background image

Replacing the CPU Switcher Card

Introduction

The CPU switcher card is used in redundant master controller configurations to automatically switch the communications bus and city circuit from

a primary CPU card to a backup (secondary) CPU card when a trouble is detected by the 24-point I/O card. The CPU switcher card is located in the

Primary CPU Bay, the top bay in the back box.
The card layout within the Primary CPU Bay is different than that of a normal CPU bay. The CPU motherboard and daughter card, for instance, are

installed at the far left of the bay, rather than the right. Also, the network card slot on the CPU motherboard must not be used in redundant master

controller configurations. Immediately to the right of the primary CPU motherboard is the CPU Switcher Card and then the 24-point I/O card. Figure 1

shows a sample layout of a Primary CPU bay within a 4100U configured with a redundant master controller.
Removing the switcher card involves removing system power, detaching the two connectors from the card (at P3 and P4), and removing the four Torx

screws that fasten the board to the standoffs at the rear of the bay. However, because the switcher card is mounted in between other cards in the bay,

the CPU motherboard must also be removed to make it possible for the switcher card to be disconnected from the adjacent cards.

Figure 1: Primary CPU Bay Layout

Remove Power and Access the Primary CPU Bay

1.  Disconnect any connection to the batteries at the PDM and then remove the power to the system at the breaker.
2.  Lower the front door to the Primary CPU Bay (the top bay in a redundant master controller configured panel). Refer to Figure 1 for the

location of the CPU switcher card and CPU motherboard within the bay.

Remove the CPU Motherboard

The CPU motherboard must be removed from the bay before the CPU switcher card can be removed. Follow the steps below to remove the CPU

motherboard from the Primary CPU Bay.

1.  Label and detach the service port and front display ribbon cables from the CPU daughter card, which is mounted to the CPU motherboard.

The service port cable is the thinner of the two ribbon cables.

2.  Release and lower the card stabilizer at the front of the bay by pressing in the tabs at either end of the stabilizer. The card stabilizer must be

lowered before cards can be removed.

3.  Pull the CPU daughter card out of its slot on the CPU motherboard and set it aside.

The next few steps involve the labeling and removal of cables connected to the CPU motherboard. You will be reattaching these cables later.

The locations and suggested labels of the connections are shown in Figure 2.

4.  Label and disconnect any plug connected to P1 on the CPU motherboard.
5.  Label and disconnect any plugs connected to P4, P5, or P6.
6.  Label and disconnect any plugs connected to P7 and P8.
7.  Label and disconnect any wires connected to TB3. Include as part of the label the name of the terminal block and the specific terminal the

wire connects to.

8.  Label and disconnect any wires connected to the eight-position terminal block. Include as part of the label the name of the terminal block

and the specific terminal the wire connects to.

Note: 

TB2, the RUI terminal on the CPU motherboard, is not used in redundant master controller configurations. Instead, use 567-217 RUI.

page 2

579-272  Rev. C

CPU Switcher Card and Class B Motherboard Replacement Instructions

Содержание 637-526

Страница 1: ...YSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation this product must be tested in accordance with NFPA72 after any programming operation or change in site specific software Reacceptance testing is required after any change addition or deletion of system components or after any modification repair or adjustment to system hardware or wiring All components circuits syste...

Страница 2: ...y in a redundant master controller configured panel Refer to Figure 1 for the location of the CPU switcher card and CPU motherboard within the bay Remove the CPU Motherboard The CPU motherboard must be removed from the bay before the CPU switcher card can be removed Follow the steps below to remove the CPU motherboard from the Primary CPU Bay 1 Label and detach the service port and front display r...

Страница 3: ... J1 header connector on the CPU motherboard from the P1 header connector on the CPU switcher card to completely detach the CPU motherboard 11 Set the board aside You will reinstall it after the new CPU switcher card is installed Remove the Existing CPU Switcher Card 1 Label and remove the two connectors connected to the CPU switcher card Label the 18 position plug located towards the top of the ca...

Страница 4: ...e 2 for the location of each labeled connection 4 Reinsert the CPU daughter card in the right most slot of the CPU motherboard refer to Figure 1 for the correct location 5 Reconnect the cables labeled service port and front display to the appropriate locations on the CPU daughter card The service port cable is the thinner of the two cables 6 If you are also replacing the class B motherboard skip a...

Страница 5: ... 5 Remove the four 6 5 16 Torx screws from each corner of the motherboard These screws are fastened to metal standoffs connected to the rear of the bay Leave the standoffs fastened to the back of the bay You will mount the new class B motherboard to them Install the New Class B Motherboard 1 Position the new motherboard in the same location where you removed the old one 2 Fasten the new class B mo...

Страница 6: ...itional listings may be applicable contact your local Autocall product supplier for the latest status Listings and approvals under Tyco Fire Security GmbH and the product names listed in this material are marks and or registered marks Unauthorized use is strictly prohibited NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association NFPA ...

Отзывы: