Simplex TrueAlert ES Series Скачать руководство пользователя страница 4

579-1034

Rev. F

R

Appliance specifications

Environmental specifications:

Rated voltage range

Special application

17 - 31 VRMS

Temperature range

32° F to 120° F (0° C to 49° C)

Humidity range

10% to 93%, non-condensing at 104° F (40° C)

Connections

Terminal for 18 AWG to 12 AWG 
(0.82 mm

2

 to 3.31 mm

2

)

Sound pressure level measurement (dBA) 

Reverberant Room at 10 
Feet in accordance with 
UL464 (See Note 2) 

Voltage

(Vrms)

Horn mode 

steady

Horn mode 

coded 

(See Note 1)

High volume 
setting using addressable 
controller (See Note 3) 

17 (Min.)

87.6

83.1

23 89.8

86

31 (Max.) 

91.9

86

Low volume setting using 
addressable controller 
(See Note 3) 

17 (Min.)

80.6

76.9

23 83.4

79.2

31 (Max.) 

86.2

82.3

Anechoic Room at 10 feet in accordance with ULC S525, see note 4.

High volume setting 

17 (Min.)

89.9

89.6

23 92.5

92.4

31 (Max.) 

94.4

93.9

Low volume setting

17 (Min.)

84.1

83.6

23 86.7

86.6

31 (Max.) 

89.1

88.6

Notes:

1. The coded category covers both Temporal and March time cadences.
2. Reverberant dBA measurements are a minimum UL rating based on sound 

power level measurements made in UL’s reverberant test chamber.

3. High and low volume settings are configured with DIP switch (CFIG1) on the 

controller.

4. If you install the 4905-9838 Sound Damper, the anechoic measurements 

decrease by approximately 9 dBA.

Current draw

Application

Appliance 
type

Maximum RMS 
operating current

UL464/
ULCS525
(0° C TO 50° C)

AO

23 mA

ULC directional characteristics for horn 

Access

Angle

dBA

Horizontal

61.5° left and right

-3 dBA

90° left and right

-4.6 
dBA

Vertical

62° up and down

-3 dBA

90° up and down

-3.8 
dBA

CAUTION:
• The appliances are available in red and white. Do 

not paint or otherwise alter the factory finishes in 
any way.

• Anechoic dBA levels below 85 do not meet ULC 

requirements for public notification.

Содержание TrueAlert ES Series

Страница 1: ... the mounting surface See Figure 1 for mounting and location information 2 Bring the building wiring through the rectangular opening in the backplate 3 Connect the building wires to the backplate See the wiring section on page 2 4 Secure the backplate to the electrical box using the provided hardware Install with the writing Install this side up at the top Use a torque wrench to tighten the screws...

Страница 2: ...agrams for the driving compatible fire alarm control panel for further instructions Notification appliances are rated using an individual module label Maintain the correct polarity on the terminal connections Terminals 1 and 2 can each accommodate two wires one wire going in and one wire going out to the next appliance TrueAlert SLC wiring connections are supervised and power limited These applian...

Страница 3: ... Setting the DIP switch address Setting the horn configuration switch Figure 4 Setting the appliance configuration Certain options for the horn can be configured directly on the appliance using the Configuration switch CFIG1 on the back of the appliance See Figure 4 AO Settings Position 1 Configuration Control OFF to enable Local Audible control positions 2 7 below ON for Panel control Position 2 ...

Страница 4: ...92 4 31 Max 94 4 93 9 Low volume setting 17 Min 84 1 83 6 23 86 7 86 6 31 Max 89 1 88 6 Notes 1 The coded category covers both Temporal and March time cadences 2 Reverberant dBA measurements are a minimum UL rating based on sound power level measurements made in UL s reverberant test chamber 3 High and low volume settings are configured with DIP switch CFIG1 on the controller 4 If you install the ...

Отзывы: