Страница 2: ...firealarmresources com...

Страница 3: ...iver Body 6 Terminal Layouts 7 Wiring Connections 8 Adjustment Procedure 10 Operating Instructions 12 Maintenance 13 Specifications 14 Troubleshooting 16 Appendix Sensitivity Selection 17 IMPORTANT Fa...

Страница 4: ...firealarmresources com...

Страница 5: ...ar infrared wavelength leave the detector s transmitter and enter the photo diode of the detector s receiver The resultant analog signals are then amplified converted to digital information and entere...

Страница 6: ...the detector goes into alarm a Form B contact transfers opens when the detector goes into trouble In addition two dry Form A contacts are provided for remote annunciation one closes when the detector...

Страница 7: ...d See Section 4 l to 4 5 of NFPA 72E Precautions l The linear space separating the detector s transmitter from its receiver must be obstacle free l Both the transmitter and receiver should be mounted...

Страница 8: ...MONITOR LED GREEN TROUBLE LED AMBER BASE OPTICAL AXIS CLAMP CONNECTING FIXTURE CHAIN HOOK MONITOR COVER COVER SETSCREW LENS COVER f SIGHT HOLE OUTPUT CONTROL FINE ADJUSTMENT COARSE ADJUSTMENT SENSITI...

Страница 9: ...to the base adaptor with the 8 32 x l 2 screws provided 5 Wire the detector base into the fire alarm system 6 7 see pages 8 and 9 Attach the back box cover to the back box Mount the transmitter or re...

Страница 10: ...to the box with the 8 32 x 1 3 8 screws provided 4 Mount the transmitter or receiver body see below Mounting the Transmitter or Receiver Body 1 Align the register mark on the body with that on the bas...

Страница 11: ...RITY RECEIVER Note Black circles indicate free terminals Receiver REMOTE TROUBLE SIG N O BROWN VIOLET REMOTE FIRE SIG N O REMOTE SIG COMMON LINE TROUBLE FIRE REMOTE PINK rJI TEST YELLOW 4 GREEN TROUBL...

Страница 12: ...D I I I I I I I I CONTROL PANEL WITH FAULT INDICATOR NEXT DETECTORS BASIC CONNECTION 1F FIRE SIGNAL CONTACT NORMALLY OPEN _____ O T O 1T TROUBLE SIGNAL CONTACT NORMALLY CLOSED 2F REMOTE FIRE SIGNAL CO...

Страница 13: ...MITTER EMITTER BASIC CONNECTION OPTION Notes 1 When wired as shown a detector trouble signal takes the form an initiating device circuit trouble at the control panel 2 The 24VDC supplied to the detect...

Страница 14: ...or cover found on the back of the receiver l The cover s left hand screw must be removed the cover s right hand screw need only be loosened it cannot be removed 2 Check to see that the red LED inside...

Страница 15: ...entarily press the SET switch Then wait 20 seconds l If the detector issues a trouble signal during the 20 second wait turn the SENSITIVITY SELECT switch OFF and repeat steps 1 2 and 3 above 4 Remove...

Страница 16: ...emission to auto SET Approx 90 sets after start of emission From auto SET to start of normal monitor condition Approx 10 sets after auto SET START OF POWER UP EMISSION NORMAL MONITOR APPROX 90 SECS C...

Страница 17: ...ter and receiver lens covers B Check for loose connections between the base and the detector body C Check the chain and hook connection D Check the optical axis for deviation by looking through the si...

Страница 18: ...gnal compensation rate 3 Adjustment for quantity of beams 4 Photo signal monitor 5 Initial photo signal setting 6 Light receiving cycle time Transmitter Specifications 1 Light source 2 Light source dr...

Страница 19: ...aterial Diecast aluminium 4 Color Metallic silver 5 Mounting lock Wrench provided Detector Components No Contents Remarks 1 Transmitter 1 2 Receiver 1 3 Base for transmitter 1 2 leads 4 Base for recei...

Страница 20: ...the same checks as for a detector that stays in alarm see 4 above Is material blocking the optical axis E g a Remove the blocking material crane or some other moveable object Is quantity of beams pro...

Страница 21: ...tor s optimum sensitivity setting should be midway between the U2 and S lines with reference to the distance separating the detector s receiver from its transmitter I Example Ceiling height 45 ft 13 7...