Switches

Switch SW1 on the dual RS-232 interface module is a bank of eight DIP switches. From top to bottom (see Figure 2) these switches are designated as

SW1-1 through SW1-8. The function of these switches is as follows:

•  SW1-1. This switch sets the baud rate for the internal FACP communications line running between the card and the FACP CPU. Set this switch

to ON.

• •  SW1-2 through SW1-8. These switches set the card’s address within the FACP. Refer to Figure 3 for a complete list of the switch settings for all

of the possible card addresses.

Programmer.

Figure 2: Address DIP Switch

Note: 

You must set these switches to the value assigned to the card by the FACP.

page 3

579-910  Rev G

Dual RS-232 Interface Module 4007-9812, 4100-6046, 4010-9918 Installation Instructions

Содержание 4007-9812

Страница 1: ...repair or adjustment to system hardware or wiring All components circuits system operations or software functions known to be affected by a change must be 100 tested In addition to ensure that other...

Страница 2: ...able 1 lists the jumper settings for the range of devices that can be attached to the dual RS 232 interface module Refer to Figure 1 for the locations of the jumpers and their corresponding pin number...

Страница 3: ...mmunications line running between the card and the FACP CPU Set this switch to ON SW1 2 through SW1 8 These switches set the card s address within the FACP Refer to Figure 3 for a complete list of the...

Страница 4: ...Configuring the Dual RS 232 Flat Card Figure 3 FACP Daughter Card Addresses page 4 579 910 Rev G Dual RS 232 Interface Module 4007 9812 4100 6046 4010 9918 Installation Instructions...

Страница 5: ...nts on a PDI card in a FACP expansion box PID series 2975 94xx It can be mounted on any available block Refer to Figure 4 Figure 4 Installing the 4 X 5 Module in a 4100U 4100ES FACP Expansion Bay page...

Страница 6: ...le mounts on an available PDI block on the top bay or expansion bay PDI card provided there is enough space to fit the card Figure 5 Installing the Dual RS 232 Module in a 4010ES Panel page 6 579 910...

Страница 7: ...ect one end of the provided harness 734 308 to connector P7 on the back of the RS 232 card 2 Use the provided hardware to secure the RS 232 bracket to the 4007ES box 3 Connect the free end of the harn...

Страница 8: ...eeves are used the junction must be insulated with a high grade electrical tape that is as sound as the original insulating jacket Shield continuity must be maintained throughout A system ground must...

Страница 9: ...dressed and bundled together using the wire ties provided with the equipment Anchor power limited wiring to tie points as shown in Figure 8 Figure 8 Power Limited Wiring Tie the wiring located between...

Страница 10: ...al listings may be applicable contact your local Simplex product supplier for the latest status Listings and approvals under Simplex Time Recorder Co Simplex and the product names listed in this mater...