the panel remove the screw on the wiring cover and then take down the cover wiring cover screw panel Step seven connect wire of indoor unit 5 If a 18k indoor unit is to be connected with Free Match...

Страница 29: ...g an circuit break must be installed in the line The circuit break should be all pole parting and the contact parting distance should be more than 3mm 3 Remove the wire clip connect the power connection wire to the wiring terminal with wire clip power connection wire cable cross hole 2 Make the power connection wire go through the cable cross hole at the back of indoor unit and then pull it out fr...

Страница 30: ...rately at the end Note The power cord and control wire can t be crossed or winding The drain hose should be bound at the bottom drain hose band connection pipe indoor power cord Step nine hang the indoor unit 1 Put the bound pipes in the wall pipe and then make them pass through the wall hole 2 Hang the indoor unit on the wall mounting frame 3 Stuff the gap between pipes and wall hole with sealing...

Страница 31: ...it grounded securely It may cause electric leakage Does the power cord follow the speci fication It may cause malfunction or damaging the parts Is there any obstruction in the air inlet and outlet It may cause insufficient cooling heating capacity The dust and sundries caused during installation are removed It may cause malfunction or damaging the parts The gas valve and liquid valve of connection...

Страница 32: ...refrigerant charging amount per meter is different according to the diameter of liquid pipe See the following sheet Additional refrigerant charging amount prolonged length of liquid pipe additional refrigerant charging amount per meter Cooling capacity Cooling capacity 5000Btu h 1465W 24000Btu h 7032W 7000Btu h 2051W 28000Btu h 8204W 9000Btu h 2637W 36000Btu h 10548W 12000Btu h 3516W 42000Btu h 12...

Страница 33: ...connection pipe Liquid pipe mm Gas pipe mm Φ6 Φ6 or Φ9 52 Φ12 Φ16 Φ19 Φ22 2 Φ9 52 or Φ12 Φ16 or Φ19 Φ19 or Φ22 2 Φ25 4 or Φ31 8 _ _ Cooling only g m Cooling and heating g m 15 15 30 60 250 250 350 350 120 120 50 20 Outdoor unit throttle Configuration of connection pipe 30 ...

Страница 34: ...ipe D Put on the union nut Remove the union nut on the indoor connection pipe and outdoor valve install the union nut on the pipe union pipe pipe E Expand the port Expand the port with expander Note A is different according to the diameter please refer to the sheet below expander hard mold pipe F Inspection Check the quality of expanding port If there is any blemish expand the port again according...

Страница 35: ......

Страница 36: ...able natural resources and help in preventing potential negative impacts to environment and human health which could be consequence of incorrect disposal of waste Ask for more details from local authorities nearest collection point in Waste Acts of respective country in the Czech Republic in Act no 185 2001 Coll in the wording of later regulations In case of incorrect disposal of this waste a fine...

Отзывы: