Full TrueAlert Operation.
TrueAlert addressable notification appliances are individually
addressed and receive power, supervision, and control signals over the SLC. Horns sound with
selectable high or low output, using a temporal, march time (60 or 120 beats per minute), or
continuous pattern. Horns are controlled separately from visible appliances installed on the same
two-wire circuit. (Combination speaker/strobe TrueAlert appliances receive audible control from
separate audio circuit wiring.)
Extensive Diagnostic Capabilities.
LEDs on the TPS flash codes that identify the nature of
trouble conditions. The TPS also monitors for short and open circuits and positive and negative
Earth fault status.
Depleted Battery Cutout (Canadian Version Only).
When AC Power fails, the Depleted
Battery Cutout feature disconnects a battery from the panel when its voltage is approximately
18 VDC.
Visual Synchronization.
A maximum of 46 MultiCandela addressable visuals may be
synchronized per SLC. All SLCs are synchronized across a TPS. All TPSs are synchronized
across the FACP.
The following table summarizes the AC Input, DC Output, and Battery Charger specifications of
the TPS.
Table 1. AC Input, DC Output, Battery Charger Specifications
AC Input Specifications
4100-5120/5121
4 A Maximum
120 VAC @ 60 Hz
4100-5122
2 A Maximum
220/230/240 VAC @ 50 or 60 Hz
DC Output Specifications
Aux Power and
Each SLC
Minimum: 19 VDC
Maximum: 32 VDC
Ripple: 2 VDC, peak to peak @ full load (9A)
Battery Charger Specifications
Input Voltage
Range
21-33 VDC
Output Voltage
27.4 VDC ± 500 mV @ 68° F (20° C), temperature compensated
at –24 mV / deg. C
High Voltage
Output
29.1 V @ 3.3 A
Output Current
Limit
1.4 A (For 6.2 –18 Ah battery)
3.3 A (Default for 18-50 Ah battery [Canada]; 18-110 Ah battery
[United States])
Continued on next page
Introduction to the TPS,
Continued
Additional Features
Input/Output/Battery