Document: LT0400
4100U-S1 Programming Guide
Addressable Device Settings
Issue 1.4
15 December 2010
Page 6-5
RELAY
– General Purpose relay
TRELAY
– Fault Relay on until fault cleared
Mx-x-2 2
nd
Sub Point (T-Sense input)
Device Type
MTSENSE
– Fixed Device type
Point Type
FIRE
– General Fire Point
UTILITY
– Input used by Custom Control Logic only
TROUBLE
– Input used to indicate a Fault status
WATER
– Sprinkler -Flow Switch setting
WSO
– Sprinkler – Flow Switch and Valve Monitor
6.3.7
4090-9119 Relay IAM with Unsupervised Input
This device has multiple sub points. The sub points can have the point type changed depending on
the operation.
Mx-x-0 Parent Point
Device Type
FRIAM
– Standard setting
Point Type
UTILITY
– Standard setting
Mx-x-1 1
st
Sub Point (relay output)
Device Type
MRELAY
– Fixed Device type
Point Type
RELAY
– General Purpose relay
TRELAY
– Fault Relay on until fault cleared
Mx-x-2 2
nd
Sub Point (feedback input)
Device Type
MFEEDBK
– Fixed Device type
Point Type
UTILITY
– Input used by Custom Control Logic only
TROUBLE
– Input used to indicate a Fault status
6.3.8
4090-9120AU 6 Point I/O Module (4 Inputs, 2 Relay outputs)
This device has multiple sub points. The sub points can have the point type changed depending on
the operation.
Mx-x-0 Parent Point