Power-Limited Guidelines

Make sure these guidelines are accounted for before wiring for power-limited systems:

•  Non-power-limited field wiring (AC power, batteries, City connection) must be installed and routed in the shaded areas shown in Figure 9.
•  Power-limited field wiring must be installed and routed in the non-shaded areas shown in Figure 9, with the exception of City wiring.
•  Excess slack should be kept to a minimum inside the back box enclosure. The wiring should be neatly dressed and bundled together using the

wire ties provided with the equipment. Anchor power-limited wiring to tie points, as shown in Figure 9.

Figure 9: Power-Limited Wiring

•  Tie the wiring located between bays to the internal wiring troughs, if applicable.
•  When powering remote units or switching power through relay contacts, power for these circuits must be provided by a power-limited power

supply that listed for fire-protective signaling use.

page 10

579-221  Rev. F

4100-6038 Dual RS-232 Module Installation Instructions

Содержание 4100-6038

Страница 1: ...ested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when...

Страница 2: ...igned to each jumper pin The specific jumper settings required on the dual RS 232 card depend on the type of device being attached to the card Refer to Table 1 for specific jumper configurations Figur...

Страница 3: ...1 2 1 2 AC Printer 3rd Party Computer Supervised 2 3 2 3 1 2 1 2 1 2 1 2 None 2 3 2 3 2 3 AC Printer Unsupervised 2 3 2 3 1 2 1 2 1 2 1 2 1 2 2 3 2 3 1 2 Setting Switches Switches Switch SW1 on the R...

Страница 4: ...Figure 3 4100 Daughter Card Addresses page 4 579 221 Rev F 4100 6038 Dual RS 232 Module Installation Instructions...

Страница 5: ...When installing 2 51 mm x 11 inch 292 mm motherboards in a 4100ES expansion bay adhere to the following guidelines Each expansion bay assembly includes a chassis two end supports one LED switch frame...

Страница 6: ...nd fill to the right 1 Orient the motherboard with the connector labeled J1 on the right and the header labeled P1 on the left 2 Attach four metal threaded standoffs and lockwashers into the screw hol...

Страница 7: ...eight pins Insert the harness connector on either the top four pins or the bottom four pins not in the middle Insert the harness connector with the white wire into the P7 connector Note that the P7 co...

Страница 8: ...bay Insert the harness connector with the blue wire into the P2 connector Note that the P2 connector has eight pins Insert the harness connector on either the top four pins or the bottom four pins no...

Страница 9: ...tinuity of the shield must be maintained throughout the entire cable length The entire length of the cable must have a resistance greater than 1 Megohm to earth ground Underground wiring must be free...

Страница 10: ...be kept to a minimum inside the back box enclosure The wiring should be neatly dressed and bundled together using the wire ties provided with the equipment Anchor power limited wiring to tie points as...

Страница 11: ...G 2 081 mm 2 or 625 feet 191 meters for 12 AWG 3 309 mm 2 All wiring is 18 AWG 0 8321 mm 2 or to local code Use of CTS line is required with or without supervised circuit When using Service Modem 565...