9-36
4007ES Panel Programmer Manual (
579-1167)
Custom Control
, Continued
Step 1. Creating a
New Self-Test
5. The next screen, shown in Figure 9-41, specifies the
Custom Control Program Number
.
This is the program number under which the self-test custom control equations created by
the wizard are stored. No specific program number is reserved for use by Self-Test
equations. Click
Next
.
Figure 9-41. Initial Data Screen
Step 2. Selecting
Start Time and
Frequency of the
Self-Test
To select time and frequency of the Self-Test:
1. In
the Self-Test Start Time
area select the time to run the Self-Test.
2. In
Recurrence Pattern
, click the frequency and the day that the self-test is going to run.
3. Click
Next
.
Figure 9-42. Self-Test Time and Recurrence (Weekly Configuration Shown as an Example)