9-8
4007ES Panel Programmer Manual (
579-1167)
Custom Control,
Continued
Adding Output
Statements
The third step in creating a new Custom Control equation is to add output statements to the new
equation. Repeat the steps in this section until all output statements in the equation have been
defined.
1. In the Equations box, position the cursor just to the right of [OUTPUTS].
2. Click on the
Add
button. The dialog shown in Figure 9-11 appears.
3. Click on the drop-down list box, select one of the output Opcodes, and click the
Next
button.
Opcode available: Select Item, Set/Reset Priority, Select Point.
4. The next dialogs displayed by the wizard depend on the Opcode you selected in Step 3.
Follow the Wizard’s windows to create the output for the equation.
5. The
Finish
button becomes available when all dialogs related to the output Opcode have
appeared. Click it to finish defining the output statement.
Floor Above/Floor
Below Wizard
This application limits the activation of NACs to the floor on which the activated initiating
device is located, referred to as the fire floor, and the floors immediately above and below the
fire floor.
Figure 9-12. Floor Above/Below
In Figure 9-12, an activated smoke detector or pull station on Floor 3 activates the NACs on
Floors 2, 3, and 4.
Содержание 4007ES Panels
Страница 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 18: ......
Страница 36: ......
Страница 56: ......
Страница 122: ...9 38...
Страница 132: ......
Страница 134: ......
Страница 150: ......
Страница 166: ...A 16...
Страница 167: ......