User manual for regulated current source SZP-73
5. Read of the registers 6, 7 and 8 in one message (example of reading a number of
registries in one frame):
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
01
03
00
06
00
03
E5
CA
COUNT L - the count of being read registers (max.16)
The answer:
ADDR
FUNC
BYTE C DATA H1,L1
DATA H2,L2
DATA H3,L3
CRC L,H
01
03
06
01
90
07
D0
00
02
61
F5
DATA H1, L1 - reg. 06h (0190h - it means that
”OUtL”
= 400),
DATA H2, L2 - reg. 07h (07D0h - it means that
”OUtH”
=2000 ),,
DATA H3, L3 - reg. 08h (0002h - it means decimal point position = ” 0.00”).
There is no full implementation of the Modbus Protocol in the device. The
functions presented above are available only.
9.
DEFAULT AND USER'S SETTINGS LIST
Parameter
Description
Default value
User's value
Desc.
page
OutL
Value displayed for current equal 4 mA
0
OutH
Value displayed for current equal 20 mA
100.0
Pnt
Decimal point position
0.0
Init
Mode of i current value initialisation
UdEF
IvAL
Current after power on (if
Init
is set to
UdEF)
4.00
Display parameters
bri
Display brightness
bri6
CoL
Basic colour of the display
grEE
RS 485 interface configuration (menu “rS”)
Addr
Device address
0
bAud
Baud rate
9.6
mbAc
Permission to changes of configuration registers
on
rESP
Additional delay of answer transmission
Std
Configuration of numerical parameters edition
Edit
Numerical parameters edit mode
dig
23