Simpson Gima Скачать руководство пользователя страница 13

13

The host initiates all transactions.  Slave devices continuously monitor the net-
work, looking for messages framed by silent periods.  The first character detected,
after a silent period, is assumed to be an address byte and is compared to the
meter’s internal address (zero for broadcasts).  An addressed slave reads the
remainder of the message and acts upon it as required.

A slave tests the message to determine its validity and uses the transmitted
checksum (CRC) to detect communication errors.  A slave will only act on valid
messages, received without error, specifically addressed to it.

ADDRESS

Valid Modbus addresses are in the range 0-247.  Individual devices may be as-
signed addresses in the range 1-247.  Address 0 is retained for broadcast com-
mands which are handled by all slaves.  When a slave responds to a command, it
places its own address in the replay message.

FUNCTION

The functions code is a single byte, telling the device what type of operation to
perform.  Valid Modbus codes are in the range 1-255 decimal, but the GIMA Op-
tions Module handles only a small subset of these as summarized below.

Figure 4.7.  Function Code Summary

DATA FIELD

Data from the host contains additional information for the remote device specific
to the command.  For example, the data field may specify which meter readings
are required or new values for energy registers.  Data from a slave may contain
meter readings or other information requested by the host.  The slave also uses
the data field to send error codes.

The size of the data field varied depending on command type and usage.  The
data format may also vary from one command to another to suit the application.
Instantaneous readings, for example, are transmitted as 2-byte Integers, whereas
energy readings are formatted as 4-byte Long Integers.  Data is always transmit-
ted with the most significant byte first.  Data formatting is described in more detail
in the following sections.

e

d

o

C

n

o

it

c

n

u

F

n

o

it

a

r

e

p

O

t

s

a

c

d

a

o

r

B

3

0

s

r

e

t

s

i

g

e

R

e

l

p

it

l

u

M

d

a

e

R

o

N

4

0

s

r

e

t

s

i

g

e

R

e

l

p

it

l

u

M

d

a

e

R

o

N

6

0

r

e

t

s

i

g

e

R

e

l

g

n

i

S

a

t

e

s

e

r

P

s

e

Y

8

0

c

it

s

o

n

g

a

i

D

k

c

a

B

p

o

o

L

o

N

6

1

s

r

e

t

s

i

g

e

R

e

l

p

it

l

u

M

t

e

s

e

r

P

s

e

Y

20

4.5.4.2 Scaling Instantaneous/Peak Values

Instantaneous readings from the GIMA  are provided as Signed Integer values
with no decimal point or legend (e.g. kW or MW).  Scaling factors are provided to
enable conversion of the raw data to real numbers in basic unit form (amps, volts,
watts, VA or var).  These scaling factors are constant values calculated in the
GIMA as a function of CT and PT Primary programming.

To convert raw data to real numbers:

R = I X 10

(K-3)

Where

I

 = Integer number

K

 = Relevant Scaling Factor

R

 = Real number result

Example:

If the meter is programmed with CT Primary = 50A and PT Primary = 415V:
The meter displays would be scaled as : 50.00A, 240.0V, 415.7VLL, 36.00kW.
Scaling factors would be as

I Scale = 1, Vph Scale = 2, VLL Scale = 2, P Scale = 4.

Integer Values would be transmitted as: 5000, 2400, 4157, and 3600.
Amps would be calculated as 5000 x 10

(1-3)

 = 5000/100 = 50.00A.

Phase Volts would be calculated as 2400 x 10

(2-3)

 = 2400/10 = 240.0V.

Line Volts would be calculated as 4157 x 10

(2-3)

 = 4157/10 = 415.7V.

3-Ph Power would be calculated as 3600 x 10

(4-3)

 = 3600 x 10 = 36000W.

4.5.5 Table 14 Meter Set-up

Notes:

9. Values in Table 14 may not be written using Command 16.

t

e

s

f

f

O

s

s

e

r

d

d

A

s

t

n

e

t

n

o

C

t

a

m

r

o

F

s

e

t

y

B

s

d

r

o

W

s

s

e

c

c

A

0

4

8

5

3

y

r

a

m

i

r

P

T

C

t

n

I

d

e

n

g

i

s

n

U

2

1

e

ti

r

W

/

d

a

e

R

9

1

5

8

5

3

y

r

a

m

i

r

P

T

P

t

n

I

d

e

n

g

i

s

n

U

2

1

e

ti

r

W

/

d

a

e

R

9

2

6

8

5

3

e

t

a

R

1

e

s

l

u

P

t

n

I

d

e

n

g

i

s

n

U

2

1

e

ti

r

W

/

d

a

e

R

9

3

7

8

5

3

e

t

a

R

2

e

s

l

u

P

t

n

I

d

e

n

g

i

s

n

U

2

1

e

ti

r

W

/

d

a

e

R

9

4

8

8

5

3

e

t

a

R

d

u

a

B

t

n

I

d

e

n

g

i

s

n

U

2

1

e

ti

r

W

/

d

a

e

R

9

5

9

8

5

3

D

I

s

u

b

d

o

M

t

n

I

d

e

n

g

i

s

n

U

2

1

e

ti

r

W

/

d

a

e

R

9

6

0

9

5

3

l

e

d

o

M

r

e

t

e

M

t

n

I

d

e

n

g

i

s

n

U

2

1

y

l

n

O

d

a

e

R

7

1

9

5

3

e

p

y

T

r

e

t

e

M

t

n

I

d

e

n

g

i

s

n

U

2

1

y

l

n

O

d

a

e

R

8

2

5

9

3

e

r

a

w

t

f

o

S

r

e

t

e

M

t

n

I

d

e

n

g

i

s

n

U

2

1

y

l

n

O

d

a

e

R

9

3

9

5

3

d

o

i

r

e

P

D

M

I

/

V

t

n

I

d

e

n

g

i

s

n

U

2

1

e

ti

r

W

/

d

a

e

R

9

Содержание Gima

Страница 1: ...NS MODULE INSTRUCTION MANUAL 32 SIMPSON ELECTRIC COMPANY 520 Simpson Avenue Lac du Flambeau WI 54538 0099 715 588 3311 FAX 715 588 3326 Printed in U S A Part No 06 116937 Edition 2 06 07 Visit us on the web at www simpsonelectric com ...

Страница 2: ...ctured by it to be free from defects in material and workmanship under normal use and service its obligation under this warranty being limited to making good at its factory or other article of equipment which shall within one 1 year after delivery of such instrument or other article of equipment to the original pur chaser be returned intact to it or to one of its authorized service centers with tr...

Страница 3: ... m 7 8 W l e n a p d n i h e b m m 0 3 1 m m 8 3 1 x m m 6 9 x m m 6 9 t h g i e W g 0 0 2 x o r p p A s l a n i m r e T m m 0 4 2 0 e g a C g n i s i R 2 s r o t c u d n o C s m m o C l a i r e S s u b d o M e p y T s u B g n i d a o L X R e v i r D X T x e l p u D f l a H V 0 s e r i W 2 4 5 8 4 S R 2 2 4 S R e l u d o M s n o i t p O r e p d a o L t i n U 4 1 s d a o L t i n U 2 3 l o c o t o r...

Страница 4: ...taneous Peak Values 20 4 5 5 Table 14 Meter Set up 20 4 5 5 1Meter Set up Values 21 4 5 6 Table 15 Peak Current and Voltage Demand 21 4 5 7 Table 16 Current and Voltage Demand 22 4 5 8 Function 04 or 03 Read Multiple Registers 22 4 5 9 Function 06 Preset a Single Register 23 4 5 10 Function 08 Loop Back Diagnostic 25 4 5 11 Function 16 Preset Multiple Registers 26 4 5 12 Exception Responses 27 4 6...

Страница 5: ...les refer to section 4 5 The All Value unit provides access to all parameters shown in the table in section 4 5 Both types of Options Units provide access to standard programmable meter set tings such as CT primary 28 Exception Response EXCEPTION FUNCTION CODE All normal function types have a most significant bit of 0 80 Hex In an Excep tion Response the meter sets the MSB to 1 adds 80H to the rec...

Страница 6: ...on errors and can handle the query it will reply with a normal response If the Options Unit does not receive the message due to a communication failure no response will be returned and the host will eventually time out If the Options Unit receives the message but detects a communication error via its CRC no response will be returned and the host will time out If the Options Unit receives the query...

Страница 7: ...al Scroll through the program settings using until the meter displays Baud Rate 1 Press to select the next highest available baud rate setting 2 Press to select the next lowest available baud rate setting 3 Press and hold for two seconds to finish r t 26 4 5 11 Function 16 Preset Multiple Registers Description This function allows a number of registers in a meter table to be set by the host in a s...

Страница 8: ...or more meters connected in a multi drop network have the same address data on the network will be corrupted and communication will fail r 25 4 5 10 Function 08 Loop Back Diagnostic Description This function provides a simple means of testing the communication network and detecting if a particular meter is present This command is not available as a broadcast command as it requires a return data pa...

Страница 9: ...ter on the bus Certain commands allow the host to transmit commands or data to all meters simultaneously These com mands are known as broadcasts and use address 0 The RS 485 standard en ables reliable communication over a maximum distance of 1200 meters Standard line repeaters may be installed to increase the maximum distance of an RS 485 network and or the number of devices that may be connected ...

Страница 10: ...ures half duplex operation in RS 485 mode with data direction control The RS 422 standard enables reliable communication over a maximum distance of 1200 meters Standard line repeaters may be in stalled to increase the maximum distance of an RS 422 network and or the num ber of devices that may be connected 23 Meter Response The example shows a replay of 6 bytes 3 integers as 3 ph kW 570 02 3A Hex ...

Страница 11: ... 5 8 Function 04 or 03 Read Multiple Registers Description This function allows a number of registers from a meter table to be read in a single operation This command is commonly used to obtain instantaneous energy or set up data from the meter This command is not available as a broadcast com mand as it requires a return data packet from the meter Host Request The example above shows a read of thr...

Страница 12: ...nd of each message is marked by a silent period of at least 3 5 character periods approximately 3 5ms 9600 baud This is shown in the RTU message from in figure 4 6 Figure 4 6 RTU Framing T R A T S S S E R D D A N O I T C N U F A T A D C R C D N E D O I R E P T N E L I S S T I B 8 S T I B 8 S T I B 8 x n S T I B 6 1 D O I R E P T N E L I S 21 4 5 5 1 Meter Set up Values Information about the GIMA c...

Страница 13: ... i t l u M d a e R o N 4 0 s r e t s i g e R e l p i t l u M d a e R o N 6 0 r e t s i g e R e l g n i S a t e s e r P s e Y 8 0 c i t s o n g a i D k c a B p o o L o N 6 1 s r e t s i g e R e l p i t l u M t e s e r P s e Y 20 4 5 4 2 Scaling Instantaneous Peak Values Instantaneous readings from the GIMA are provided as Signed Integer values with no decimal point or legend e g kW or MW Scaling fa...

Страница 14: ... final contents of the CRC register are tagged on to the end of the mes sage with the most significant byte first 8 Swap the low and high order bytes of the integer result 19 4 5 3 Table 12 Additional Instantaneous Values Notes 4 Use Power Scale at address 2840 to convert to real W VA or var 4 5 4 Table 13 Peak Values Notes 5 Use Amps Scale at address 2837 to convert to real peak hold amps 6 Use P...

Страница 15: ...t address 2840 to convert to real W VA or var t e s f f O s s e r d d A s t n e t n o C t a m r o F s e t y B s d r o W s s e c c A 0 6 1 8 2 h P 3 W k r e g e t n I d e n g i S 2 1 y l n O d a e R 4 1 7 1 8 2 h P 3 A V k r e g e t n I d e n g i S 2 1 y l n O d a e R 4 2 8 1 8 2 h P 3 r a v k r e g e t n I d e n g i S 2 1 y l n O d a e R 4 3 9 1 8 2 h P 3 F P r e g e t n I d e n g i S 2 1 y l n O ...

Страница 16: ... e R 7 9 1 5 o L d n I h r a v k 8 0 2 5 i H p a C h r a v k g n o L d e n g i s n U 4 2 e t i r W d a e R 9 1 2 5 o L p a C h r a v K 17 4 5 1 2 Writing to Energy Registers Function 6 or 16 may be used to write to the energy registers in Table 2 Function 6 allows access to the upper and lower integers of the 4 byte long individually Upper integers have a maximum write value of 0x00F preventing ou...

Отзывы: