4

Table 4 provides a description of trouble flags and other diagnostic data for the
data reader.  The example shown is with the following diagnostic data:

450E4C3E400E410E551B*

Table 4.  Diagnostic Data

Byte

Description

Value

Example

1

Synchronization Nibble and
Product Identification Nibble

(SYNC) 

HEX

15 = (not yet assigned)
25 = (not yet assigned)
35 = 4098-9601
35 = 4098-9605
35 = 4098-9607
45 = 4098-9602
55 to 58 = (for R&D use only)
59 to 5F  (not yet assigned)

45 

HEX  

= Indicates Device

4098-9602

2

Sample Pulse

(PULSLO) 

HEX

smoke sample value

0E 

HEX 

= 14 

DEC

3

Alarm Threshold

(AT) 

HEX

factory calibrated alarm threshold value

4C 

HEX

 = 76

 DEC

4

Alarm Threshold - Factory
Clean Air

(DELTA) 

HEX

factory calibrated alarm delta value

3E 

HEX 

= 62 

DEC

5

Trouble and Status Flags

(STATUS)

 HEX

(Several flags could be set
simultaneously therefore the
Hex code should be translated
to binary to see which bits
have been set.)  See Table 5.

8  7  6  5  4  3  2  1 (BIT)

High sensitivity
(chamber contamination > 

/2)

Exceeded limit to chamber
compensation
Magnet test mode
Factory test mode
Thermistor alarm
Thermistor test error
(thermistor open)
Manufacturing location
(1=Westminster, 0 =other)

Alarm

40 

HEX 

= 01000000 

BIN

BIT 7 Indicates manufacturing
location is Westminster

6

Mfg-Cal.Year  (5 bits = 32
years) + P/O Week # Data
(3 bits)

(CAL-MSB)

 HEX

year=1996+first 5 bits (see example)

week # = last 3 bits of this byte + first 3 bits of next byte
(6 bits total)

0E 

HEX 

= 00001110 

BIN

Year = 00001 

BIN 

= 1 

DEC

Year = 1996 + 1 = 1997

7

P/O Week # Data (3 bits) +
Firmware Ver. (5 bits)

(CAL-LSB)

 HEX

First 3 bits are the rest of the week # data (of previous
byte) last 5 bits are the firmware version (up to 32
versions)

41 

HEX 

= 01000001 

BIN

Week = 110010 

BIN 

= 50 

DEC

Week = 50
Rev = 00001 

BIN 

=1 

DEC

Rev. 1

8

Sample Pulse Average Value

(RAAV)

 HEX

Chamber compensation value, used to adjust the actual
alarm threshold

0E 

HEX

 = 14 

DEC

9

Thermistor Value
[4098-9602 ONLY]*

(THMVAL) 

HEX

Thermistor ramp count, used to calculate the
temperature value
TEMP (F

°

) = [THMVAL 

DEC

/2] + 27

55 

HEX 

= 85 

DEC

[85/2] + 27 = 70

°

 F

9/10

Check sum

(CHKSUM)

 HEX

Count used to verify data integrity of bit stream

1B 

HEX 

= 27 

DEC

*

Model Number 4098-9602 outputs 10 bytes of data.  All other models output 9 bytes.

Diagnostic Data

Information in shaded cells are not for field use