4-5
It may be necessary during maintenance of the system to turn the outputs (notification
appliances and relays, for example) off. This prevents maintenance actions that generate an
alarm condition from triggering the NACs or relays.
1. Select the output point that you want to turn off. Refer to Chapter 5 for information on
selecting points.
2. Press the OFF/FLT TEST key.
3. Press the ENTER key to confirm the operation.
1. Select the output point that you want to force ON. Refer to Chapter 5 for information on
selecting points.
2. Press the ON/ALM TEST key.
3. Press the ENTER key to confirm the operation.
Turning an output point on or off generates a “Manual Override Trouble,” which is used to
remind you that the point has been manually turned on or off. When you are ready to return
the system to automatic operation (i.e., system not operator controls the outputs), you need to
acknowledge the trouble (individual acknowledge systems only), select the point, and then
press the <AUTO> key.
Turning a Point ON or OFF
Overview
Turning a Point OFF
Turning a Point ON
Returning a Point to
Automatic Operation
firealarmresources.com
Содержание SafeLINC 4100
Страница 1: ...FIRE 4100 Fire Indicator Panel Operator s Manual LT0293 579 314 Rev 1 1 FIRE firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 8: ...firealarmresources com...
Страница 14: ...firealarmresources com...
Страница 40: ...firealarmresources com...
Страница 50: ...firealarmresources com...
Страница 56: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 82: ...firealarmresources com...
Страница 100: ...firealarmresources com...