background image

Wiring Overview

The Class A Adapter has one Signal Line Circuit (SLC) for power and communication wiring
Once installed on the repeater, the TB1 on the Class A Adapter replaces the TB1 IDNAC OUT on the repeater. It’s important that nothing be connected

to the repeater’s TB1.

Figure 4: Use the Class A Adapter terminal block

page 3

579-1080  Rev. F

4009-9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide

Содержание 4009-9814

Страница 1: ...r more information on the 4009 IDNAC Repeater referred to as Repeater from this point on in the manual Card specifications Table 1 Card specifications Card Specifications Operating Conditions 32 o F 120 o F 0 o C 49 o C Up to 93 relative humidity at 90 o F 32 o C non condensing Electrical Specifications IDNAC Output 29V Special application 3A Max IDNAC Input for Class A Extension mode 4 unit loads...

Страница 2: ...d J2 on the Repeater and jumper J1 on the Class A Adapter card must be set to the same setting For a local Class A loop To create a Class A local loop off of the repeater set the jumper to the Local setting jumper position 1 2 For an extended Class A loop To make the repeater part of a Class A loop extending from a DCAI set the jumper to the Class A Ext setting jumper position 2 3 Figure 3 Class A...

Страница 3: ...installed on the repeater the TB1 on the Class A Adapter replaces the TB1 IDNAC OUT on the repeater It s important that nothing be connected to the repeater s TB1 Figure 4 Use the Class A Adapter terminal block page 3 579 1080 Rev F 4009 9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide ...

Страница 4: ...rs of the IDNAC circuit reside in the same metal conduit and only under certain conditions Check with your local sales office before using wiring that is not twisted pair Device wiring guidelines Review the following guidelines for devices before you begin the field wiring Only IDNAC devices and other compatible devices are allowed on the SLCs Consult the Extended Power Supply manual 579 1015 for ...

Страница 5: ...Class A Loop Mode Configuration Note To achieve this a 4100 6103 Dual Class A Isolator DCAI must be part of the EPS configuration manual 579 1029 The Extended Class A Loop Mode does not support the 4905 9929 TrueAlert Isolator Module To wire the Repeater as part of an Extended Class A loop 1 Route the wire coming from the DCAI to the A and the A inputs on the Class A Adapter terminal block that is...

Страница 6: ...Figure 7 Extended Class A loop wiring page 6 579 1080 Rev F 4009 9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide ...

Страница 7: ...card 1 Open or create a job in the ES Programmer 2 Open the Hardware Tab 3 Double click on the Icon of the EPS module that the Class A Adapter s 4009 IDNAC Repeater is installed on to open the Properties window 4 Open the Point Editing tab 5 Select the Repeater in the Select Device drop down menu 6 Go to the Repeater Operation drop down menu and select the setting that represents the jumper config...

Страница 8: ...nal listings may be applicable contact your local Simplex product supplier for the latest status Listings and approvals under Simplex Time Recorder Co Simplex and the product names listed in this material are marks and or registered marks Unauthorized use is strictly prohibited NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association NFPA ...