background image

 

 

2

 
 

 

Cautions and  
Warnings 

 

READ AND SAVE THESE INSTRUCTIONS- 

Follow the instructions in this installation 

manual. These instructions must be followed to avoid damage to this product and associated 
equipment. Product operation and reliability depend upon proper installation. 
 

 

DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED

- Upon

 

unpacking your Simplex product, inspect the contents of the carton for shipping damage. If 
damage is apparent, immediately file a claim with the carrier and notify an authorized 
Simplex

 

product supplier.

 

 

ELECTRICAL HAZARD 

- Disconnect electrical field power when making any internal adjust-

ments or repairs. All repairs should be performed by a representative or authorized agent of 
your local Simplex product supplier. 

 

STATIC HAZARD 

Static electricity can damage components. Handle as follows: 

 

Ground yourself before opening or installing components. 

 

Prior to installation, keep components wrapped in anti-static material at all times. 

 

FCC RULES AND REGULATIONS – PART 15 

- This equipment has been tested and 

found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC 
Rules. These limits are designed to provide reasonable protection against harmful 
interference when the equipment is operated in a commercial environment. This equipment 
generates, uses, and can radiate radio frequency energy and, if not installed and used in 
accordance with the instruction manual, may cause harmful interference to radio 
communications. Operation of this equipment in a residential area is likely to cause harmful 
interference in which case the user will be required to correct the interference at his own 
expense. 
 

 

SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES

 

-

 To ensure 

proper system operation, this product must be tested in accordance with NFPA72-1996, 
Chapter 7 after any programming operation or change in site-specific software.  
Reacceptance testing is required after any change, addition or deletion of system components, 
or after any modification, repair or adjustment to system hardware or wiring. 
 
All components, circuits, system operations, or software functions known to be affected by a 
change must be 100% tested.  In addition, to ensure that other operations are not 
inadvertently affected, at least 10% of initiating devices that are not directly affected by the 
change, up to a maximum of 50 devices, must also be tested and proper system operation 
verified. 

 

 

 

 

 

Cautions and Warnings 

firealarmresources.com

Содержание 4100-5101

Страница 1: ...XNAC This product is compatible with 4100U and 4100ES Fire Alarm Control Panels FACP IMPORTANT Verify FACP System Programmer Executive and Slave Software compatibility when installing or replacing sy...

Страница 2: ...Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate r...

Страница 3: ...across all 3 circuits when those circuits are used as special applications NACs The XPS has a 9 A capacity Each NAC is rated at 3 A A NAC can also be configured as an auxiliary power point in which c...

Страница 4: ...ED LED4 XNAC CONNECTOR P3 NAC TERMINAL BLOCK TB1 NAC STATUS LEDs LED1 LED2 LED3 BATTERY TROUBLE LED LED5 DEVICE ADDRESS DIP SWITCH SW1 SIGNAL POWER CONNECTOR P1 POWER COMMS OUTPUT TO NEXT PDI P2 3 A N...

Страница 5: ...uring initialization of the XPS LEDs 1 2 3 illuminate because the NACs are held in the isolate stage and create an open circuit trouble Table 1 summarizes the input and output specifications for the X...

Страница 6: ...inst the back of the expansion bay Connect to the PDI as shown in Figure 2 Correctly align the screw hole at the top of the XPS assembly with the hole in the bay chassis Use one 6 torx screw to secure...

Страница 7: ...4100 CPU Set this switch to ON to communicate SW1 2 through SW1 8 These switches set the card s address within the 4100 FACP Refer to Table 2 for a complete list of the switch settings for all of the...

Страница 8: ...ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON 29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF 30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON 31 ON ON OFF OFF OFF OFF OFF 91 OFF ON...

Страница 9: ...PDM in the 4100U 4100ES connecting to a host FACP with two XPSs SPS XPS PDM BATTERY BATTERY BTRY AC XPS BTRY AC AC BTRY INCOMING AC POWER Figure 4 System Power The instructions in this section describ...

Страница 10: ...twice through the bead as shown in Figure 5 Figure 5 Loop wires through bead as shown 2 Wire 120 220 230 240 VAC to the PDM keeping AC wires at least 1 inch away from all other wires AC power must st...

Страница 11: ...connection point 5 Repeat step 4 for the second XPS if applicable P1 P2 P3 P4 P5 Figure 6 XPS PDM Connection Step 3 Internal Wiring Continued Power Distribution Module Connections RED WIRE BLACK WIRE...

Страница 12: ...when the front panel is lowered Connect the separate red and black wires with yellow female terminations to plugs P4 black and P5 red on the XPS 2 For AC wiring connect the white and black wires Harn...

Страница 13: ...m 1 2 Ohms 1 50 A 70 ft 21 m 111 ft 34 m 177 ft 54 m 282 ft 86 m 1 Ohm 1 75 A 60 ft 18 m 95 ft 29 m 152 ft 46 m 242 ft 74 m 0 86 Ohm 2 A 53 ft 16 m 83 ft 25 m 133 ft 41 m 211 ft 64 m 0 75 Ohm 2 25 A 4...

Страница 14: ...m 222 ft 68 m 354 ft 108 m 564 ft 172 m 2 Ohms 1 75 A 120 ft 37 m 191 ft 58 m 304 ft 93 m 483 ft 147 m 1 71 Ohms 2 A 105 ft 32 m 167 ft 51 m 266 ft 81 m 423 ft 129 m 1 5 Ohms 2 25 A 93 ft 28 m 148 ft...

Страница 15: ...current must be deducted from the total 9 A available current All wiring that leaves the building requires overvoltage protection Install module 2081 9044 3 A or 2081 9028 A inside a UL Listed electr...

Страница 16: ...s any given SPS RPS or XPS must be from either Table 5 or Table 6 mixing of appliances from both tables is not possible within a power supply For use with Notification Appliances not listed in Table 5...

Страница 17: ...4 Repeat steps 1 through 3 for each NAC output you want to use 5 Leave the 10 K factory installed W brown black orange resistor 378 030 on each unused circuit The circuit must connect B to B terminal...

Страница 18: ...t steps 1 through 3 for each NAC output you want to use 5 Leave the 10 K W brown black orange resistor 378 030 on each unused circuit The circuit must connect B to B terminals B B A A B B A A B B A A...

Страница 19: ...leaves the building requires overvoltage protection Install module 2081 9044 3 A or 2081 9028 A inside a UL Listed electrical box wherever wire enters or exits the building A maximum of four 2081 9044...

Страница 20: ...AC 1 Insert plastic standoffs 202 078 and a metal standoff 202 077 to the XPS as shown in Figure 12 2 Plug J1 on the XNAC into P3 on the XPS using a header 166 549 The holes on the edges of the XNAC s...

Страница 21: ...ected or is depleted The precise status of the battery is given by the SPS These modules report Low Battery This trouble is merely to indicate a wiring problem to the XPS blown fuse not connected etc...

Страница 22: ...oards XPS P2 on Motherboards Pin 1 5 TXD Pin 2 6 COMMON Pin 3 7 RCV Pin 4 8 CODE P3 on Motherboards Pin 1 5 8 C Pin 2 6 8 V Pin 3 7 24 C Pin 4 8 24 V P2 4 wires blue wire on top 2 wires white wire on...

Страница 23: ...ITE FREE RUN TNA 4904 9332 V O 75CD RED SYNC TNA 4904 9343 V O 75CD WHITE SYNC TNA 4904 9170 V O 110CD RED FREE RUN TNA 4904 9173 V O 110CD WHITE FREE RUN TNA 4904 9175 V O 24VDC 110CD RED VER F S 490...

Страница 24: ...70V TNA 4903 9358 S V 110CD RED 25 70V TNA 4903 9361 S V 110CD WHITE 25 70V TNA 4903 9198 S V 110CD RND TNA 4906 9151 S V 15 30 75 110cd W M RED TNA 4906 9153 S V 15 30 75 110cd W M WHT TNA 4906 9154...

Страница 25: ...4903 9431 A V 15CD WHITE STD TNA 4903 9432 A V 75CD WHITE STD TNA 4903 9433 A V 110CD WHITE STD TNA 4906 9127 A V 15 30 75 110cd W M RED 4906 9129 A V 15 30 75 110cd W M WHT 4906 9128 A V 15 30 75 110...

Страница 26: ...iling Mount 12 24V 3dB 8Cd 5Mount HSWC HN STR White 2 Wire Ceiling Mount 12 24V 3dB 8Cd 5Mount HSRCS HN STR Silver Red 2 Wire Ceiling Mount 12 24V 3dB 8Cd 5Mount HSWCS HN STR Silver White 2 Wire Ceili...

Страница 27: ...24V 8Cd 5 Mount STWCS STR Silver White 2 Wire Ceiling Mount 12 24V 8Cd 5 Mount ZRS MCW ZRS Series Strobe 24V Multi Cd Wall Mount ZRS MCWH ZRS Series Strobe 24V Multi High Cd Wall Mount ZRS 24MCC ZRS...

Страница 28: ...Mount E50A 24MCC E50B 24MCC E50 Series Speaker Strobe 24V Multi Cd Ceiling Mt Amber Blue E60 24MCW E60 Series Speaker Strobe 24V Multi Cd Wall Mount E60 24MCWH E60 Series Speaker Strobe 24V Multi Hig...

Страница 29: ...ies Horn 24V AH 24WP AH Series Weatherproof Horn 12V or 24V HNR Horn Red 2 Wire Wall 12 24V 3dB 5 Mount HNW Horn White 2 Wire Wall 12 24V 3dB 5 Mount HNRS Horn Silver Red 2 Wire Wall 12 24V 3dB 5 Moun...

Страница 30: ...574 772 Rev K firealarmresources com...

Отзывы: