10.2.
TRANSMISSION ERRORS DESCRIPTION
If an error occurs while write or read of single register, then the device sends an error
code according to Modbus RTU specifications (example message no 1).
Error codes:
01h
- illegal function (only functions 03h, 06h and 10h are available),
02h
- illegal register address
03h
- illegal data value
08h
- no write permission ( see: “
mbAc
” parameter)
A0h
- exceed of upper border of input range
60h
- exceed of lower border of input range
A0h and 60h codes can appear only during reg. 01h is reading by 03h function (read of