INSTALLING THE OUTDOOR UNIT

INSTALLER

BLEEDING

INSTALLER

1

3

Do not install the outdoor unit in pits or air vents

Installing the pipes

Use suitable connecting pipes and equipment for 
the refrigerant R410A.

Wrap all the refrigerant pipes and joints.

Tighten the connections using two wrenches wor-
king in opposite directions.

Vacuum pump

Humid air left inside the refrigerant circuit can cause com-
pressor malfunction. After having connected the indoor
and outdoor units, bleed the air and humidity from the
refrigerant circuit using a vacuum pump.

(1) Unscrew and remove the caps from the 2-way and 3-
      way valves.
(2) Unscrew and remove the cap from the service valve.
(3) Connect the vacuum pump hose to the service valve.
(4) Operate the vacuum pump for 10-15 minutes until an
      absolute vacuum of 10 mm Hg has been reached.
(5) With the vacuum pump still in operation, close the 
      low-pressure knob on the vacuum pump coupling.
      Stop the vacuum pump.
(6) Open the 2-way valve by 1/4 turn and then close it
      after 10 seconds. Check all the joints for leaks using
      liquid soap or an electronic leak device.
(7) Turn the body of the 2-way and 3-way valves. Discon-
      nect the vacuum pump hose.
(8) Replace and tighten all the caps on the valves.

Vacuum pump

Vacuum pump

Location

Twisting moment (N.m)

35-40

60-65

45-50

70-75

ĭ

ĭ

Diameter (mm) 

ĭ

ĭ

15-20

ĭ

18K unit need to be installed the indoor unit 

Caution: Installation Must be Performed in Accordance 
with the NEC/CEC by Authorized Personnel Only.

conversion joint

18K MODE:

Ɣ

INDOOR

UNIT

Connect to the

indoor unit

Refrigerant fluid di

rection of fiow

3-w

ay valve

2-w

ay valve

inlet

(2)Turn
(8) Secure

(7)Turn to open fully

(2)Turn

(8) Secure

(6) Open by 1/4 turn

(7)Turn to open fully

(2)Turn

(8) Secure

V

alve cap

Valve cap

Service

The refrigerant pipes must not exceed the maximum

Use bolts to secure the unit to a flat, solid floor.
When mounting the unit on a wall or the roof, make
sure the support is firmly secured so that it cannot
move in the event of intense vibrations or a strong
wind.

Install the drain fitting and the drain hose
(for model with heat pump only)

Condensation is produced and flows from the out-
door unit when the appliance is operating in the 
heating mode. In order not to disturb neighbours 
and to respect the environment,install a drain fitting 
and a drain hose to channel the condensate water.
Install the drain fitting and rubber washer on the 
outdoor unit chassis and connect a drain hose to it 
as shown in the figure.

Models(m)

18Kx2

14Kx2

28Kx4

Max. connection pipe length

20

70

Max. connection pipe length
(Simple one indoor unit)

10

20

10

20

21Kx3 24Kx3

60

20

60

20

The sum of the capacity codes of the indoor units should be
among 50%-150% of that of the outdoor unit.

heights 5m(14K&18K)or 10m(21K&24K&28K).

Содержание MS-E14AIN

Страница 1: ...USER S MANUAL MS E14AIN MS E18AIN MS E21AIN MS E24AIN MS E28AIN NEW MULTI SYSTEM EN ...

Страница 2: ... Original instructions ...

Страница 3: ... without displayer the position and shape of the displayer please refer to the real one In line with the company s policy of continual product improvement the aesthetic and dimensional characteristics technical data and accessories of this appliance may be changed without notice This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilitie...

Страница 4: ...lectric shock Donot spray wateronindoorunit It may cause electric shock ormalfunction After removing the filter do not touch fins to avoid injury Do not use fire or hair dryer to dry the filter to avoid deformation or fire hazard Maintenance must be performed by qualified professionals Otherwise it may cause personal injury or damage Do not repair air conditioner by yourself It may cause electric ...

Страница 5: ... Air switch should be included magnet buckle and heating buckle function it can protect the circuit short and overload Air Conditioner should be properly grounded Incorrect grounding may cause electric shock Don t use unqualified power cord Properly connect the live wire neutral wire and grounding wire of power socket Do not put through the power before finishing installation If the supply cord is...

Страница 6: ...t and outdoor unit should be connected by a professional If the length of power connection wire is insufficient please contact the supplier for a new one Avoid extending the wire by yourself For the air conditioner with plug the plug should be reachable after finishing installation For the air conditioner without plug an circuit break must be installed in the line If you need to relocate the air c...

Страница 7: ...r off according to your requir ement automatically please do not turn on or turn off the unit freque ntly otherwise disadvantage effect may be caused to the unit Rated voltage of this air conditi oner 220 240V 50Hz The com pressor will vibrate sharply if the voltage is too low resappointed amage to refrigerating system Electrical component are easy to damage if the voltage is too high Don t attemp...

Страница 8: ...e sure to cut off the power supply before cleaning the air conditioner otherwise electric shock might happen Wetting of air conditioner may cause the risk of electric shock Make sure not to wash your air conditioner in any case This product must not be disposed together with the domestic waste This product has to be disposed at an authorized place for recycling of electrical and electronic applian...

Страница 9: ...ct has to be disposed at an authorized place for recycling of electrical and electronic appliances Volatile liquids such as thinner or gasoline will cause damage to the appearance of air conditioner Only use soft dry cloth moist cloth clean the air conditioner cabinet The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube Note The above ...

Страница 10: ...ENERAL INFORMATION 8 Indoor side DB WB ć Outdoor side DB WB ć 43 26 32 23 Maximum cooling 27 Maximum heating 24 18 Ɣ The operating temperature range outdoor temperature for cooling only unit is 15ć 43ć for heat pump unit is 15ć 24ć m charge the refrigerant liquid pipe total length Max connection pipe length Under the condition of no need to Max installation altitude Max connection pipe length One ...

Страница 11: ...pes and the connectiong wirings of the unit A and unit B must be corresponding to each other respective Note the above figures are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units that have been purchased The appliance shall be installed in accordance with national wiring regulations MS E18AIN L N To the power supply To unit B Power cord T...

Страница 12: ...ast 3mm in all pole should be connected in fixed wiring The connection pipes and the connectiong wirings of the unit A unit B and unit C must be correspo nding to each other respective Note The above figures are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units that have been purchased The appliance shall be installed in accordance with nat...

Страница 13: ... cable ensure that leads between connection to fixed point have some space An all pole disconnection switch having a contact separation of at least 3mm in all pole should be connected in fixed wiring The connection pipes and the connectiong wirings ofthe unit A unit B unit C and unit D must be corresponding to each other respective The appliance shall be installed in accordance with national wirin...

Страница 14: ...ing a contact separation of at least 3mm in all pole should be connected in fixed wiring The connection pipes and the connectiong wirings ofthe unit A unit B unit C and unit D must be corresponding to each other respective The appliance shall be installed in accordance with national wiring regulations MS E14AIN HANDLING After having removed the packaging check that the contents are intact and comp...

Страница 15: ...40 60 65 45 50 70 75 ĭ ĭ Diameter mm ĭ ĭ 15 20 ĭ 18K unit need to be installed the indoor unit Caution Installation Must be Performed in Accordance with the NEC CEC by Authorized Personnel Only conversion joint 18K MODE Ɣ INDOOR UNIT Connect to the indoor unit Refrigerant fluid direction of fiow 3 way valve 2 way valve inlet 2 Turn 8 Secure 7 Turn to open fully 2 Turn 8 Secure 6 Openby 1 4 turn 7 ...

Страница 16: ...alified person Do not use any other refrigerant than R410A ƽ MAINTENANCE INSTALLER INSTALLATION DIMENSION DIAGRAM INSTALLER 14 MS E24AIN MS E28AIN MS E18AIN MS E21AIN MS E14AIN 30cm Space to the cover or above 30cm 50cm Air inlet side or above or above Space to the wall 30cm Space to the cover or above 30cm 50cm Air inlet side or above or above Space to the wall 30cm Space to the cover or above 30...

Страница 17: ...nits Have the length of refrigerating pipe and refrigerant charge amount been recorded Has the unit been safely grounded Problems Owing to Improper Installation The unit may drop vibrate or make noises May cause unsatisfactory cooling heating effect May cause condensation and water dropping May cause condensation and water dropping The unit may bread down or the components may be burned out The un...

Страница 18: ...is located INFORMATION CONCERNING USED REFRIGERANT MEDIUM This unit is containing fluorinated gases included in the Kyoto protocol The maintanance and the liquidation must be carried out by qualified personel Type of refrigerant R410A The composition of the cooling medium R410A 50 HFC 32 50 HFC 125 The quantity of the refrigerant please see the unit label The value GWP 2088 GWP Global Warming Pote...

Отзывы: