
22
Test operation and check after installation
☆
Test operation
1. Preparation for trial run
installations are not completed.
(2)
Connect of control circuit should be correct
all wire connect should be firm.
(3)
Cut-off valves of both thick and thin pipes should be turned on.
(4)
All scattered components, especially metal scrap thrum etc., should be cleared from unit.
2. Test operation method
(1)
P ress ON/OFF on wireless remote control after connecting to power supply, unit begins running.
(2)
Press MODE to select run mode of COOL, HEAT and SWING etc. to check if it can run normally.
(3)
When wireless remote control is losed, operation unit by following mode:
(a) When unit is halt, press the ON/OFF button, then unit begins running in AUTO micro-
computer select COOL, DRY, HEAT or FAN automatically according to indoor temp.
to make comfort effect. Repress ON/OFF to stop the unit from running.
(b) When unit is running, press ON/OFF to stop unit from running.
☆
Check after installation
Items to be checked
Is the installation firm enough
?
Possible malfunction
Unit may drop, shake or emit noise
Is leakage test done
?
It may cause insufficient of cooling (heating) capacity
Is heat insulation sufficient
?
Condensation or water drop may occur
Is drainage smooth
?
Condensation or water drop may occur
product nameplate
?
Malfunction or burn out of parts may occur
Malfunction or burn out of parts may occur
Is the install of circuit and pipeline correct
?
Is the unit earthed safely
?
Creepage may o ccur
Is model of wire fits that of regulation
?
Malfunction or burn out of parts may occur
capacity may occur.
Is both the air inlet or outlet vent of indoor
and outdoor unit blocked
?
Is length of refrigerant pipe and charge amount recorded
?
Charge amount of refigerant is hard to handle.
ON/OFF button
Running indicator
Cooling indicator
Heating indicator
(1)
Don't turn on power supply if entire
Is the power voltage the same with that in
Insufficient of cooling (heating)
Содержание FC-H07AIF
Страница 1: ...USER S MANUAL FC H07AIF FC H09AIF FC H12AIF FREE COMBI SERIES ...
Страница 2: ... T T ...