User manual for  RTD,TC,mV/4-20mA converter module SPT-86L

5. 

   PRINCIPLE OF OPERATION

 

 

SPT-86L

 module allows the conversion of temperature and voltage on current in 4-20 mA 

standard. Present value of temperature or voltage is available as measurement register of 

device (reg. addr. 01h). I

f input signal exceeds the permissible range, shortcut or break of 

measurement circuit occur, appropriate error code will be set in 

status register

 (register 02h). 

Measurement input's parameters are located in the group of registers 

Input

” (see 

LIST

OF REGISTERS

 on page 

18

) and allow:

input type selection (parameter 

InputType

”) 

connection type selection (parameter ”

InputConn

”, applies only to RTD measurement),

change   of   the   filtration   degree   of   the   values   in   measurement   register   (parameter 

InputFilter

”),

shift   of   the   measurement   scale   (parameter   ”

InputOffset

”,   applies   only   to   temperature 

measurement),

processing characteristic setup (applies only to voltage measurement).

The proper operation of the module is signalized by flashing green LED diode placed on 

the front panel and labelled  

RUN

. The yellow LED diode (labelled  

RS-485

), by fast flashes, 

signalizes data transmission via serial interface. The red LED diode (labelled  

ERROR

), if lit, 

signalizes measurement error. It may mean that measured signal exceeded the permissible 

range, the sensor was damaged or wires' short circuit or break occurred.

Parameters are kept in non-volatile EEPROM memory. All parameters can be set via 

serial interface (see 

LIST OF REGISTERS

 on page 18

).

5.1. 

 

 VOLTAGE MEASUREMENT

 

 

Measurement   results   can   be   internally   recalculated   due   to   one   of   available 

characteristics: linear, square, square root or user definable multipoint (max. 20 points length). 
The expansion of nominal range is defined by 

InputHiRange

” 

parameter (see figure below).

Fig. 5.1 

Example of definition of permissible range of input signal - 

InputHiRange

” 

parameter (0-100 mV mode)

8

InputHiRange

” = 5,0 % (5 mV)

105

permissible measurement range

nominal measurement range (0-100 mV)

[mV]

100

120

0

U

max

range exceeded

range exceeded

Содержание SPT-86L

Страница 1: ...for RTD TC mV 4 20mA converter module SPT 86L Firmware v 1 00 or higher Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes wi...

Страница 2: ...OF QUERY ANSWER FRAMES 21 9 DEFAULT AND USER S SETTINGS LIST 23 Explanation of symbols used in the manual This symbol denotes especially important guidelines concerning the installation and operation...

Страница 3: ...nd voltage to current in 4 20 mA standard converter The device is equipped with one voltage input 0 150 mV one RTD input Pt 100 500 1000 and one TC thermocouple input K S J T N R B E The device automa...

Страница 4: ...igit Accuracy of cold ends temperature compensation 1 C Temperature stability 50 ppm C Galvanic isolation Supply input together with RS 485 interface measurement input and current output are all galva...

Страница 5: ...ics installation of the unit must be conducted correctly and according to the local regulations Read the basic safety requirements on page 2 prior to starting the installation Ensure that the power su...

Страница 6: ...operation of the unit must be applied To avoid the unit of improper indications keep recommendations listed below Avoid common parallel leading of signal cables and transmission cables together with p...

Страница 7: ...nents and shorten the fault free time of unit operation In cases where the unit gets dirty do not clean with solvents For cleaning use warm water with small amount of detergent or in the case of more...

Страница 8: ...only to voltage measurement The proper operation of the module is signalized by flashing green LED diode placed on the front panel and labelled RUN The yellow LED diode labelled RS 485 by fast flashe...

Страница 9: ...nts Coordinate X defines the percentage ratio of input value to selected measurement range The X range 99 9 199 9 Coordinate Y defines the value returned in measurement register for particular X coord...

Страница 10: ...is of the measurement result Before turning off the device it is recommended to first disable the current output s power supply and then the device itself If the current output is supplied while the d...

Страница 11: ...d fig 5 2 If no peaks are detected while time HoldTime elapses device returns the current value of input signal in the peak value register 06h register The current output can be controlled depending o...

Страница 12: ...by fixed coefficients determined by InputLow and InputHigh parameters when the normalized results is equal 0 then value InputHigh is returned and when the normalized results is equal 1 then value Inpu...

Страница 13: ...cteristic 6 1 4 User defined characteristic User defined characteristic is defined as set of X Y points Number of the points is variable and may be set from 2 to 20 points which make linear segments s...

Страница 14: ...le input range 0 100 mode If in 0 100 mode the user sets InputHiRange 10 0 then permissible input voltage range will be equal 0 110 mV Upper border of the range is the result of calculations 100 mV 10...

Страница 15: ...teristic Let assume the input mode 0 100 is chosen Parameter InputLow and InputHigh equal to 300 and 1200 respectively The calculations will be done for three different input voltages from example 2 a...

Страница 16: ...0 90 0 Y10 900 0 X11 100 0 Y11 820 0 Additionally all other points must to be defined and stored in the device memory a Uinp 37 5 mV and Un 0 375 The segment defined by X6 30 0 and X7 40 0 for this Un...

Страница 17: ...urrent output to 3 8 21 mA Output current will be calculated for three measurement values a W 175 According to formula from page 9 Iout 175 100 200 100 16 mA 4 mA 0 75 16 4 16 mA Calculated Iout do no...

Страница 18: ...9 9999 Measurement value no decimal point 02h No 0h A0h 60h C0h 10h 20h Status of the current measurement 0h data valid A0h top border of the measurement range is exceeded 60h bottom border of the mea...

Страница 19: ...ire Modbus group of registers 20h1 Yes 0 199 Parameter ModbusAddr device address 21h No 205Bh Device identification code ID 22h2 Yes 0 7 Parameter ModbusBaud baud rate 0 1200 bit sec 1 2400 bit sec 2...

Страница 20: ...9 Parameter OutputLow no decimal point included A2h Yes 999 9999 Parameter OutputHigh no decimal point included A3h Yes 0 499 Parameter OutputLoRange expressed in 0 1 A4h Yes 0 99 Parameter OutputHiRa...

Страница 21: ...cription ADDR Device address on modbus network FUNC Function code REG H L Starting address address of first register to read write Hi and Lo byte COUNT H L No of registers to read write Hi and Lo byte...

Страница 22: ...essage ADDR FUNC REG H L DATA H L CRC L H 01 06 00 20 00 02 09 C1 4 Read of the registers 1 2 and 3 in one message example of reading a number of registries in one frame ADDR FUNC REG H L COUNT H L CR...

Страница 23: ...de Current output mode measured value OutLow Measured value for which 4 mA is generated 0 0 OutHigh Measured value for which 40 mA is generated 100 0 OutLoRange Extension of the bottom of the nominal...

Страница 24: ...SIMEX Sp z o o ul Wielopole 7 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Отзывы: