background image

 

 

S4906-0005-3  5/2013

110

75

30

15

FACP

Optional 4905-9915 (white) or 4905-9916 (red)
Adapter, recommended for surface mounted box

Wiring terminals and address setting
are located behind the housing

Ceiling reference,
surface mounted box

Ceiling reference,
flush mounted box

Strobe intensity viewing slot

Intensity selection plug,
accessible only from rear of
lens housing; factory setting is
FACP, controlled by panel

Optional 4905-9928
Adapter Plate, required
for surface mounted
electrical box

Optional 4905-9927

Red Wire Guard

Four mounting clamps
included, two each side

End View

Magnetic test area

LED indicator

Strobe housing straight-on view

4" (102 mm)
square box,
1-1/2" (38 mm)
minimum depth

 

 

Compatible Controller 

Data Sheet 

Reference 

Controller 

Output 

IDNAC SLC 

Output Voltage 

Appliance Voltage 

Design Reference 

4100ES with EPS+ or EPS Power Supply 

S4100-0100 

IDNAC SLC 

29 VRMS 

(regulated) 

23 VRMS 

(with 6 VRMS drop)

4009 IDNAC Repeater 

S4009-0004 

General Specifications

 

(see page 2 for dimensions)

 

Environmental 

32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C) 

Connections 

Terminal blocks for 18 AWG to 12 AWG (0.82 mm

2

 to 3.31 mm

2

); two wires per 

terminal for in/out wiring 

Reference 

Installation Instructions 579-808 

Electrical Specifications 

Typical Operating Voltage Range 

23 VRMS to 31 VRMS, Special Application (see page 4 for 17 VRMS rating) 

Flash Rate and Synchronized SLC Loading 

1 Hz; with up to 46 synchronized strobes maximum per NAC; maximum 30 

 

resistance between appliances 

 Candela 

Setting 

15 cd 

30 cd 

75 cd 

110 cd 

  Horn Output Selection 

High Low High Low High Low High Low 

23 VRMS

 Current Ratings, for connection to 

IDNAC Addressable SLCs, horn steady on 

75 mA 

70 m A  110 mA

105 mA

198 mA  193 mA  250 mA

245 mA 

Horn Output Characteristics 

2400 to 3700 Hz sweep, modulated at 120 Hz rate 

Horn Output Ratings 

@ 10 ft (3 m) 

Sound Type (see Note) 

Steady 

Coded 

Setting 

High Low  High  Low 

Reverberant Chamber, 

UL 464 Test 

84.6 dBA 

79.1 dBA 

80.6 dBA 

75.5 dBA 

Anechoic Chamber 

90 dBA 

84 dBA 

86 dBA 

80 dBA 

Note: 

Coded horn values are typical of the output measured with a Temporal or March Time pattern and with a sound level meter 

reading on a “fast” setting. Under the same test conditions, coded horn output “peak” sound level readings are typically 4 dBA 
higher. 

 Ceiling Mount A/V and Guard Installation Reference 

 TrueAlert Strobe and IDNAC SLC Controller Compatibility Reference 

 Specifications

 

 